3-13
400V Class : Single phase. F : Standards for built-in filter
Model : L510-
□□□
-H3-N A
(L510-
□□□
-H3F-P A)
401 402 403
Horse power (HP)
1
2
3
Suitable motor capacity (KW)
0.75
1.5
2.2
Rated output current (A)
2.3
3.8
5.2
Rated capacity (KVA)
1.7
2.9
4.0
Input voltage range(V)
Three Phase : 380~480V,50/60HZ
Allowable voltage fluctuation
+10%-15%
Output voltage range(V)
Three phase 0~480V
Input current (A)
4.2
5.6
7.3
Allowable momentary power loss time (S)
2.0
2.0
2.0
Enclosure IP20
(Models of 400V machines are all marked A, built in the power supply of 24V.)
*The input current is calculated value at full rated output current.
3.4.2
General Specifications
Item
L510
Control Mode
V/F C Auto-torque compensation function
Range
0.01~650.00Hz
Digital input : 0.01Hz
Setting resolution
Analog input : 0.06Hz/60Hz
Keypad : Set directly with
▲▼
keys or the VR (Potentiometer)
on the keypad
External Input Terminals:
AVI(0/2~10V), ACI(0/4~20mA)input
Multifunction input up/down function(Group3)
Setting
Setting frequency by Communication method.
Frequency
Frequency limit
Lower and upper frequency limits
3 -skip frequency settings.
Keypad run, stop button
External terminals:
Multi- operation-mode 2 / 3 wire selection
Jog operation
Run
Operation set
Run signal by communication method.
V / F curve setting
6 fixed curve and one customized curve
Carrier frequency
1~16KHz(default 5KHz)
Acceleration and
deceleration control
2 off Acc / dec time parameters.
4 off S curve parameters.
Multifunction input
19 functions (refer to description on group3)
Multifunction output
14 functions (refer to description on group3)
Multifunction analog
output
5 functions (refer to description on group3)
Commonly
Control
Main features
Overload Detection, 8 preset speeds, Auto-run, Acc/Dec
Switch (2 Stages), Main/Alt run Command select, Main/Alt
Frequency Command select, PID control, torque boost, V/F
start Frequency ,Fault reset, Firemode.