4-11
Group 02: Motor Parameters
02-13
SLV Slip
Compensation Gain
0~150
by series
%
02-14
SLV Torque Compensation Gain
0~100
100
%
02-15
Low Frequency Torque Gain
0~100
50
%
02-16
SLV Without Load Slip
Compensation Gain
0~200
by series
%
02-17
SLV With Load Slip Compensation
Gain
0~200
150
%
Group 03: External Digital Input and Output Parameters
Code
Parameter Name
Setting Range
Default
Unit
Notes
03-00
Multi-function Terminal Function
Setting-S1
0: Forward/Stop Command or Run /Stop
1: Reverse/Stop Command Or REV/FWD
2: Preset Speed 1 (5-02)
3: Preset Speed 2 (5-03)
4: Preset Speed 4 (5-05)
6: Jog Forward Command
7: Jog Reverse Command
8: Up Command
9: Down Command
10: Acc/Dec 2
11: Acc/Dec Disabled
12: Main/Alternative Run Command select
13: Main/Alternative Frequency Command select
14: Rapid Stop ( Decel to stop)
15: Base Block
16: Disable PID Function
17: Reset
18: Auto Run Mode enable
0
-
03-01
Multi-function Terminal Function
Setting-S2
1
-
03-02
Multi-function Terminal Function
Setting-S3
2
-
03-03
Multi-function Terminal Function
Setting-S4
3
-
03-04
Multi-function Terminal Function
Setting-S5
17
-
03-05
Reserved
03-06
Up/Down Frequency Band
0.00~5.00
0.00
Hz
03-07
Up/Down Frequency Modes
0: When Up/Down is used, the preset frequency
is held as the inverter stops, and the UP/Down
function is disabled.
0
-
1: When Up/Down is used, the preset frequency
is reset to 0 Hz as the inverter stops.
2: When Up/Down is used, the preset frequency
is held as the inverter stops, and the UP/Down is
available.
03-08
S1~S5 Scan Confirmation
1~200. Number of Scan cycles
10
2ms
03-09
S1~S5 Switch Type Select
xxxx0:S1 NO xxxx1:S1 NC
00000
-
xxx0x:S2 NO xxx1x:S2 NC
xx0xx:S3 NO xx1xx:S3 NC
x0xxx:S4 NO x1xxx:S4 NC
03-10
Reserved
03-11
Output Relay (RY1)
0:Run
0
-
1:Fault
2:Setting Frequency Reached
3:Frequency Reached (3-13±3-14)
4:Output Frequency Detection1(> 3-13)
5:Output Frequency Detection2(< 3-13)
6:Auto-Restart