4-12
Group 03: External Digital Input and Output Parameters
Code
Parameter Name
Setting Range
Default
Unit
Notes
7:Momentary AC Power Loss
8:Rapid Stop
9:Base Block
10:Motor Overload Protection(OL1)
11:Drive Overload Protection(OL2)
12:Reserved
13:Output Current Reached
14:Brake Control
15:PID feedback disconnection detection
03-12
Reserved
03-13
Output frequency detection level (Hz) 0.00~599.00
0.00
Hz
*1
03-14
Frequency Detection band
0.00~30.00
2.00
Hz
*1
03-15
Output Current Detection Level
0.1~15.0
0.1
A
03-16
Output Current Detection Period
0.1~10.0
0.1
s
03-17
External Brake Release
level
0.00~20.00
0.00
Hz
03-18
External Brake Engage
Level
0.00~20.00
0.00
Hz
03-19
Relay Output Function Type
0: A (Normally Open)
0
-
1: B (Normally Closed)
03-20
Braking Transistor On Level
100.0~800.0
220v:380
380/400v:
690
415/460v:
780
VDC
03-21
Braking Transistor Off Level
100.0~800.0
220v:340
380/400v:
670
415/460v:
760
VDC
Group 04: External Analog Input and Output Parameters
Code
Parameter Name
Setting Range
Default
Unit
Notes
04-00
AVI/ACI analog Input signal type
select
AVI ACI
0
-
0:0~10V 0~20mA
1:0~10V 4~20mA
2:2~10V 0~20mA
3:2~10V 4~20mA
04-01
AVI Signal Verification Scan rate
1 ~ 200
100
2ms
04-02
AVI Gain
0 ~ 1000
100
%
*1
04-03
AVI Bias
0 ~ 100
0
%
*1
04-04
AVI Bias Selection
0: Positive
0
-
*1
1: Negative
04-05
AVI Slope
0: Positive
0
-
*1
1: Negative
04-06
ACI Signal Verification Scan rate
1 ~ 200
100
2ms
04-07
ACI Gain
0 ~ 1000
100
%
*1
04-08
ACI Bias
0 ~ 100
0
%
*1
04-09
ACI Bias Selection
0: Positive
0
-
*1
1: Negative
04-10
ACI Slope
0: Positive
0
-
*1