Operation in Warning and Fault Status
WARNING
Led
Short circuit
LED5, LED6 on
Overload fault
LED5 on, LED6 flashing
Bad battery
LED5, LED7 on
Charger under voltage
LED5 on, LED7 flashing
Charger over voltage
LED5 on, LED7 flashing
Charger failure
LED5 on, LED7 flashing
Inverter fault
LED1, LED5 on
PFC fault
LED1 flashing, LED2, LED5 on
DC/DC fault
LED2, LED5 on
Over-temperature
LED3 flashing, LED5 on
DC BUS over voltage
LED2 flashing, LED5 on
Output over voltage
LED1, LED5 on
Battery disconnected
LED5, LED7 flashing
Low battery
LED7 flashing
Overload warning
LED6 flashing
Out of bypass range
LED3, LED5 flashing
Other warning
LED5 flashing
Warning Table
9
Communication Interfaces
The UPS is factory-equipped with
USB Communication Interfaces
. On the UPS rear side there are the connections
of the Interfaces.
To activate USB communication it is sufficient to connect the USB cable only.
The USB signals are all isolated through photo-couplers from the dangerous voltages that are present inside
the UPS.
Connecting to the Web site
www.tecnoware.com,
it is possible to download, free of charge, the update UPS
management Software, compatible with the most popular Operative Systems.