UPS EVO DSP PLUS 

11

 

User’s manual 

8

 

Functioning 

8.1

 

Turning ON and OFF 

Let’s see carefully the consequences of the pressure of 

ON/OFF 

buttons. 

The UPS is in Stand-by mode (the Inverter is OFF);

 

if the 

ON/OFF

 button is pressed, after few seconds the Inverter 

starts and the UPS switches in Normal mode. 

The UPS is in Normal mode

 

(the Inverter is ON);

 

if the 

ON/OFF

 button is pressed, the Inverter turns OFF and the 

UPS switches in Stand-by mode. 
 

 

To turn completely OFF the UPS please do the following steps: 

 

Put the UPS in Stand-by mode by pressing the ON/OFF button 

 

Disconnect the AC Input Voltage for the UPS. 

The Led panel is OFF only when the UPS is completely OFF. 

 
If  UPS  is  used  daily,  it  is  recommended  to  leave  the  UPS  connected  to  the  AC  Input  line  and  use  the 

ON/OFF 

buttons on the front panel to activate/deactivate the Inverter. 

If the UPS has to be turn OFF completely for several days, it is recommended to disconnect the AC Input line for 
the UPS and then press the 

ON/OFF

 button.  

If the 

ON/OFF

 button is pressed when AC Input line is not present, the UPS switches ON even, and works in Battery 

mode after some seconds. 

If the 

OFF

 button is pressed when AC Input line is not present, then the Inverter switches OFF and consequently 

there will be no Output power. 
 

8.2

 

Low Battery and Automatic Restart 

The  UPS  reaches  the 

Low

 

Battery 

condition

 

whenever,  during  working  in  Battery  mode,  the  batteries  reach  a 

charge level allowing the connected devices to operate for few minutes more. 

The  UPS  warns  operators  of 

Low

 

Battery 

by  lighting  of  the 

LOW  BATT. 

led  on  led  panel  and  by  emitting  an 

acoustic signal every second. 

If  AC  Input  does  not  come  back  on  within  few  minutes,  the  UPS 

shuts-down  automatically

  thus  preventing  the 

batteries from discharging excessively; the UPS stops supplying Output power, deactivates control panel indication 
and goes to a waiting state. Once AC Input comes back on, the UPS

 restarts automatically 

and after 4 seconds it 

goes back to work in Normal mode. 

After  a  complete  discharge,  the  UPS  needs  4  hours  to  recharge  completely  the  batteries.  The  UPS  recharges 
batteries automatically if it works in Normal mode, in Bypass mode or in Stand-By mode. 

 

 

 

 

 

 

 

 

Содержание UPS EVO DSP PLUS 1.0 MM

Страница 1: ...UPS EVO DSP Plus 1 0 MM Uninterruptible Power Supply User s manual Manuale utente...

Страница 2: ......

Страница 3: ...2 Rear Side 8 6 Electrical Installation 9 6 1 Installation 9 7 First Start Up 10 8 Functioning 11 8 1 Turning ON and OFF 11 8 2 Low Battery and Automatic Restart 11 8 3 Load Testing 12 8 4 Static Byp...

Страница 4: ...osteriore 26 6 Installazione Elettrica 27 6 1 Installazione 27 7 Prima Accensione 28 8 Funzionamento 29 8 1 Accensione e Spegnimento 29 8 2 Fine Autonomia e Riaccensione Automatica 29 8 3 Controllo de...

Страница 5: ...ed by producer The producer declines any responsibility if this warning is disregarded The electric installation has to be done by qualified personnel Follow all the Safety Standards CEI Standards in...

Страница 6: ...ents spikes interferences etc thus protecting the devices connected to its outlets During a power failure EVO DSP PLUS continues supplying adequate AC power with a true sine wave to all connected devi...

Страница 7: ...in case you need to send the UPS for maintenance purposes In case of transport damage notify the carrier and dealer immediately We recommend paying attention to the below points in order to choose a c...

Страница 8: ...ENGLISH User s manual 4 UPS EVO DSP PLUS 4 Operating Modes Figure 1 Operating modes BATTERY MODE NORMAL MODE BYPASS MODE...

Страница 9: ...kout or Overvoltage Brownout it then switches into Battery mode In this case the batteries supply the required Output power thanks to the DC AC conversion carried out by the Inverter The UPS switches...

Страница 10: ...and the AC Input line is removed from UPS then the UPS switches completely off The Stand by mode is identified by The Led panel LED4 LED 7 are on see fig 3 5 EXTERNAL DESCRIPTION 5 1 Front Panel The f...

Страница 11: ...ser s manual 5 1 1 LED Panel Please refer to figure 3 LED1 Line MODE LED2 Battery MODE LED3 Bypass MODE LED4 Power ON LED5 Warning or Fault LED6 LOAD LEVEL LED7 BATTERY LEVEL Figure 3 Led Panel 1 13 4...

Страница 12: ...coustic Alarm Battery Mode Beeping once every 4 seconds Low Battery Beeping once every second Overload Beeping twice every second Fault Mode Beeping continuously 5 2 Rear Side Figure 4 Rear Side 1 Com...

Страница 13: ...k the grounding of AC line outlet 2 Connect the devices to be supplied to the UPS outputs Be sure all the devices have the main switch in OFF position It is compulsory to ground the UPS according to t...

Страница 14: ...in Normal Mode 5 Simulate a black out by removing the AC Input line The UPS starts working in Battery mode the led panel will show the path of energy during Battery mode Moreover UPS emits a brief ac...

Страница 15: ...on If the ON OFF button is pressed when AC Input line is not present the UPS switches ON even and works in Battery mode after some seconds If the OFF button is pressed when AC Input line is not presen...

Страница 16: ...er than than 130 Once the requested power is back within range the UPS switches automatically to the Normal mode Make sure that the UPS never indicates Overload condition Do not connect a load greater...

Страница 17: ...LED5 on Battery disconnected LED5 LED7 flashing Low battery LED7 flashing Overload warning LED6 flashing Out of bypass range LED3 LED5 flashing Other warning LED5 flashing Warning Table 9 Communicatio...

Страница 18: ...ac 5 Nominal Frequency 50 60 Hz automatic selection Frequency Range Normal mode 47 53 Hz 57 63 Hz Input Power Factor 0 99 at 100 Load OUTPUT Nominal Voltage Single Phase 220 230 240 Vac Voltage Regula...

Страница 19: ...ife Relative Humidity Range 0 95 non condensing Max Altitude without Derating 3000 m Protection level IP 20 Cooling Fan cooling Audible Noise at 1 meter 45 dBA STANDARDS Safety EN 62040 1 1 EN 60950 1...

Страница 20: ...UPS is ON and working in Normal or in Bypass mode for after approximately 4 hours with AC Input line present Battery life strongly depends on the ambient temperature There are also other factors like...

Страница 21: ...electric shock There are no internal parts in the UPS which are user serviceable Any repair or maintenance work must be performed exclusively by qualified technical personnel authorized by the produc...

Страница 22: ...ent and for human health A correct waste disposal of products having the dustbin symbol marked by a cross help to avoid negative consequences to the environment and to human health Lead Batteries mode...

Страница 23: ...zzato dal produttore In caso contrario il produttore declina ogni sua responsabilit L installazione elettrica nonostante la sua semplicit deve essere eseguita esclusivamente da elettricisti qualificat...

Страница 24: ...r grazie a questa doppia conversione il grado di protezione per il carico diventa assoluto Al verificarsi di una qualsiasi avaria della linea elettrica la potenza richiesta continua ad essere fornita...

Страница 25: ...rasporto annotarli sulla bolla di accompagnamento merce e contattare subito il fornitore Si consiglia di conservare l imballo originale in luogo sicuro nell eventualit futura che l UPS dovesse essere...

Страница 26: ...ITALIANO Manuale utente 22 UPS EVO DSP PLUS 4 Modi di Funzionamento Figura 1 Modi di Funzionamento MODO NORMALE MODO BYPASS MODO BATTERIA...

Страница 27: ...zione dell ampiezza della Tensione di Rete oltre le specifiche allora passa nel modo Batteria In questo caso sono le batterie che forniscono la potenza necessaria in Uscita grazie sempre alla conversi...

Страница 28: ...alcuni secondi Il modo Stand by caratterizzato da Il pannello Led mostra LED4 LED 7 accesi vedi fig 3 5 Descrizione Esterna 5 1 Pannello Frontale Il pannello frontale informa l utente sullo stato di f...

Страница 29: ...1 1 Pannello Led Prego riferirsi alla figura 3 LED1 Modalit Rete LED2 Modalit Batteria LED3 Modalit Bypass LED4 Acceso LED5 Allarme o avviso LED6 LIVELLO DEL CARICO LED7 LIVELLO BATTERIA Figura 3 Pan...

Страница 30: ...w Battery Fine Autonomia Allarme acustico ogni secondo Overload Allarme acustico 2 volte ogni secondo Condizioni di Guasto Fault Allarme acustico continuo 5 2 Pannello Posteriore Figura 4 Pannello Pos...

Страница 31: ...ica che deve avere obbligatoriamente una connessione a terra secondo le norme vigenti Verificare accuratamente il collegamento a terra della presa d alimentazione elettrica 2 Collegare i dispositivi d...

Страница 32: ...togliendo la Tensione di Rete elettrica in Ingresso L UPS passa a funzionare nel modo Batteria l UPS ogni 4 secondi emette un breve segnale acustico di allarme Quando l autonomia delle batterie si sta...

Страница 33: ...gresso l UPS si accende ugualmente dopo alcuni secondi attiva l Inverter e comincia a funzionare nel modo Batteria Se premuto il pulsante ON OFF quando non presente la Tensione di Rete elettrica in In...

Страница 34: ...di Overload scompare dopo alcuni secondi l UPS ricommuta automaticamente dal modo Bypass al modo di funzionamento Normale Controllare che l UPS non indichi mai la condizione di Overload Non applicare...

Страница 35: ...2 LED5 accesi Errore DC DC LED2 LED5 accesi Sovratemperatura LED3 lampeggiante LED5 acceso DC BUS alta LED2 lampeggiante LED5 acceso Tensione uscita alta LED1 LED5 acceso Batterie disconnesse LED5 LED...

Страница 36: ...quenza Nominale 50 60 Hz selezione automatica Range Frequenza modo Normale 47 53 Hz 57 63 Hz Fattore di Potenza d Ingresso 0 99 con carico al 100 USCITA Tensione Nominale Monofase 220 230 240 Vac Rego...

Страница 37: ...0 95 senza condensazione Altitudine Massima senza Declassamento 3000 m Livello di Protezione IP 20 Raffreddamento Forzato tramite ventole Rumorosit ad 1 metro 45 dBA CONFORMIT ALLE NORME Sicurezza EN...

Страница 38: ...Normale che in modo Stand by Lasciare l UPS in ricarica per circa 4 ore con la Rete elettrica sempre presente in ingresso La durata delle batterie dipende fortemente dalla temperatura dell ambiente d...

Страница 39: ...ivo contattare il Servizio Assistenza Rischio di shock elettrico Non smontare l UPS contiene parti sotto tensione che sono potenzialmente pericolose e possono provocare lesioni o morte per shock elett...

Страница 40: ...esidenziali questo prodotto pu produrre radio interferenza nel qual caso pu essere necessario adottare misure aggiuntive da parte dell utilizzatore Smaltimento del Prodotto Il prodotto EVO DSP PLUS no...

Страница 41: ......

Страница 42: ...TECNOWARE s r l www tecnoware com...

Отзывы: