10
Technical Characteristics
UPS EVO DSP MM Model
1.2
2.4
3.6
Power
1200 VA
2400 VA
3600 VA
Nominal Active Power
840 W
1680 W
2520 W
Power Factor
0.7
Technology
On-Line Double Conversion Transformerless
Dimension (W x H x D)
15 x 22 x 40 cm
19 x 32 x 42 cm
Net Weight
13 kg
26 kg
28 kg
INPUT
Nominal Voltage
Single Phase 208/220/230/240 Vac
110 Vac ± 5% (at 0-60% load)
120 Vac ± 5% (at 60-70% load)
140 Vac ± 5% (at 70-80% load)
Lower Limit (transfer
to Battery mode)
160 Vac ± 5% (at 80-100% load)
Lower Limit (come
back to Line mode)
175 Vac ± 5%
Upper Limit (transfer
to Battery mode)
300 Vac ± 5%
Voltage Range for
Normal mode
Upper Limit (come
back to Line mode)
290 Vac ± 5%
Nominal Frequency
50/60 Hz (automatic selection)
Frequency Range (Normal mode)
47 ~ 53 Hz / 57 ~ 63 Hz
Input Power Factor
0.99 (at 100% Load)
OUTPUT
Nominal Voltage
Single Phase 208/220/230/240 Vac (selectable)
Voltage Regulation
±2%
Inverter Waveform
True Sinewave
Nominal Frequency
50/60 Hz (selectable)
Free Running Frequency (Battery mode)
(50 Hz ± 0.25%) or (60 Hz ± 0.25%)
Total Harmonic Distortion (THD)
< 3% (Linear Load); < 6% (Non-Linear Load)
Crest Factor
3:1 max
Overload
(100÷110)% only acoustic alarm ; (110÷130)% for 30 sec; > 130% per 100 ms
(Normal <--> Battery)
0 ms
Transfer Time
(Battery <--> Bypass)
4 ms (typical)
Efficiency
> 92% (Normal mode) ; > 98% (ECO mode)
BATTERIES
Battery Type
Lead acid, sealed, free maintenance
Number of batteries
3
6
Nominal Battery Voltage
36 Vdc
72 Vdc
Battery Specifications
12 Vdc – 7.2 Ah
12 Vdc – 7.2 Ah
12 Vdc – 9 Ah
Backup Time (typical)
8 min
Battery Charge Time (typical)
4 hours
Expandable Autonomy
Available, through external Battery Box (optional)
Содержание EVO DSP MM 1.2