ENGLISH
User’s manual
14
UPS EVO DSP MM
2.
Connect the devices to be supplied to the UPS outputs, by using only the included cables. Be sure all the
devices have the main switch in OFF position.
3.
Only if there is an external Battery Box:
We suggest to use ONLY Battery Box supplied by TECNOWARE. TECNOWARE declines any
responsibilities if this rule is not followed.
Before starting whichever operation be sure that the Battery circuit breaker of Battery
Box is in “OFF” position.
3.1.
Remove the metal cover (#6) on the rear side (see figure 4) to access to the Battery Box Connector.
3.2.
Connect the Battery Box to the Battery Box connector.
3.3.
Place the Battery circuit breaker of Battery Box in “ON” position.
It is compulsory to ground the UPS according to the Safety Standards.
The case of the UPS is internally connected to the ground terminal (GND) of the IN/OUT
terminals, in order to guarantee safety to the user. To guarantee safety it is necessary
to be sure that the local electric plant is supplied with GROUND (in compliance with the
Safety Standards), and that a valid connection is guaranteed between the GROUND of
the UPS and the GROUND of the local electric plant.
Any interruption of the GROUND conductor is absolutely prohibited.
Risk of electric shock at the Output lines if the UPS is ON, even when the UPS is not
connected to AC utility line.
Risk of electric shock at the Output lines while the unit is connected to the AC utility
line.
Risk of electric shock: do not remove the cover. The UPS contains internal parts which
are at a high Voltage and are potentially dangerous, capable of causing injury or death
by electric shock.
There are no internal parts in the UPS which are user serviceable. Any repair or
maintenance work must be performed exclusively by qualified technical personnel
authorized by TECNOWARE. TECNOWARE declines any responsibility if this warning is
disregarded.
Disregard for these warnings may lead to a risk of electric shock to operators.
7
First Start Up
Turning the UPS ON is very easy. Nevertheless we recommend that, on First Start Up, the following procedure is
observed for greater safety.
1.
Be sure all the devices connected to the UPS outputs have the main switch in OFF position.
2.
Restore the AC Input line for the UPS; be sure that the AC utility power is available, and that its voltage and
frequency are within the specifications.
3.
As a consequence of point 2, the UPS turns on the graphic display and goes in Stand-by mode: the UPS
recharges only the batteries and doesn’t supply Output power. Check the graphic display shows the path of
energy flow during Stand-by mode.