remove the exchange package in order to proceed with the installation operation.
Separate the recovery unit from the body.
The recovery unit body is to be fixed to the wall using a fixing suitable for the type of wall.
Cut the plastic tubes according to the thickness of the wall.
Connect the drainage tube, making it come out of the hole made in the external grille.
Once the recovery unit body is fixed, insert the exchange package into its seat, position the
body and assemble the internal grille, making sure to connect the control panel’s electrical power
supply terminals.
Assemble the external grille, making sure to check the correct position of the plastic tubes and the
drainage tube for condensation.
FIXING THE WALL-MOUNTED RECOVERY UNIT
Heat recovery units require periodic maintenance (at least once every 6 months), which is required
in order to optimise their operation.
Access to the filters and the exchange package, which can be removed to wash them, is via the
two grilles.
The cleaning of the filters must be carried out with a specific detergent for filters, the exchange
package must be cleaned and blown with compressed air.
IMPORTANT!
Before performing any cleaning or maintenance operation, disconnect the equipment
from the power supply using the main switch.
MAINTENANCE