Tecnologic TLK 94 Скачать руководство пользователя страница 9

4.12 - REACHING OF THE SET POINT AT CONTROLLED
SPEED AND AUTOMATIC SWITCHING BETWEEN TWO SET
POINTS (RAMPS AND DWELL TIME)

All the parameters referring to the ramps functioning are contained
in the group 

]

rEG”.

It is possible to reach the set point in a predetermined time (in any

case longer than the time the plant would naturally need). This
could be useful in those processes (heating or chemical

treatments, etc.) where the set point has to be reached gradually,
in a predetermined time.

Once the instrument has reached the first Set Point (SP1) it is pos-
sible to have automatic switching to the second Set Point (SP2) af-

ter a set time, thus obtaining a simple automatic process cycle.
These functions are available for all the programmable controls

(PID single and double action, ON/OFF and Neutral Zone
ON/OFF).

The function is determined by the following parameters : 

"SLor"

 - Gradient of first ramp expressed in unit/minute 

"SLoF"

 - Gradient of second ramp expressed in unit/minute.

"dur.t"

 - Dwell time of Set Point “SP1” before automatic switching

to Set Point “SP2” (expressed in hrs. and min.).

The functions are deactivated when the relative parameters are =
InF.

If is desired only one ramp (ex. to reach “SP1”) it is enough to
program on  the par. "SLor" the desired value.   

The ramp "SLor" it will always active at power on and when the
Active Set Point value is changed.

S P 1

[U n it]

S V

S P 1   V a lu e

c h a n g e

S P 1

tim e  [m in .]

S L o r

S L o r

If it is desired an automatic cycle from the power on instead it is

necessary to program the par. "nSP" = 2, to program the two Set  
Point values "SP1" and "SP2" and naturally to program the par.

"SLor", "dur.t" and "SLoF" with the desired values.   
In this case at the end of the cycle all the ramps won't be more

active.

[ U n i t ]

S P 1

S V

A U T O

c h a n g e

S e t

d u r . t

S P 2

t i m e   [ m i n . ]

S L o r

S L o F

Examples with starts from values lower than SP and with
decreasing of SP.

Note:

 In case of PID control, if Auto-tuning is desired whilst the

ramp function is active, this will not be carried out until the tuning
cycle has been completed. It is therefore recommended that
Auto-tuning be started avoiding activating the ramp function and,
once the tuning is finished, deactivate Auto-tuning  (“Auto” = OFF),
program the desired ramp and, if it automatic tuning is desired,
enable the Self-tuning function.

4.13 - SOFT-START FUNCTION

All the parameters referring to the Soft -Start functioning are
contained in the group 

]

rEG”.

The Soft-Start function only works through PID control and allows

the limitation of control power when the instrument is switched on,
for a programmable period of time.

This is useful when the actuator, driven by the instrument, may be
damaged excess power supplied when the application is not yet in

the normal rating. (ex. for certain heating elements). 
The function depends on the following parameters :

 “St.P”

 - Soft-Start power

“SSt”

 - Soft-Start time (expressed in hh.mm)

“HSEt”

 - End Soft Start cycle threshold

If both parameters are programmed with values other than OFF,
when switched on the instrument gives an output power as

programmed on par. “St.P” for the time programmed on par. “SSt”
or when is reached the absolute value programmed at par. “HSEt”.

Practically, the instrument works in manual condition and switches
to automatic control at the elapsing of time “SSt” or when is

reached the absolute value programmed at par. “HSEt”.
To disable the Soft-Start function simply program par.  “SSt” = OFF.

Whenever, a measurement errors occurs during the Soft-Start
execution, the function is interrupted and the instrument gives an

output power as programmed on par. “OPE”.
If the measurement is restored, the Soft-Start is still deactivated.

If it’s desired to activate the Autotuning with Soft-Start set par.
“Auto”=4 / -4

The Autotuning will start automatically at the end of programmed
Soft-Start cycle (see. par. 4.8).

4.14 - ALARMS OUTPUTS FUNCTIONS  (AL1, AL2, AL3, AL4)

The alarms depend on the process value (AL1, AL2, AL3, AL4) and

before setting them to work, it is necessary to know which output
the alarm has to correspond to.

First of all it is necessary to configure in the groups of parameters  

]

Out ”,

 the parameters relative to the outputs required as alarm

(“O1F”, “O2F”, “O3F”, “O4F”, “O5F”, “O6F”) programming the

parameter relating to the desired output as follows :

= ALno

 if the alarm output has to be ON when the alarm is active,

while it is OFF when the alarm is not active

= ALnc

 if the alarm output has to be ON when the alarm is not

active, while it is OFF when the alarm is active 

Note:

 In all the examples that follow is made reference to the alarm

AL1. Naturally the operation of the other alarms results analogous.

Have now access at the group 

]

AL1”,

 and program on par.

“OAL1”

 , to which output the alarm signal has to be sent.

The alarm functioning is instead defined by parameters :

"AL1t "

 - ALARM TYPE

"Ab1"

 - ALARM CONFIGURATION

“AL1”

 - ALARM THRESHOLD 

“AL1L”

 - LOW ALARM THRESHOLD (for band alarm) OR

MINIMUM SET OF AL1 ALARM THRESHOLD (for low or high

alarm)

“AL1H”

 - HIGH ALARM THRESHOLD (for band alarm) OR

MAXIMUM SET OF AL1 ALARM THRESHOLD (for low or high

alarm)

“HAL1” - 

ALARM HYSTERESIS

“AL1d”

 - ALARM ACTIVATION DELAY (in sec.)

"AL1i"

 - ALARM BEHAVIOUR IN THE EVENT OF

MEASUREMENT ERROR

"AL1t" - ALARM TYPE :

  the alarm output can behave in six

different ways.

LoAb

 = ABSOLUTE LOW ALARM: The alarm is activated when

the process value goes below the alarm threshold set on parameter
"AL1” and will be deactivated when it goes above the value

[AL1+HAL1]. 
With this mode is possible to program the minimum and the

maximum set  of   “AL1” by “AL1L” and “AL1H” parameters.

HiAb

 = ABSOLUTE HIGH ALARM: The alarm is activated when the

process value goes higher than the alarm threshold  set on

parameter "AL1" and will be deactivated when it goes below the
value [AL1 - HAL1].

With this mode is possible to program the minimum and the
maximum set  of   “AL1” by “AL1L” and “AL1H” parameters.

LoAb

off

ON

AL1

AL1

PV

HiAb

HAL1

time

off

ON

AL1

PV

time

HAL1

off

off

ON

OUT

off

off

ON

OUT

AL1

TECNOLOGIC spa - TLK 94

 

-OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 9

Содержание TLK 94

Страница 1: ...ONS 4 14 SOFT START FUNCTION 4 13 REACHING OF SET POINT AT CONTROLLED SPEED AND AUTOMATIC COMMUTATION BETWEEN TWO SET POINTS 4 12 SPLIT RANGE FUNCTION 4 11 LIMITATION OF THE CONTROL POWER VARIATION SPEED MAXIMUM RATE OF RISE 4 10 CONTROL POWER LIMITATION 4 9 AUTO TUNING AND SELF TUNING FUNCTIONS 4 8 PID CONTROL FOR MOTORIZED ACTUATORS WITH TIME POSITIONING 4 7 DOUBLE ACTION PID CONTROL 4 6 SINGLE ...

Страница 2: ...s access to the programming mode and the parameters level see par 2 3 12 Led TUN indicates that the Self tuning function is activated light on or that Auto tuning flashing is in progress 13 Display PV normally indicates the process value 14 Display SV normally indicates the active Set value however it can be programmed using par diSP to visualize other values 2 PROGRAMMING 2 1 FAST PROGRAMMING OF ...

Страница 3: ...ained in the group PAn This parameter can be programmed as SE The active Set Point can be modified while the alarm thresholds cannot be modified AE The active Set Point cannot be modified while the alarm thresholds can be modified SAE Both the active Set Point and the alarm thresholds can be modified SAnE Both the active Set Point and the alarm thresholds cannot be modified 2 4 CONTROL STATE The c...

Страница 4: ... probe has to be kept separate from line voltage wiring If the input cable of the probe is screened it has to be connected to the ground with only one side We recommend that a check should be made that the parameters are those desired and that the application functions correctly before connecting the outputs to the actuators so as to avoid malfunctioning that may cause irregularities in the plant ...

Страница 5: ...ivated The coupling outputs number outputs number alarms can be made in the group referring to the alarm to the alarm AL1 2 3 4 The option On it results usable for the output OUT6 standard on all the models to have an auxiliary supply output for input sensors ANALOGICAL OUTPUTS 0 4 20 mA or 0 2 10 V only OUT1 2 With the parameter Aorn it is possible to set the beginning of the scale used for the o...

Страница 6: ...ble overshoots at the start up of the process or at the changing of the Set Point to be avoided Please remember that a low value on this parameter reduces the overshoot while a high value increase it 2 1 3 S P P V tim e 1 FuOC OK 2 FuOC too high 3 FuOC too low 4 6 DOUBLE ACTION PID CONTROLLER 1 rEG 2 rEG All the parameters referred to PID control are contained into the group rEG The Double Action ...

Страница 7: ...ed on on the condition that the process value is lower with Func HEAt than SP SP 2 or higher with Func CooL than SP SP 2 2 if FAST autotuning is desired automatically the next time the instrument is switched on on the condition that the process value is lower with Func HEAt than SP SP 2 or higher with Func CooL than SP SP 2 and once the tuning is finished the par Auto is automatically swapped to t...

Страница 8: ... output from 1 rEG H ro2 L minimum power in output from 2 rEG C ro2 H maximum power in output from 2 rEG C The limitation is not active under the OPLO manual control mode 4 10 LIMITATION OF THE CONTROL POWER VARIATION SPEED This function makes it possible to limit the variation speed of the control power in output separately for both control outputs It is only possible to use this function if the ...

Страница 9: ... HSEt End Soft Start cycle threshold If both parameters are programmed with values other than OFF when switched on the instrument gives an output power as programmed on par St P for the time programmed on par SSt or when is reached the absolute value programmed at par HSEt Practically the instrument works in manual condition and switches to automatic control at the elapsing of time SSt or when is ...

Страница 10: ...AL1d expressed in sec and the alarm will be activated only after the elapsing of that time ALARM LATCH the alarm output may behave in two different ways depending on the value added to par Ab1 0 ALARM NOT LATCHED The alarm remains active in alarm conditions only 4 ALARM LATCHED The alarm is active in alarm conditions and remains active even when these conditions no longer exist until the correctly...

Страница 11: ...vention the instrument visualizes the message LbA and behaves as in the case of a measurement error giving a power output as programmed on par OPE programmable in the group InP To restore normal functioning after the alarm select the control mode OFF and then re program the automatic control rEG after checking the correct functioning of probe and drive To exclude the Loop Break alarm set OLbA OFF ...

Страница 12: ...programming of the instruments which need to have the same parameters configuration or to keep a copy of the programming of an instrument and allow its rapid retransmission To use the device A01 it s necessary that the device or instrument are being supplied Instrument supplied and device not supplied SUPPLY Instrument supplied from the device ADAPTER SUPPLY AC SUPPLY 12 VDC P A For the instrument...

Страница 13: ...ut on OFF Output off O1F 22 Note Def Range Description Par On 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 6 see O1F O6F 35 OFF 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 5 see O1F O5F 34 OFF 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 4 see O1F O4F 33 OFF 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 3 see O1F O3F 32 0 Ao2L 9999 Maximum reference for analogical output 2 ...

Страница 14: ... OLbA 72 Note Def Range Description Par Group Hb parameters relative to Heater Break Alarm OFF Out1 Out2 Out3 Out4 Output where alarm HB is addressed OHb 74 Note Def Range Description Par 100 0 IHbL IFS High alarm HB threshold with Out 1 rEG OFF IHbH 78 0 0 0 0 IFS Low alarm HB threshold with Out 1 rEG ON IHbL 77 1 1 2 3 4 HB Alarm function 1 Min 1 rEG on 2 Max 1 rEG off 3 Min 1 rEG on and Max 1 r...

Страница 15: ... Once the error has been found try to repeat the auto tuning FAST Autotuning not possible because the process value is too higher or too lower ErAt The measured variable is over the probe s limits over range oooo The measured variable is under the probe s limits under range uuuu Verify the correct connection between probe and instrument and then verify the correct functioning of the probe Probe in...

Страница 16: ...n PID PID for motorized actuators with time positioning Measurement range according to the used probe see range table Display resolution according to the probe used 1 0 1 0 01 0 001 Overall accuracy 0 2 fs 1 digit PTC NTC 0 5 fs 1 digit Max cold junction compensation drift in tc 0 04 C C with operating temperature 0 50 C after warm up of 20 min Sampling rate 130 ms Serial Interface RS485 insulated...

Страница 17: ... PTC KTY81 121 HCFG rtd SEnS Ptc 199 9 850 0 C 199 9 999 9 F 200 850 C 328 1562 F Pt100 IEC HCFG rtd SEnS Pt1 7 6 INSTRUMENT ORDERING CODE TLK94 a b c d e f g h i j kk ll m a POWER SUPPLY L 24 VAC VDC H 100 240 VAC b OUTPUT OUT1 R OUT1 Relay O OUT1 VDC for SSR I OUT1 analog 0 4 20 mA V OUT1 analog 0 2 10 V c OUTPUT OUT2 R OUT2 Relay O OUT2 VDC for SSR I OUT1 analog 0 4 20 mA V OUT1 analog 0 2 10 V...

Отзывы: