Up to 2 analogue outputs: 0/4 ..20 mA (Load Max. 300
Ω
) or 0/2
..10 V.
Auxiliary supply output / OUT6: 12 VDC / 20 mA Max.
Electrical life for relay outputs: 100000 operat.
Installation category: II
Measurement category: I
Protection class against electric shock: Class II for Front panel
Insulation:
Reinforced insulation between the low voltage section
(supply and relay outputs) and the front panel; Reinforced
insulation between the low voltage section (supply and relay
outputs) and the extra low voltage section (inputs, analogue
outputs, SSR outputs); analogue and SSR outputs optoisolated
respect to the input. 50 V insulation between RS485 and extra low
voltage section.
7.2 - MECHANICAL DATA
Housing: Self-extinguishing plastic, UL 94 V0
Dimensions: 48 x 96 mm DIN, depth 98 mm
Weight: 260 g approx.
Mounting: Flush in panel in 45 x 92 mm hole
Connections: 2 x 1 mm
2
screw terminals block
Degree of front panel protection : IP 54 mounted in panel with
gasket
Pollution situation: 2
Operating temperature: 0 ... 50 °C
Operating humidity: 30 ... 95 RH% without condensation
Storage temperature: -10 ... +60 °C
7.3 - MECHANICAL DIMENSIONS, PANEL CUT-OUT AND
MOUNTING [mm]
TUN
SET
Out6
SV
PV
TLK 94
Out1 Out2 Out3
Out5
Out4
48
96
97,5
10
89,5
PANEL CUTOUT
RECOMMENDED
45
92
min. 10 mm
min
. 2
0 mm
PANEL + GASKET
MAX. 8 mm
BRACKETS
7.4 - FUNCTIONAL FEATURES
Control: ON/OFF, single and double action PID, PID
for motorized
actuators with time positioning
Measurement range: according to the used probe (see range table)
Display resolution: according to the probe used 1/0,1/0,01/0,001
Overall accuracy: +/- (0,2 % fs + 1 digit); PTC/NTC: +/- (0,5 % fs +
1 digit)
Max. cold junction compensation drift (in tc) : 0,04 °C/°C with
operating temperature 0 ... 50 °C after warm-up of 20 min.
Sampling rate: 130 ms.
Serial Interface : RS485 insulated
Communication protocol: MODBUS RTU (JBUS)
Baud rate: Programmable from 1200 ... 38400 baud
Display: Display: 4 digit, 1 Red (PV) h 10mm and 1 green (SV), h
7,5 mm
Compliance: ECC directive EMC 2004/108/CE (EN 61326), ECC
directive LV 2006/95/CE (EN 61010-1).
7.5 - MEASURING RANGE TABLE
-46.0 ... 785.0 °C
-50.8 ... 999.9 °F
-46 ... 785 °C
-50 ... 1445 °F
IRS range “A”
“HCFG” = tc
“SEnS”= Ir.J - Ir.CA
0.0 ... 999.9 °C
32.0 ... 999.9 °F
0 ... 2320 °C
32 ... 4208 °F
tc C
“HCFG” = tc
“SEnS” = C
-199.9 ... 400.0 °C
-199.9 ... 752.0 °F
-250 ... 400 °C
-418 ... 752 °F
tc T
“HCFG” = tc
“SEnS” = t
-50.0 ... 999.9 °C
-58.0 ... 999.9 °F
-50 ... 1760 °C
-58 ... 3200 °F
tc R
“HCFG” = tc
“SEnS” = r
-199.9 ... 999.9 °C
-199.9 ... 999.9 °F
-250 ... 1300 °C
-418 ... 2372 °F
tc N
“HCFG” = tc
“SEnS” = n
-150.0 ... 900.0 °C
-199.9 ... 999.9 °F
-150 ... 900 °C
-252 ... 1652 °F
tc L
“HCFG” = tc
“SEnS” = L
-150.0 ... 750.0 °C
-199.9 ... 999.9 °F
-150 ... 750 °C
-252 ... 1382 °F
tc E
“HCFG” = tc
“SEnS” = E
72.0 ... 999.9 °C
162.0 ... 999.9 °F
72 ... 1820 °C
162 ... 3308 °F
tc B
“HCFG” = tc
“SEnS” = b
0.0 ... 999.9 °C
32.0 ... 999.9 °F
0 ... 1760 °C
32 ... 3200 °F
tc S
“HCFG” = tc
“SEnS” = S
-100.0 ... 999.9 °C
-148.0 ... 999.9 °F
-100 ... 1370 °C
- 148 ... 2498 °F
tc K
“HCFG” = tc
“SEnS” = CrAl
-160.0 ... 999.9 °C
-199.9 ... 999.9 °F
-160 ... 1000 °C
- 256 ... 1832 °F
tc J
“HCFG” = tc
“SEnS” = J
“dP”= 1, 2, 3
“dP” = 0
INPUT
TECNOLOGIC spa - TLK 94
-OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 16