Tecnologic TLK 94 Скачать руководство пользователя страница 10

LodE

 = DEVIATION LOW ALARM: The alarm is activated when

the process value goes below the value [SP1 + AL1] and will be
deactivated when it goes above the value [SP1 + AL1 + HAL1].

With this mode is possible to program the minimum and the
maximum set  of   “AL1” by “AL1L” and “AL1H” parameters.

HidE

 = DEVIATION HIGH ALARM: The alarm is activated when the

process value goes above the value [SP1 + AL1] and will be
deactivated when it goes below the value [SP1 +  AL1 - HAL1].

With this mode is possible to program the minimum and the
maximum set  of   “AL1” by “AL1L” and “AL1H” parameters.

LodE

ON

off

PV

SP

-AL1

HAL1

time

off

ON

SP

AL1

PV

HidE

time

HAL1

ON

off

off

off

off

ON

OUT

AL1

OUT

AL1

LHAb

 = ABSOLUTE BAND ALARM: The alarm is activated when

the process value goes under the alarm threshold set on parameter

"AL1L" or goes higher than the alarm threshold set on parameter
"AL1H" and will be deactivated when it goes below the value [AL1H

- HAL1] or when it goes above the value [AL1L + HAL1].

LHdE

 = DEVIATION BAND ALARM: The alarm is activated when

the process value goes below the value [SP1 + AL1L] or goes

above than the value [SP1 + AL1H] and will be deactivated when it
goes below the value [SP1 + AL1H - HAL1] or when it goes above

the value [SP1 + AL1L + HAL1].

LHAb

ON

off

AL1H

AL1L

PV

ON

time

off

HAL1

HAL1

SP

AL1L

AL1H

PV

time

LHdE

HAL1

HAL1

off

off

ON

ON

off

off

OUT

AL1

OUT

AL1

"

Ab1" - ALARM CONFIGURATION:

 This parameter can assume a

value between 0 and 31.
The number to be set, which will correspond to the function

desired, is obtained by adding the values reported in the following
descriptions :

ALARM BEHAVIOUR AT SWITCH ON: the alarm output may
behave in two different ways, depending on the value added to par.

“Ab1”.
+0 = NORMAL BEHAVIOUR: The alarm is always activated when

there are alarm conditions.
+1 = ALARM NOT ACTIVATED AT SWITCH ON: If, when switched

on, the instrument is in alarm condition, the alarm is not activated.
It will be activated only when the process value is in non-alarm

conditions  and then back in alarm conditions.

P V

+ 1

+ 0

t i m e

A L 1

O N

O N

O N

o f f

o f f

o f f

o f f

A b 1

exemple with absolute low alarm

ALARM DELAY:  the alarm output may behave in two different
ways depending on the value added to par. “Ab1”.

+0 = ALARM NOT DELAYED: The alarm is immediately activated
when the alarm condition occurs.

+2 = ALARM DELAYED: When the alarm condition occurs, delay
counting begins, as programmed on par. “AL1d” (expressed in

sec.) and the alarm will be activated only after the elapsing of that
time.

ALARM LATCH: :  the alarm output may behave in two different
ways depending on the value added to par. “Ab1”.

+ 0 = ALARM NOT LATCHED: The alarm remains active in alarm
conditions only.

+ 4 = ALARM LATCHED: The alarm is active in alarm conditions
and remains active even when these conditions no longer exist,

until  the correctly programmed key “U”, (“USrb”=Aac) has been
pushed.

A L 1

P V

O N

O N

t i m e

+ 0

A b 1

+ 4

o f f

o f f

o f f

exemple with absolute high alarm

ALARM  AKNOWLEDGEMENT: :  the alarm output may behave in

two different ways depending on the value added to par. “Ab1”.
+ 0 = ALARM NOT AKNOWLEDGED: The alarm always remains

active in alarm conditions.
+ 8 = ALARM AKNOWLEDGED: The alarm is active in alarm

conditions and can be deactivated by key “U” if properly
programmed (“USrb”=ASi), and also if alarm conditions still exist.

ALARM BEHAVIOUR AT SET POINT CHANGE (DEVIATION
ALARMS ONLY): the alarm output may behave in two different

ways, depending on the value added to par. “Ab1”.
+0 = NORMAL BEHAVIOUR: The alarm is always activated when

there are alarm conditions.
+16 = ALARM NOT ACTIVATED AT SET POINT CHANGE: If,

when Set Point change, the instrument is in alarm condition, the
alarm is not activated. It will be activated only when the process

value is in non-alarm conditions  and then back in alarm conditions.

"AL1i" - ALARM ACTIVATION IN CASE OF MEASUREMENT
ERROR:

 This allows one to establish how the alarm have behave

in the event of a measurement error (yES=alarm active; no=alarm

deactivated).

4.15 - HEATER BREAK ALARM FUNCTION  (HB)

All the parameters referring to the Heater Break alarm function are
contained in the group 

]

Hb”.

The Heater Break alarm function (Breakage of the heating element)
is only available when the instrument is equipped with the input

(TAHB) to measure the current and if use a digital output to control
the load.

This input accepts signals coming from current transformers (TA)
with max. output 50 mA. 

The first operation to be carried out in order to obtain a correct
current measurement, is to set the current that the instrument has

to measure at the end of scale of the input TA (50 mA) on par.

“IFS”

.

T L K   9 4

T A

E H

K M

L o a d

P o w e r

S u p p l y

A C

5 b 6 b

o u t   1 . r E G

It is necessary to establish to which output the alarm has to
correspond.  

To do this it is necessary to set the parameter relative to the output
to be used (“O1F”, “O2F”, “O3F”, “O4F”, “O5F”, “O6F”) in the
groups 

]

Out”, 

programming the parameter as :

TECNOLOGIC spa - TLK 94

 

-OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 10

Содержание TLK 94

Страница 1: ...ONS 4 14 SOFT START FUNCTION 4 13 REACHING OF SET POINT AT CONTROLLED SPEED AND AUTOMATIC COMMUTATION BETWEEN TWO SET POINTS 4 12 SPLIT RANGE FUNCTION 4 11 LIMITATION OF THE CONTROL POWER VARIATION SPEED MAXIMUM RATE OF RISE 4 10 CONTROL POWER LIMITATION 4 9 AUTO TUNING AND SELF TUNING FUNCTIONS 4 8 PID CONTROL FOR MOTORIZED ACTUATORS WITH TIME POSITIONING 4 7 DOUBLE ACTION PID CONTROL 4 6 SINGLE ...

Страница 2: ...s access to the programming mode and the parameters level see par 2 3 12 Led TUN indicates that the Self tuning function is activated light on or that Auto tuning flashing is in progress 13 Display PV normally indicates the process value 14 Display SV normally indicates the active Set value however it can be programmed using par diSP to visualize other values 2 PROGRAMMING 2 1 FAST PROGRAMMING OF ...

Страница 3: ...ained in the group PAn This parameter can be programmed as SE The active Set Point can be modified while the alarm thresholds cannot be modified AE The active Set Point cannot be modified while the alarm thresholds can be modified SAE Both the active Set Point and the alarm thresholds can be modified SAnE Both the active Set Point and the alarm thresholds cannot be modified 2 4 CONTROL STATE The c...

Страница 4: ... probe has to be kept separate from line voltage wiring If the input cable of the probe is screened it has to be connected to the ground with only one side We recommend that a check should be made that the parameters are those desired and that the application functions correctly before connecting the outputs to the actuators so as to avoid malfunctioning that may cause irregularities in the plant ...

Страница 5: ...ivated The coupling outputs number outputs number alarms can be made in the group referring to the alarm to the alarm AL1 2 3 4 The option On it results usable for the output OUT6 standard on all the models to have an auxiliary supply output for input sensors ANALOGICAL OUTPUTS 0 4 20 mA or 0 2 10 V only OUT1 2 With the parameter Aorn it is possible to set the beginning of the scale used for the o...

Страница 6: ...ble overshoots at the start up of the process or at the changing of the Set Point to be avoided Please remember that a low value on this parameter reduces the overshoot while a high value increase it 2 1 3 S P P V tim e 1 FuOC OK 2 FuOC too high 3 FuOC too low 4 6 DOUBLE ACTION PID CONTROLLER 1 rEG 2 rEG All the parameters referred to PID control are contained into the group rEG The Double Action ...

Страница 7: ...ed on on the condition that the process value is lower with Func HEAt than SP SP 2 or higher with Func CooL than SP SP 2 2 if FAST autotuning is desired automatically the next time the instrument is switched on on the condition that the process value is lower with Func HEAt than SP SP 2 or higher with Func CooL than SP SP 2 and once the tuning is finished the par Auto is automatically swapped to t...

Страница 8: ... output from 1 rEG H ro2 L minimum power in output from 2 rEG C ro2 H maximum power in output from 2 rEG C The limitation is not active under the OPLO manual control mode 4 10 LIMITATION OF THE CONTROL POWER VARIATION SPEED This function makes it possible to limit the variation speed of the control power in output separately for both control outputs It is only possible to use this function if the ...

Страница 9: ... HSEt End Soft Start cycle threshold If both parameters are programmed with values other than OFF when switched on the instrument gives an output power as programmed on par St P for the time programmed on par SSt or when is reached the absolute value programmed at par HSEt Practically the instrument works in manual condition and switches to automatic control at the elapsing of time SSt or when is ...

Страница 10: ...AL1d expressed in sec and the alarm will be activated only after the elapsing of that time ALARM LATCH the alarm output may behave in two different ways depending on the value added to par Ab1 0 ALARM NOT LATCHED The alarm remains active in alarm conditions only 4 ALARM LATCHED The alarm is active in alarm conditions and remains active even when these conditions no longer exist until the correctly...

Страница 11: ...vention the instrument visualizes the message LbA and behaves as in the case of a measurement error giving a power output as programmed on par OPE programmable in the group InP To restore normal functioning after the alarm select the control mode OFF and then re program the automatic control rEG after checking the correct functioning of probe and drive To exclude the Loop Break alarm set OLbA OFF ...

Страница 12: ...programming of the instruments which need to have the same parameters configuration or to keep a copy of the programming of an instrument and allow its rapid retransmission To use the device A01 it s necessary that the device or instrument are being supplied Instrument supplied and device not supplied SUPPLY Instrument supplied from the device ADAPTER SUPPLY AC SUPPLY 12 VDC P A For the instrument...

Страница 13: ...ut on OFF Output off O1F 22 Note Def Range Description Par On 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 6 see O1F O6F 35 OFF 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 5 see O1F O5F 34 OFF 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 4 see O1F O4F 33 OFF 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 3 see O1F O3F 32 0 Ao2L 9999 Maximum reference for analogical output 2 ...

Страница 14: ... OLbA 72 Note Def Range Description Par Group Hb parameters relative to Heater Break Alarm OFF Out1 Out2 Out3 Out4 Output where alarm HB is addressed OHb 74 Note Def Range Description Par 100 0 IHbL IFS High alarm HB threshold with Out 1 rEG OFF IHbH 78 0 0 0 0 IFS Low alarm HB threshold with Out 1 rEG ON IHbL 77 1 1 2 3 4 HB Alarm function 1 Min 1 rEG on 2 Max 1 rEG off 3 Min 1 rEG on and Max 1 r...

Страница 15: ... Once the error has been found try to repeat the auto tuning FAST Autotuning not possible because the process value is too higher or too lower ErAt The measured variable is over the probe s limits over range oooo The measured variable is under the probe s limits under range uuuu Verify the correct connection between probe and instrument and then verify the correct functioning of the probe Probe in...

Страница 16: ...n PID PID for motorized actuators with time positioning Measurement range according to the used probe see range table Display resolution according to the probe used 1 0 1 0 01 0 001 Overall accuracy 0 2 fs 1 digit PTC NTC 0 5 fs 1 digit Max cold junction compensation drift in tc 0 04 C C with operating temperature 0 50 C after warm up of 20 min Sampling rate 130 ms Serial Interface RS485 insulated...

Страница 17: ... PTC KTY81 121 HCFG rtd SEnS Ptc 199 9 850 0 C 199 9 999 9 F 200 850 C 328 1562 F Pt100 IEC HCFG rtd SEnS Pt1 7 6 INSTRUMENT ORDERING CODE TLK94 a b c d e f g h i j kk ll m a POWER SUPPLY L 24 VAC VDC H 100 240 VAC b OUTPUT OUT1 R OUT1 Relay O OUT1 VDC for SSR I OUT1 analog 0 4 20 mA V OUT1 analog 0 2 10 V c OUTPUT OUT2 R OUT2 Relay O OUT2 VDC for SSR I OUT1 analog 0 4 20 mA V OUT1 analog 0 2 10 V...

Отзывы: