disconnect and connect the unit, finally try to replace a new 

“Cartridge Sensor

”. If the condition is not change, it will 

be necessary to replace the unit and/or send it back to the supplier to repair. 

All LED activate (

>24mA output signal

):

 

this happens when the “

Cartridge Sensor

” is not working or gas concentra-

tion is out of scale (higher than 100% LEL) If there are not any gas leaks and the condition is not change, it will be 
necessary to replace the unit and/or send it back to the supplier to repair. 

INSTALLATION 

The detector must be accurately installed according to the national dispositions in force on the safety of the plants 
and installation of electric devices in areas with danger of explosion. 

Mounting

: The 

Fig. 2

 shows the instrument size. The unit must be positioned vertically with the sensor downwards. 

Model TS282PG 

should be fixed at 20-30 cm from the floor (LPG gas is heavier than air). 

Model TS282PM

 should be fixed at 20-30 cm from the ceiling (Methane gas is lighter than air). 

Model TS282PI

 should be fixed at 20-30 cm from the ceiling (Hydrogen gas is lighter than air). 

Model TS282PB 

should be fixed at 20-30 cm from the floor (Petrol vapours are heavier than air). 

Model TS282PX 

should be fixed in high position with a gas Vapour Density less than 1 (the gas is lighter than air) 

or in bottom position with a density greater than 1, (the gas is heavier than air) (

see Table 3

 – column n.4

). 

Electrical Connection (

see Fig.2

)

: the maximum distance to install each detector from the Gas Central Unit is show 

in 

table 1

. Normally use a tree wire shielded cable. 

The terminals (+

 - S

), are plug-in type, it is necessary to extract them to make the connection. Pay attention when 

you insert them again, being polarized. With the Dip-Switches the Alarm Red Led activation is determined. 

Note:  Dip-Switch  should  be  set  with  instrument  powered  off.  Dip-Switch  1  settled  ON  activates  ALARM 

Red LED indication (

see Table 2

). 

Important

:

  Once  installation  is  completed,

  power  up  the  unit, 

wait  about  20÷30  minutes  and  then, 

only  if  it  is 

necessary

to adjust the sensor to the environment conditions,

 carry out the 

Zero Adjust 

(

see 

Test and Calibration

)

.

 

COMPATIBILITY WITH OTHER CENTRAL UNITS: 

In case of a central unit other than Tecnocontrol, please verify 

the max load resistor as shown 

in 

Fig. 4

. We suggest using 24Vdc power supply. 

WARNING 

Average life

: The sensitive element used in this detector has an excellent stability in time. In fresh air and in nor-

mal working condition the sensor's life is about 5 years from the date of installation. After this period the yellow LED 

FAULT

” flashes every 4 seconds, is necessary replacing the “

Cartridge Sensor

”. 

Periodical testing

: we advise to carry out working tests every 12 months. Tests, Zero Adjust and Calibration with 

Gas/Air mixture as explained in chapter “

Tests and Calibration

”. 

Note:

  the  detector  is  not  able  to  detect  gas  leaks  occurring  outside  the  room  where  it  is  installed,  neither  inside 

walls nor under the floor. 

Important:

 

The catalytic Pellistor sensor operates only in presence of Oxygen. Do not use pure gases or a lighter 

directly on the sensor since they could damage it irremediably. 

Warning:

 

some substances cause a permanent reduction in sensitivity. Avoid contacts of the sensor with vapours 

of Silicone compounds, Tetra-ethyl Lead (petrol antiknock additive)  and  Phosphate esters, since they can  reduce 
irremediably  its sensitivity.  Some substances  produce a temporary loss of sensitivity. This “inhibitors” include Hy-
drogen  sulphides,  Chlorine,  Chlorinated  hydrocarbons  and  halogenated  compounds.  The  sensitivity  is  recovered 
after a short period of running in clear air. 

TEST and CALIBRATION 

PAY  ATTENTION

This  procedure  has  to  be  made  with  extreme  attention  and  by  authorized  and  trained 

people;  because  starting  this  procedure  it  will  increase  mA  Output  causing  the  activation  of  connected 
alarm devices to the gas Central Unit. 

Operation Check, Zero Adjust and Calibration

:

 are different code protected functions. To access these functions is 

necessary  to  insert  the  relevant  “

Code

"  through  the  keys  F1s  and  F2.  To  have  the  key  pressure  recognized,  hold 

pressing  it for around a second (

until the Green Led doesn't switch off for a moment

). Then the next key can  be pressed. In 

case of error all it takes is waiting around 10 seconds and the sequence is automatically erased. 

Calibration Kit, Sample Gas Bottles

 (

for Calibration Check and Calibration

) please, only using a mixture: 

20%LEL (0.88%v/v)

 

Methane in Air (20.9% Oxygen).

 

Pellistor sensors  cannot  work in oxygen deficiency

. It is possible to use  either the disposable  one  litre  cylin-

ders with adjust valve or the high pressure ones with reduction gear. It is also necessary to use 

the calibration kit 

Tecnocontrol model TC011 

(

for non-corrosive gases

) or 

TC014 

(

Stainless steel

). 

“INSTRUMENT OPERATION CHECK” (

Check Code

: F2, F2, F1, F1)

this function allows to effect a functional test 

of the equipment. After having put the system in safety and inserted the "

Code Test

", all Led are switched off. Then 

they will switch on in sequence, the Led, from the yellow up to the red. At the end all the Led will remain lighted for 
around 5 seconds, then the central returns at the conditions of normal operation. It is advisable to perform this op-
eration every 6-12 months according to the use. 

Note: this function is not working if the red Led is already switched on 

 

 “ZERO ADJUST” (

Zero Code

: F2, F1, F1, F2)

this function is to adjust the Zero sensor and can be done in clean 

air only (environment without the presence of gas or other pollutants). Immediately after having inserted the "

Zero 

Code

", as a confirmation of the operation carried out there will be 

1

 flash of the red Led and the output will become 

4,0 mA. We suggest performing this operation 

only if the output is different from 4mA

 after the installation or af-

ter the change of the cartridge and every 6-12 months based on the environmental conditions. 

Содержание TS282PB

Страница 1: ...o load resistor résistance de charge 50 ohm 12Vdc 10 500 ohm 24Vdc 10 Campo di misura Standard Range Champ de mesure 0 100 LIE LEL Limite Scala Limits Limite échelle 100 LIE LEL Vita media in aria pulita Average Life in fresh air Vie moyenne en air pur 5 anni years ans Tempo di risposta T90 Response Time T90 Temps de réponse T90 60 secondi seconds secondes Ripetibilità Repeatability Répétitivité 5...

Страница 2: ...Led Rosso ALARM si accende se è stato abilitato se la concentrazione di Gas supera il 20 LIE I Guasti possibili sotto elencati sono indicati dall accensione del Led giallo FAULT e portando l uscita S a 0mA Il Led Giallo si accende ogni 4 secondi con il Led Verde acceso per avvisare che la Cartuccia Sensore ha su perato il suo limite di vita circa 5 anni e non è più garantito il corretto funzioname...

Страница 3: ...i e la sequenza è automaticamente cancellata Kit di Taratura e Bombole con Miscela Aria Gas per Calibrazione e Verifica la miscela da utilizzare è Gas Metano al 20 LIE 0 88 v v in aria 20 9 Ossigeno circa I sensori Pellistor non possono assolutamente funzionare in carenza d ossigeno È possibile usare sia bom bole monouso con valvola d erogazione sia ricaricabili ad alta pressione con riduttore di ...

Страница 4: ...e a gas lighter than air Its density as to air is 0 55 and its LEL Lower Explosive Limit is 4 4 v v volume TS282PG GPL is calibrated to detect LPG a gas heavier than air and consists of a mixture of 20 30 Propane C3H8 and 80 70 Butane C4H10 Propane density as to air is 1 56 while Butane is 2 05 The LEL is 1 7 v v for Propane and 1 4 v v for Butane Standard calibration to LPG is carried out for But...

Страница 5: ...re as explained in chapter Tests and Calibration Note the detector is not able to detect gas leaks occurring outside the room where it is installed neither inside walls nor under the floor Important The catalytic Pellistor sensor operates only in presence of Oxygen Do not use pure gases or a lighter directly on the sensor since they could damage it irremediably Warning some substances cause a perm...

Страница 6: ... a voltmeter connected to the Test Point TESTmA see fig 2 the value reach the mV value as shown in Table 3 on column 6 corresponding to mA output value 0 2mA as indi cated in column 7 The central unit should be display about the LEL value 2 as indicated in column 8 If the re sult is different is necessary to recalibrate the sensor see Calibration Then close the gas bottle remove TC011 Then the mA ...

Страница 7: ...é de fuite de gaz et que la condition perdure après la substitution de la Cartouche il sera nécessaire d envoyer le détecteur au fournisseur pour réparation INSTALLATION Les détecteurs doivent être installés et positionnés en suivant toutes les règles nationales en vigueur pour les ins tallations électriques dans les zones avec dangers d explosions et les normes de sûreté des installations Montage...

Страница 8: ...er cette opération que si la sortie est différente de 4mA après l installation ou après le changement de la cartouche et chaque semestre en fonction des conditions ambiantes Remarque Il n est pas possible d exécuter l opération si la LED Rouge est allumée ou si la sortie en mA est supé rieure à 10 de la LIE 5 6mA Dans le cas il nécessaire de procéder à la calibration ou bien de substituer la car t...

Страница 9: ...ir 1 NOTA 1 NOTE 1 REMARQUE 1 20 LIE LEL v v TESTmA TP1 TP2 mV Uscita Output Sortie mA LIE LEL TS282PM Metano Methane Méthane 1 4 4 0 55 0 88 72 7 2 20 TS282PG Butano Butane Butane 1 43 1 4 2 05 0 28 89 8 9 31 TS282PI Idrogeno Hydrogen Hydrogène 1 54 4 0 07 0 8 72 7 2 20 TS282PB Benzina Petrol Essence 0 91 1 2 2 8 0 24 89 8 9 31 TS282PX Acetato di etile Ethyl acetate 1 67 2 2 3 04 0 44 95 9 5 34 A...

Страница 10: ...tie Test 40 200mV 12 24Vdc Alimentazione Power Supply Alimentation S Uscita 4 20 mA 4 20 mA Output Sortie en 4 20 mA mV Fig 3 Tester di calibrazione Calibration Tester Kit de Calibration 0 3L min F1 F2 Tasti Key Touches TC011 TC014 Alimentazione Power Supply Alimentation 100 300 400 500 50 0 5 200 Vdc RL Resistenza di carico Load resistor Resistance de charge RL Ohm Fig 4 Alimentazione Resistenza ...

Отзывы: