background image

IST-2282.PM01.01

 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag.10/10

 

 

 

TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI ) 

Tel. +39 02 26922890 - Fax +39 02 2133734

 

 

 

 

Fig. 1 –

 

Dimensioni /

 Size / 

Dimensions 

 

 

1

 

2

 

3

 

4

 

ON

 

OFF

 

Dip Switch

 

SET

 

Fig. 2 -

 

Schema di collegamento 

/ Wiring diagram / Schéma

 

TESTmV

 

TP2 

TP1 

 

 

 

 

12

-2

4V

 

mA

 

Centrale rivelazione gas 

Gas Central Unit

 

Centrale de détection

 

RL

 

-

 

S

 

+

 

Test Uscita  

Output Test 

Sortie Test 

40÷200mV

 

+/- 

(12÷24Vdc)

 

Alimentazione / Power Supply / Alimentation

 

“S” = 

Uscita 4÷20 mA 

4÷20 mA Output / Sortie en 4÷20 mA

 

mV

 

 

 

Fig. 3 -

 Tester di calibrazione 

/ Calibration Tester / Kit de Calibration 

0,3L/min

 

F1 

F2 

Tasti / 

Key / Touches

 

TC011 / TC014

 

 

 

Alimentazione 

/ Power Supply / Alimentation

 

100

 

300

 

400

 

500

 

50

 

0

 

5

 

200

 

Vdc

 

RL=Resistenza di carico 

/ Load resistor / Resistance de charge

 

RL

 

Ohm

 

Fig.4 -

 

Alimentazione / Resistenza di Carico 4÷20mA 

Power supply / Load resistance diagram 4÷20mA 
Alimentation / Résistance de charge 4÷20mA

 

600

 

0

 

10

 

15

 

20

 

25

 

28

 

650

 

10,8

 

24

 

Area di funzionamento 

Allowable oparating region 

350

 

700

 

800 

 

Содержание TS282PB

Страница 1: ...o load resistor résistance de charge 50 ohm 12Vdc 10 500 ohm 24Vdc 10 Campo di misura Standard Range Champ de mesure 0 100 LIE LEL Limite Scala Limits Limite échelle 100 LIE LEL Vita media in aria pulita Average Life in fresh air Vie moyenne en air pur 5 anni years ans Tempo di risposta T90 Response Time T90 Temps de réponse T90 60 secondi seconds secondes Ripetibilità Repeatability Répétitivité 5...

Страница 2: ...Led Rosso ALARM si accende se è stato abilitato se la concentrazione di Gas supera il 20 LIE I Guasti possibili sotto elencati sono indicati dall accensione del Led giallo FAULT e portando l uscita S a 0mA Il Led Giallo si accende ogni 4 secondi con il Led Verde acceso per avvisare che la Cartuccia Sensore ha su perato il suo limite di vita circa 5 anni e non è più garantito il corretto funzioname...

Страница 3: ...i e la sequenza è automaticamente cancellata Kit di Taratura e Bombole con Miscela Aria Gas per Calibrazione e Verifica la miscela da utilizzare è Gas Metano al 20 LIE 0 88 v v in aria 20 9 Ossigeno circa I sensori Pellistor non possono assolutamente funzionare in carenza d ossigeno È possibile usare sia bom bole monouso con valvola d erogazione sia ricaricabili ad alta pressione con riduttore di ...

Страница 4: ...e a gas lighter than air Its density as to air is 0 55 and its LEL Lower Explosive Limit is 4 4 v v volume TS282PG GPL is calibrated to detect LPG a gas heavier than air and consists of a mixture of 20 30 Propane C3H8 and 80 70 Butane C4H10 Propane density as to air is 1 56 while Butane is 2 05 The LEL is 1 7 v v for Propane and 1 4 v v for Butane Standard calibration to LPG is carried out for But...

Страница 5: ...re as explained in chapter Tests and Calibration Note the detector is not able to detect gas leaks occurring outside the room where it is installed neither inside walls nor under the floor Important The catalytic Pellistor sensor operates only in presence of Oxygen Do not use pure gases or a lighter directly on the sensor since they could damage it irremediably Warning some substances cause a perm...

Страница 6: ... a voltmeter connected to the Test Point TESTmA see fig 2 the value reach the mV value as shown in Table 3 on column 6 corresponding to mA output value 0 2mA as indi cated in column 7 The central unit should be display about the LEL value 2 as indicated in column 8 If the re sult is different is necessary to recalibrate the sensor see Calibration Then close the gas bottle remove TC011 Then the mA ...

Страница 7: ...é de fuite de gaz et que la condition perdure après la substitution de la Cartouche il sera nécessaire d envoyer le détecteur au fournisseur pour réparation INSTALLATION Les détecteurs doivent être installés et positionnés en suivant toutes les règles nationales en vigueur pour les ins tallations électriques dans les zones avec dangers d explosions et les normes de sûreté des installations Montage...

Страница 8: ...er cette opération que si la sortie est différente de 4mA après l installation ou après le changement de la cartouche et chaque semestre en fonction des conditions ambiantes Remarque Il n est pas possible d exécuter l opération si la LED Rouge est allumée ou si la sortie en mA est supé rieure à 10 de la LIE 5 6mA Dans le cas il nécessaire de procéder à la calibration ou bien de substituer la car t...

Страница 9: ...ir 1 NOTA 1 NOTE 1 REMARQUE 1 20 LIE LEL v v TESTmA TP1 TP2 mV Uscita Output Sortie mA LIE LEL TS282PM Metano Methane Méthane 1 4 4 0 55 0 88 72 7 2 20 TS282PG Butano Butane Butane 1 43 1 4 2 05 0 28 89 8 9 31 TS282PI Idrogeno Hydrogen Hydrogène 1 54 4 0 07 0 8 72 7 2 20 TS282PB Benzina Petrol Essence 0 91 1 2 2 8 0 24 89 8 9 31 TS282PX Acetato di etile Ethyl acetate 1 67 2 2 3 04 0 44 95 9 5 34 A...

Страница 10: ...tie Test 40 200mV 12 24Vdc Alimentazione Power Supply Alimentation S Uscita 4 20 mA 4 20 mA Output Sortie en 4 20 mA mV Fig 3 Tester di calibrazione Calibration Tester Kit de Calibration 0 3L min F1 F2 Tasti Key Touches TC011 TC014 Alimentazione Power Supply Alimentation 100 300 400 500 50 0 5 200 Vdc RL Resistenza di carico Load resistor Resistance de charge RL Ohm Fig 4 Alimentazione Resistenza ...