IST-2282.PM01.01
Istruzione / User’s Manual / Manuel d’utilisation
Pag.6/10
TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI )
Tel. +39 02 26922890 - Fax +39 02 2133734
Note
:
This function is not working if mA output is more than 5,6mA (10% LEL) and/or red Led is already
been switched on. In this case, it will be necessary to recalibrate the unit and/or replacing the “Cartridge”
“CALIBRATION” (
Calibration Code
: F2, F2, F2, F1, F2, F1)
:
this function allows completely recalibrate the sensor.
Warning
: to guarantee that no errors of elaboration happen, the rare possibility exists that during the Calibration
the
yellow LED switch off every 8 seconds,
in this case interrupt the procedure, switch off and witch on the instru-
ment and repeat the Calibration. If condition persists it will be necessary to send the detector to the supplier for the
reparation.
Important note:
During Calibration routine the mA output indicates 0mA
.
The Calibration can be done in clean air only (
environment without the presence of flammable or other polluting gas
). With the
keys perform the “Calibration
Code
". Wait until the Yellow and Green Led switch on fix and the red Led starts to
flash. Insert the TC011 into the sensor holder, adjust the sample gas bottle valve (
0.88%v/v methane in air
), as the
flow meter indicates around 0.3 l/mins (
see Fig.3
). Wait around 3 minutes, then when the red Led switch on (
and while
it's SWITCHED ON
), press the key F2 on the instrument and hold it pressed until the Red Led is switched off for at
least 2 seconds (
if the Red Led continue to flash, repeat the operation
).
Then, close the gas cylinder and remove TC011
. At
this point we can have two possibilities:
Yellow and Green Led illuminates:
the calibration routine has correctly been performed.
Wait 8 seconds, until
the instrument automatically restores the normal working conditions
.
(
see “Operational Description > Preheating”
)
Yellow LED illuminates:
the routine has failed. In this case, wait 8 seconds, until the instrument automatically re-
peat
Preheating
, then repeat the “
Calibration”
routine without inserting again the code. If condition still persists after the
replacement of the cartridge, it will be necessary to send the detector back to the manufacturer for reparation.
“CALIBRATION CHECK” (
no Code required
)
:
this operation allows performing a real functional test of the equip-
ment with gas
after the "
Calibration
" routine, or after the installation. The “
Calibration Check
” routine should be done
during the periodic maintenances because this is the only method to verify the instrument real functioning.
This routine should be done
using a mixture 20%LEL (0.88%v/v)
Methane in Air (
20.9% Oxygen
)
Insert the TC011 over the sensor holder, adjust the sample gas bottle valve (
0.88%v/v methane in air
), as the flow me-
ter indicates around 0.3 l/mins (
see Fig.3
),
verify with a voltmeter connected to the Test-Point “
TESTmA
”,
(
see fig.2
)
the value reach the
mV
value as shown in
Table 3 on column 6
[corresponding to mA output value
(
±0.2mA
) as indi-
cated in
column 7
. T
he central unit should be display about the %LEL value (±2) as indicated in
column 8
].
If the re-
sult is different, is necessary to recalibrate the sensor (
see “Calibration”
).
Then, close the gas bottle, remove TC011.
Then, the mA output will slowly decrease up to 4mA.
Using a cylinder with the specific gas/Air mixture, the output signal will correspond to the gas used. (Example if
you have to verify a hydrogen detector, using a cylinder with H
2
at 0.8% v/v (20% LIE) in air, the mA output will be
approximately 7.2 mA (corresponding about to 72mV measured on "
TESTmA
”).
FR
DESCRIPTION
Le
TS282P
est un transmetteur (4÷20mA) pour gaz et vapeurs combustibles avec capteur catalytique Pellistor
pouvant également être utilisé en systèmes centralisés d'alarme pour l’industrie et le tertiaire. Le détecteur est
constitué par une boîtier contenant le circuit électronique et les borniers de raccordement; dans le porte capteur,
placé dans la partie inférieure du boîtier, est logée une "
cartouche capteur échangeable
" contenant l'élément sen-
sible et les données identificatrices et de réglage.
Le
TS282P
est un transmetteur sur 3 fils avec un signal de sortie
S
4÷20 mA avec fond d’échelle à 100% de la LIE
(
Limite Inférieure d'Explosivité
), du gaz mesuré (
Tableau 3
) Il s’utilise en se raccordant sur les centrales d’alarmes mono
et multivoies Tecnocontrol. Sur le couvercle, se trouvent les touches de codage F1 et F2 pour les opérations de vé-
rification et calibrage et 3 LED indiquant les conditions de fonctionnement:
Signalisations et commandes:
Led Rouge "ALARM":
signal d'alarme ALARM (20%LIE).
Led Vert "ON":
fonctionnement normal.
Led Jaune "FAULT":
capteur en panne ou déconnecté ou saturé ou échu.
Touches F1
et
F2
pour les opérations de vérification et calibrage
MODÈLES
Le
TS282PM
permet de détecter le
méthane (CH
4
gaz naturel)
. Le méthane est un gaz plus léger que l'air. Sa
densité relative à l'air est 0,55 et sa LIE, est 4,4%v/v, exprimé en % Volume.
Le
TS282PG
permet de détecter le
GPL
. Le GPL est un gaz plus lourd que l'air, formé d'un mélange composé de
20-30% de propane (C
3
H
8
) et de 70-80% de butane (C
4
H
10
). Sa densité relative à l'air est 1,56 pour le Propane et
2,05 pour le butane; la LIE, est 1,7%v/v pour le propane et 1,4%v/v pour le butane. Les étalonnages pour GPL doi-
vent être exécutés pour gaz butane qui est l'élément le plus présent dans le GPL.
Le
TS282PI
permet de détecter
l’hydrogène (H
2
)
qui est le plus léger gaz existant, il est inodore, sans couleur, ex-
trêmement inflammable. Sa densité relative à l'air est 0,07 et sa LIE, est 4%v/v, exprimé en % Volume.
Le
TS282PB
permet de détecter les
vapeurs d’essence
, qui constituent un gaz plus lourd de l'air, extrêmement
inflammable. Sa densité relative à l'air est 2,8 et sa LIE, est 1,2%v/v, exprimé en % Volume.
Le
TS282PX
à la demande, est étalonnable pour les gaz indiqués au
Tableau 3.