INSTALLATION AND SETTING INSTRUCTIONS
- 20 -
Connection to the condensate drain fittings
WARNING
Pipes with external diameter ranging between 24 and 30 mm are to be used in connecting the air
treatment unit to the syphon. The head must not be smaller than 25 mm.
The total weight of the condensate drain system must not weigh on the equipment, and must be
suitably and separately mounted.
The configuration of the condensate drain system must facilitate the removal of the inspection panels.
The condensate drain system must be easily disassembled to perform inspection and/or maintenance
operations.
The two-condensate drain systems of the unit should be separately connected.
LEVEL SWITCH (PROVIDED WITH THE APPLIANCE )
A level switch
must compulsorily
be installed in the chimney
flue “T”
-shaped fitting, in order to stop the
burner in case of accidental flooding of the heat exchanger (ex. in case of failure in the condensate drain
system)
condensate
drain
condensate
drain