background image

IST-2193.KM02.01/B 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag. 11 / 11 

 

 

 

TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI ) 

 Tel: 02/26 92 28 90   Fax: 02/21 33 734

 

 

 

 

 

 

0,3L/min

 

TC011

 

Fig.2

 - TC011 Tester di calibrazione 

Calibration Tester / Tester d’étalonnage

 

Fig.1 - 

Verifica

 / Test / Vérification

 

 

Centralina Gas

 

Gas Control Unit 
Centrale de détection

 

+  -  S 

mV

 

mV TEST

 

40÷200mV

 

F2 

F1 

TP2- 

S

 

+

 

-

 

LED Verde 

Green / Vert

 

LED Giallo 

Yellow / Jaune 

TP1+ 

Tasti 

/ Key / Touches

 

“S” = 

Uscita 4÷20 mA 

4÷20 mA Output 

Sortie en 4÷20 mA

 

Imbocco Femmina Conico ¾” EN 10226-1 

”¾” 

EN 10226-1 

Female Conical Thread 

Entrée femelle Conique ¾” 

EN 10226-1 

Fissaggio

 - fori di fissaggio Ø 6mm 

Fastening

 - mounting holes Ø 6mm. 

Fixation murale

 - trous de fixation de Ø 6mm 

190 

65 

83 

105 

70 

Ø42 

107 

Fig. 3 –

 

Dimensioni /

 Size / Dimensions 

Содержание SE193 KB

Страница 1: ...r Capteur Catalitico Catalityc Catalytiques Campo di misura Standard range Champ de mesure 0 20 LIE LEL Limite del Sensore Sensor limits Limite échelle 50 LIE LEL Preriscaldo Preheating Préchauffage 60 secondi seconds secondes Tempo di risposta Response time Temps de résponse T90 60 secondi seconds secondes Precisione Accuracy Precision 10 2 LIE LEL Deriva a lungo termine in aria pulita Long time ...

Страница 2: ...po il rilevatore è in grado di rilevare il gas ma raggiunge le condizioni di stabilità ottimali dopo circa 48 ore di funzionamento continuo In seguito si consiglia di verificare in aria pulita che l uscita sia circa 4 mA 0 LIE sulla centrale cui è collegato il rilevatore e solo se necessario procedere alla Regolazione del 4mA come indicato avanti in VERIFICA FUNZIONAMENTO Guasti in caso di guasto ...

Страница 3: ...rafo VERIFICA Importante Il sensore catalitico funziona solo in presenza d Ossigeno Non usare gas puri o l accendino direttamente sul sensore che potrebbe essere irrimediabilmente danneggiato Nota Il rilevatore non è in grado di rivelare perdite che avvengono fuori del locale in cui è installato o all interno dei muri o sotto il pavimento ATTENZIONE Considerare che in ambienti particolarmente inqu...

Страница 4: ...te il rilevatore e va eseguita quando la VERIFICA non è stata superata Attenzione Durante la Calibrazione l uscita in mA diventerà 0mA AVVERTENZA La Calibrazione va eseguita esclusivamente in aria pulita ambiente senza la presenza di gas in fiammabili o altri inquinanti e usando solo la miscela Gas Metano al 20 LIE 0 88 v v in aria 20 9 O2 circa 1 Dopo aver eseguito il Codice Calibrazione il Led V...

Страница 5: ...rate but it is necessary as soon as possible to replace it with a new one Periodical testing The verification with Gas Air mixture is the only safe method to check the effective operation of the detector and the correct response to the gas It is recommended to perform the testing every 6 12 months After 2 year we advise to perform the recalibration of the circuit with Gas Air mixture as explained ...

Страница 6: ...l the Green Led doesn t switch off for a moment Then the next key can be pressed In case of error the Yel low LED flashes quickly just wait about 10 seconds and the sequence is automatically cancelled Calibration Kit and Sample Gas Bottles for Calibration Check and Full Calibration please only using a mixture 20 LEL 0 88 v v Methane in Air 20 9 Oxygen Catalytic sensors cannot work in oxygen defici...

Страница 7: ... de chauffage et les environ nements à protéger des fuites éventuelles de gaz tels que le méthane le GPL etc Les sondes sont produites en différentes versions que présentent les mêmes caractéristiques Ils sont sondes de gaz 4 20mA sur 3 fils permettant de détecter des gaz combustibles et utilisent un capteur à combustion catalytique étalonné jusque 20 de la LIE Limite Inférieure d Explosivité La s...

Страница 8: ...ilation Montage en Fig 3 sont indiquées les dimensions La fixation murale doit être effectuée en utilisant les trous de fixa tion de Ø 6mm Le détecteur doit être monté en position verticale avec le capteur tourné vers le bas Évitez les obstructions qui empêchent la diffusion d air vers le capteur Considérez que les mouvements d air peu vent affecter la détection de gaz Évitez de monter le détecteu...

Страница 9: ...ité et avoir inséré le Code Test ÉTAT DU TEST ÉLECTRIQUE LED JAUNE LED VERTE SORTIE en mA S CENTRALE Après avoir entré le code de test OFF OFF 0 mA FAULT Avvio Test Elettrico ON ON 0 mA pendant 2 secondes FAULT Dans les 2 secondes la sortie en mA OFF ON devient 4 mA pendant 5 secondes NORM dans les 2 secondes la sortie en mA ON ON devient 20 mA pendant 5 secondes ALARM Fin de test et fonctionnemen...

Страница 10: ...édure sans réinsérer la séquence Si la condition persiste il sera nécessaire de remplacer et ou renvoyer le détecteur au fournisseur pour réparation Tabella 1 Table 1 Tableau 1 Centrali collegabili agli SE193K Control unit which can be connected to the SE193K series Centrales raccordable au SE193K Modello Model Modelé N Rilevatori Detectors number nombre de sondes SE127K SE128K SE139K ID250K 1 SE1...

Страница 11: ...tion Centralina Gas Gas Control Unit Centrale de détection S mV mV TEST 40 200mV F2 F1 TP2 S LED Verde Green Vert LED Giallo Yellow Jaune TP1 Tasti Key Touches S Uscita 4 20 mA 4 20 mA Output Sortie en 4 20 mA Imbocco Femmina Conico EN 10226 1 EN 10226 1 Female Conical Thread Entrée femelle Conique EN 10226 1 Fissaggio fori di fissaggio Ø 6mm Fastening mounting holes Ø 6mm Fixation murale trous de...

Отзывы: