background image

5

Sensor installation

Correct arrangement and installation of the sensors is extremely important for correct functioning of

the system. To this end, also ensure that they are completely inserted in their sensor wells. The cable

fittings provided serve as strain relief. When used outdoors, no water must be allowed to penetrate

the sensor wells (

risk of frost

). The contact sensors must be insulated well to protect them from be

-

ing influenced by the ambient temperature.
Sensors should generally not be exposed to moisture (such as condensation) since this can diffuse

through the cast resin and damage the sensor. If this happens, heating the sensor to 90 °C for an

hour may help. When using sensor wells in stainless steel cylinders or swimming pools, particular

attention must be given to their corrosion resistance.

Collector sensor (grey lead with junction box):

 Either insert into a pipe which is brazed or riveted

directly to the absorber and protrudes from the collector housing, or insert a tee into the flow

manifold of the outermost collector into which the sensor well, together with the brass cable fit

-

ting (= protection against moisture), can be inserted; then insert the sensor. To protect against

lightning damage, the junction box has a surge protection (voltage dependent resistor) which is

clamped in parallel between the sensor and the extension cable.

Boiler sensor (boiler flow):

 This sensor is either inserted into a sensor well in the boiler or fitted

to the flow line as close to the boiler as possible.

DHW cylinder sensor:

 The sensor required for the solar thermal system should be used with a

sensor well for finned tube heat exchangers just above the exchanger or, if integrated smooth

tube heat exchangers are used, in the lower third of the exchanger or the exchanger’s return out

-

let so that the sensor well protrudes into the heat exchanger tube. The sensor monitoring the

heating of the DHW cylinder by the boiler is installed at a level corresponding to the amount of

domestic hot water required during the heating season. The supplied cable fitting acts as strain

relief. Installation below the associated coil or heat exchanger is not permissible under any cir

-

cumstances.

Buffer sensor:

 The sensor required for the solar thermal system is fitted in the lower section of

the cylinder just above the solar indirect coil using the sensor well supplied. The supplied cable

fitting acts as strain relief. As the reference sensor for the heating system hydraulics, it is recom

-

mended to insert the sensor into the sensor well between the centre and upper third of the buffer

cylinder, or positioned against the cylinder wall underneath the insulation.

Pool sensor (swimming pool):

 Fit a tee into the suction line immediately on the pool outlet and

insert the sensor with a sensor well. In the process, ensure the material used is corrosion-resist

-

ant. A further option would be to fit the sensor as a contact sensor with appropriate thermal insu

-

lation against ambient influences.

Contact sensor:

 Use scroll springs, pipe clips, etc. to attach the contact sensor to the respective

line. Ensure the material used is suitable (corrosion, temperature resistance, etc.). Then insulate

the sensor thoroughly so that the pipe temperature is captured accurately and ambient tempera

-

tures cannot falsify the result.

DHW sensor:

 A rapid reaction to changes in the water volume is extremely important when using

the  controller  in  systems  that  generate  domestic  hot  water  by  means  of  an  external  heat

exchanger and variable speed pump (freshwater module). Therefore fit the DHW sensor directly

on the heat exchanger outlet. This ultra-quick sensor (special accessory, type MSP) should pro

-

trude into the output with the aid of a tee sealed in with an O-ring. The heat exchanger should be

installed upright with the DHW outlet at the top

Radiation sensor:

 The parallel collector orientation is important in order to obtain a measure

-

ment that corresponds to the collector position. Consequently it should be secured to the sheet

steel covering or adjacent to the collector on an extension of the mounting rail. To this end, the

sensor casing has a blind hole that can be opened at any time. The sensor is also available as a

wireless version.

Содержание UVR610K

Страница 1: ...www ta co at UVR610K FREELY PROGRAMMABLE UNIVERSAL CONTROLLER Console variant Installation instructions English Manual Version 1 17...

Страница 2: ...s 9 CAN Bus network 10 Terminal diagram CAN bus cable 10 Guidelines for the topology of a CAN network 10 Technical principles 10 Lightning protection 11 Examples of different network versions 11 Cable...

Страница 3: ...this is the case disable the controller and equipment and secure against unintentional use Maintenance If treated and used correctly the device will not require any maintenance Use a cloth mois tened...

Страница 4: ...pacing 5 08 mm SD card If an SD card is required this must be a Micro SD card with no more than 32 GB storage capacity and FAT32 formatting Opening the module The device may only be opened at the manu...

Страница 5: ...d during the heating season The supplied cable fitting acts as strain relief Installation below the associated coil or heat exchanger is not permissible under any cir cumstances Buffer sensor The sens...

Страница 6: ...dance with the relevant local regula tions Note In line with regulations the system must be equipped with protection against lightning surge arrester Sensor failures due to thunderstorms and static el...

Страница 7: ...f analogue output A9 to an M Bus interface In the po sition shown at the top the analogue output is active Mains connection Power is supplied through a power supply unit integrated into the module The...

Страница 8: ...T500 sensors must be screened If screened cables are used the screen must be connected to the sensor earth GND All sensor leads with a cross section of 0 5 mm2 can be extended to up to 50 metres With...

Страница 9: ...when capturing data from two controllers with a single datalogger Never run the data cable together with a CAN BUS cable in the same conduit Terminal diagram DL bus data cable Bus load of DL sensors A...

Страница 10: ...ing The BUS cable screen must be connected well at every node to provide continuity For larger net works we recommend including the screen in the equipotential bonding in line with the exam ples shown...

Страница 11: ...e 230 V mains supply cable indirect lightning strike appropriate lightning conductors and surge arresters compliant with local regulations must be fitted in the upstream distribution systems In order...

Страница 12: ...isconnected network is connected at each bus converter to CAN bus earth GND This screen must not be directly earthed Without CAN Bus surge arresters this version only protects against potential differ...

Страница 13: ...n order to be able to communicate with each other Recommendations A 2x2 pole screened twisted pair twist CAN L with CAN H or 12 V with GND with a cable cross section of at least 0 5 mm and a conductor...

Страница 14: ...pole cable and termination of the ter minal network nodes network inside one building Each CAN network is to be provided with a 120 ohm BUS terminator at the first and last network sub scriber termin...

Страница 15: ...s perfectly with a low number of CAN nodes and an inexpensive J Y St Y EIB KNX 2x2x0 8 KNX bus cable with a char acteristic impedance of 75 to 90 ohm 3 Up to a bus length of 150 m and with only a few...

Страница 16: ...e back With jumper J plugged in output 6 is not po tential free Example Connecting a pump C L Phase conductor A6 Normally open contact N O NC Normally closed contact N C If the jumper is unplugged out...

Страница 17: ...come the positive pole the GND connection is the negative pole If programmed as a switching output a maximum of 1 HIREL 230V or HIREL PF auxiliary relay can be connected M Bus Output 9 can be converte...

Страница 18: ...rminal W therefore corresponds to phase conductor L If the fuse is removed both outputs will be potential free whilst remaining connected to one another via root W The relay module can be connected to...

Страница 19: ...or up to 4 M Bus meters 24V Supply for external 24 V devices max 6 W in total including the 12 V devices Max bus load DL bus 100 CAN bus Standard data rate 50 kbit s adjustable from 5 to 500 kbit s Di...

Страница 20: ...c from short circuits and from voltage surges in connec tion with the integrated surge protection The glass tube fuse is located on the back of the module Realistic temperatures but faulty operation o...

Страница 21: ...relay outputs may also be potential free It is thus only possible to directly switch a 230 V consumer when the appropriate wiring has been implemented If it is not possible to switch the output ON or...

Страница 22: ...circuits between cables leads Check for short circuits across GND or screen and the signal cables Check for earth loops for this the screen is undone at each node and the current tested If there is a...

Страница 23: ...kaging manual and type label Issuer Technische Alternative RT GmbH A 3872 Amaliendorf Langestra e 124 This declaration is submitted by Dipl Ing Andreas Schneider General manager 19 06 2019 This declar...

Страница 24: ...installation instructions or incorrect maintenance 4 The warranty claim will expire if repairs or actions are carried out by persons who are not authorised to do so or have not been so authorised by...

Отзывы: