Incorrect temperatures

 could be the result of the following:

• Values such as -9999.9 in the case of a sensor short circuit or 9999.9 in the case of a sensor

lead break may not be the result of a material or termination error. Is the correct sensor type

selected in the input menu (KTY, PT1000, RAS, GBS, etc.)?

• A sensor can also be checked without a tester simply by swapping the sensor that is proba

-

bly faulty with one that works at the terminal strip and checking the temperature display. If

the error is reproduced, the problem is the sensor. However, if the problem remains on the

same input of the device, the fault is either due to the sensor type setting or the input itself is

faulty (such as faulty surge protection).

Table of resistances of various sensor types

If the sensor is faulty, note the sensor type when replacing. While it is possible to use a different type

of sensor, the parameters for that input also have to be set to suit the type of sensor used.
The current standard type used by Technische Alternative is PT1000.
KTY (2 kΩ) was the standard type until 2010/2011.

Manual switching of an output not possible:

• Ensure that output 6 is generally potential-free and therefore does not carry live voltage. Aux

-

iliary relay outputs may also be potential-free. It is thus only possible to directly switch a 230 

V consumer when the appropriate wiring has been implemented.

• If it is not possible to switch the output ON or OFF in manual mode, a message may be active 

at that moment which switches the corresponding output dominantly ON or OFF (red frame 

around the output symbol; indication of the message in the upper status bar). Subject to pro

-

gramming and user status, manual mode is not possible in this case.

Troubleshooting – hardware

In a clear case of a hardware fault, please return the device to your retailer or the manufacturer for

repair. In this case it is essential to include a fault description with the device (simply stating "the de

-

vice does not work, please repair" is insufficient). Processing is accelerated if an RMA number is re

-

quested via our homepage www.ta.co.at.The defect must be clarified with our technical support

beforehand.

Temp.

[°C]

0

10

20

25

30

40

50

60

70

80

90

100

PT1000

[Ω]

1000 1039 1078 1097 1117 1115 1194 1232 1271 1309 1347 1385

KTY (2kΩ)  [Ω]

1630 1772 1922 2000 2080 2245 2417 2597 2785 2980 3182 3392

KTY (1kΩ) [Ω]

815

886

961 1000 1040 1122 1209 1299 1392 1490 1591 1696

PT100

[Ω]

100

104

108

110

112

116

119

123

127

131

135

139

PT500

[Ω]

500

520

539

549

558

578

597

616

635

654

674

693

Ni1000

[Ω]

1000 1056 1112 1141 1171 1230 1291 1353 1417 1483 1549 1618

Ni1000

[Ω]

TK5000

1000 1045 1091 1114 1138 1186 1235 1285 1337 1390 1444 1500

Содержание UVR610K

Страница 1: ...www ta co at UVR610K FREELY PROGRAMMABLE UNIVERSAL CONTROLLER Console variant Installation instructions English Manual Version 1 17...

Страница 2: ...s 9 CAN Bus network 10 Terminal diagram CAN bus cable 10 Guidelines for the topology of a CAN network 10 Technical principles 10 Lightning protection 11 Examples of different network versions 11 Cable...

Страница 3: ...this is the case disable the controller and equipment and secure against unintentional use Maintenance If treated and used correctly the device will not require any maintenance Use a cloth mois tened...

Страница 4: ...pacing 5 08 mm SD card If an SD card is required this must be a Micro SD card with no more than 32 GB storage capacity and FAT32 formatting Opening the module The device may only be opened at the manu...

Страница 5: ...d during the heating season The supplied cable fitting acts as strain relief Installation below the associated coil or heat exchanger is not permissible under any cir cumstances Buffer sensor The sens...

Страница 6: ...dance with the relevant local regula tions Note In line with regulations the system must be equipped with protection against lightning surge arrester Sensor failures due to thunderstorms and static el...

Страница 7: ...f analogue output A9 to an M Bus interface In the po sition shown at the top the analogue output is active Mains connection Power is supplied through a power supply unit integrated into the module The...

Страница 8: ...T500 sensors must be screened If screened cables are used the screen must be connected to the sensor earth GND All sensor leads with a cross section of 0 5 mm2 can be extended to up to 50 metres With...

Страница 9: ...when capturing data from two controllers with a single datalogger Never run the data cable together with a CAN BUS cable in the same conduit Terminal diagram DL bus data cable Bus load of DL sensors A...

Страница 10: ...ing The BUS cable screen must be connected well at every node to provide continuity For larger net works we recommend including the screen in the equipotential bonding in line with the exam ples shown...

Страница 11: ...e 230 V mains supply cable indirect lightning strike appropriate lightning conductors and surge arresters compliant with local regulations must be fitted in the upstream distribution systems In order...

Страница 12: ...isconnected network is connected at each bus converter to CAN bus earth GND This screen must not be directly earthed Without CAN Bus surge arresters this version only protects against potential differ...

Страница 13: ...n order to be able to communicate with each other Recommendations A 2x2 pole screened twisted pair twist CAN L with CAN H or 12 V with GND with a cable cross section of at least 0 5 mm and a conductor...

Страница 14: ...pole cable and termination of the ter minal network nodes network inside one building Each CAN network is to be provided with a 120 ohm BUS terminator at the first and last network sub scriber termin...

Страница 15: ...s perfectly with a low number of CAN nodes and an inexpensive J Y St Y EIB KNX 2x2x0 8 KNX bus cable with a char acteristic impedance of 75 to 90 ohm 3 Up to a bus length of 150 m and with only a few...

Страница 16: ...e back With jumper J plugged in output 6 is not po tential free Example Connecting a pump C L Phase conductor A6 Normally open contact N O NC Normally closed contact N C If the jumper is unplugged out...

Страница 17: ...come the positive pole the GND connection is the negative pole If programmed as a switching output a maximum of 1 HIREL 230V or HIREL PF auxiliary relay can be connected M Bus Output 9 can be converte...

Страница 18: ...rminal W therefore corresponds to phase conductor L If the fuse is removed both outputs will be potential free whilst remaining connected to one another via root W The relay module can be connected to...

Страница 19: ...or up to 4 M Bus meters 24V Supply for external 24 V devices max 6 W in total including the 12 V devices Max bus load DL bus 100 CAN bus Standard data rate 50 kbit s adjustable from 5 to 500 kbit s Di...

Страница 20: ...c from short circuits and from voltage surges in connec tion with the integrated surge protection The glass tube fuse is located on the back of the module Realistic temperatures but faulty operation o...

Страница 21: ...relay outputs may also be potential free It is thus only possible to directly switch a 230 V consumer when the appropriate wiring has been implemented If it is not possible to switch the output ON or...

Страница 22: ...circuits between cables leads Check for short circuits across GND or screen and the signal cables Check for earth loops for this the screen is undone at each node and the current tested If there is a...

Страница 23: ...kaging manual and type label Issuer Technische Alternative RT GmbH A 3872 Amaliendorf Langestra e 124 This declaration is submitted by Dipl Ing Andreas Schneider General manager 19 06 2019 This declar...

Страница 24: ...installation instructions or incorrect maintenance 4 The warranty claim will expire if repairs or actions are carried out by persons who are not authorised to do so or have not been so authorised by...

Отзывы: