Incorrect temperatures
could be the result of the following:
• Values such as -9999.9 in the case of a sensor short circuit or 9999.9 in the case of a sensor
lead break may not be the result of a material or termination error. Is the correct sensor type
selected in the input menu (KTY, PT1000, RAS, GBS, etc.)?
• A sensor can also be checked without a tester simply by swapping the sensor that is proba
-
bly faulty with one that works at the terminal strip and checking the temperature display. If
the error is reproduced, the problem is the sensor. However, if the problem remains on the
same input of the device, the fault is either due to the sensor type setting or the input itself is
faulty (such as faulty surge protection).
Table of resistances of various sensor types
If the sensor is faulty, note the sensor type when replacing. While it is possible to use a different type
of sensor, the parameters for that input also have to be set to suit the type of sensor used.
The current standard type used by Technische Alternative is PT1000.
KTY (2 kΩ) was the standard type until 2010/2011.
Manual switching of an output not possible:
• Ensure that output 6 is generally potential-free and therefore does not carry live voltage. Aux
-
iliary relay outputs may also be potential-free. It is thus only possible to directly switch a 230
V consumer when the appropriate wiring has been implemented.
• If it is not possible to switch the output ON or OFF in manual mode, a message may be active
at that moment which switches the corresponding output dominantly ON or OFF (red frame
around the output symbol; indication of the message in the upper status bar). Subject to pro
-
gramming and user status, manual mode is not possible in this case.
Troubleshooting – hardware
In a clear case of a hardware fault, please return the device to your retailer or the manufacturer for
repair. In this case it is essential to include a fault description with the device (simply stating "the de
-
vice does not work, please repair" is insufficient). Processing is accelerated if an RMA number is re
-
quested via our homepage www.ta.co.at.The defect must be clarified with our technical support
beforehand.
Temp.
[°C]
0
10
20
25
30
40
50
60
70
80
90
100
PT1000
[Ω]
1000 1039 1078 1097 1117 1115 1194 1232 1271 1309 1347 1385
KTY (2kΩ) [Ω]
1630 1772 1922 2000 2080 2245 2417 2597 2785 2980 3182 3392
KTY (1kΩ) [Ω]
815
886
961 1000 1040 1122 1209 1299 1392 1490 1591 1696
PT100
[Ω]
100
104
108
110
112
116
119
123
127
131
135
139
PT500
[Ω]
500
520
539
549
558
578
597
616
635
654
674
693
Ni1000
[Ω]
1000 1056 1112 1141 1171 1230 1291 1353 1417 1483 1549 1618
Ni1000
[Ω]
TK5000
1000 1045 1091 1114 1138 1186 1235 1285 1337 1390 1444 1500