DL bus
44
DL input
Sensor values from DL bus sensors are transferred via a DL input.
Up to 32 DL inputs can be programmed.
Example:
Programming the parameters of DL input 1
Select:
Analogue or digital
DL bus address and DL bus index
Every DL sensor must have its own
DL bus address.
Setting the address of a DL sensor is described
in the sensor's datasheet.
Most DL sensors can measure various different values (e.g. flow rate and temperatures). Every value
measured must be given its own
index
number. The applicable index number can be found in the DL
sensor's datasheet.