Outputs
27
Display of links
When you select this icon, the output's links to the functions will be displayed.
Example:
In this example, output 1 is controlled by two functions, and it has just been switched on by function 1
(DHW demand 1).
Tapping a function takes you directly to the menu for that function.
Blocking protection
Circulating pumps which do not run for a long period (e.g. heating circuit
pump during the summer) often encounter start-up problems as a result
of corrosion. This problem can be avoided by starting the pump periodical
-
ly for 30 seconds.
The menu item
Blocking protection
added after output 10 allows you to
specify a time and all the outputs to receive blocking protection.
The outputs selected in the Output assignment will be switched on for 30
seconds on Tuesday and Friday at 4:30 p.m. if the output has not been ac
-
tive since the last controller start or since blocking protection was last in
-
itiated.
The outputs 3, 4, 6 and 7 were selected.
The controller does not switch on all the outputs at the same time, but in
-
stead begins with one output, switches to the next after 30 seconds, and
so on.