CAN bus
41
Designation and transmission condition
Every CAN analogue output can be given its own designation. The designation can be selected from
various designation groups or can be user defined, as for the inputs.
Example:
Transmission condition
Example:
If change > 1.0 K
If the current value has changed by more than 1.0 K compared to the last
transmitted value, a new transmission is made. The unit used by the
source is applied to the output value (minimum setting: 0.1 K).
Blocking time 10 s
If the value changes by more than 1.0 K within 10 seconds of the last
transmission, the value is nevertheless only transmitted again after 10
seconds (minimum setting: 1 sec.).
Interval time 5 m
The value is transmitted every 5 minutes even if it has not changed by
more than 1.0 K since the last transmission (minimum setting: 1 minute).