Outputs
20
Outputs 1+2, 3+4, 5+6, 7+8 and 9+10 as an output pair
These outputs can be used as single switching outputs or as an output pair together with the follow
-
ing switching output (e.g. to control a mixer drive).
The output pairs
1+2
,
3+4
and
5+6
are available as standard. The output pairs
7+8
and
9+10
require
the use of auxiliary relays (relay modules).
The output pair is only programmed at the first of the affected outputs (e.g. output 1 for output
pair 1+2).
Runtime
The mixer runtime must be entered for
every
output pair.
If a mixer runtime of 0 is entered, the output pair will not be utilised.
Runtime limit
When the runtime limit is active, output pair control is terminated if the re
-
maining runtime of 20 minutes has counted down to 0. The remaining
runtime is reloaded if the output pair is switched to manual mode, is
switched by a message (to dominant ON or OFF), changes its direction of
control, or if enabling is switched from OFF to ON.
If the runtime limit is deactivated, the remaining runtime only counts down to 10 seconds and output
pair control is not terminated.
If two different functions act on the two outputs in the output pair simultaneously, the output with
the lower number ("OPEN" command) will be activated.
Exception:
the
"Message"
function – if the simultaneous command comes from this function, the
output with the higher number ("CLOSE" command) will be activated.