Application 3
Room drying with minimum temperature monitoring and
“Comfort ventilation”
The humidity should be lowered in a humid room. If a ventilated room is too cold, the fan is switched
off.
In order to guarantee a minimum room air quality for every day, even on days
-
with humid exterior air or
-
a drop below the set minimum room temperature
the fan is switched on with “comfort ventilation” for one or several time windows, preferable in the cool
morning hours.
The fan for room drying runs if:
-
the absolute humidity is lower outside than inside
and
-
the room temperature is high enough (protection against too much cooling down in the winter)
and
the optional interval switch ("Timer") is active.
The fan for “comfort ventilation” runs
-
Daily according to time window
Recommended settings for UVR61-3
Menu
ENTER Par
Code:
32
Menu
ENTER Men
Code:
64
Program
PR
129
EXT DL
Linking of output
LO
OFF
Ext. Sensor E1
14
max 1
/
75/70
no effect
Ext. Sensor E2
24
max 3
10
minimum room temperature
Ext. Sensor E3
22
min1
/
2/1
minimum humidity, inside
Ext. Sensor E4
12
min3
9
If the temperature falls below this
room temperature, the fan is
blocked.
diff1
/
1,0/0,5
minimum humidity differential,
outside/inside
SENSOR
(value transfer)
TIME W
Sensor S1
E1
Time window 1
Within this time window, the fan
runs independently of the humidity
and temperature conditions.
Sensor S2
E2
Outputs
OPO 2
Sensor S3
E3
Time on/off
4.00/4.30
Sensor S4
E4
Time window 2
Outputs
OPO 2
Time on/off
5.30/6.00
Time window 3
Outputs
OPO 2
Time on/off
7.30/8.00
TIMER
optional
Outputs
OPA 1
The fan is switched ON and OFF
alternately (ON and OFF time in
minutes).
Release time
00:20
Block time
00:40