Technische Alternative UVR61-3 Скачать руководство пользователя страница 2

Planning principles 

 

Blow direction of the fan always from the outside to the inside!

  

If the fan blows from the inside to the outside, there is a danger of warm and thus humid air 
following from adjacent building parts thus increasing the problem! 

 

A supply air fan is usually sufficient!

  

The “exhaust air” is pushed out through leaks in the building. With building that are very leak-
proof, an overflow opening (flap, …) must be created. If supply and exhaust fans are used, the 
efficiency of the exhaust fan must never be above that of the supply fan. 

 

The ventilated buildings (the ventilated room) must be as leak-proof as possible!

  

In order to prevent unwanted penetration of humid air through natural circulation, windows and 
doors should be closed. 

  In order to (especially in the winter) keep the cooling of rooms within limits, 

timer-controlled 

interval operation

 is useful. An additional minimum temperature monitoring can be imple-

mented. 

  The 

exterior humidity sensor

 must not be directly subjected to insolation or rain. If neces-

sary, the sensor will be protected with a small shield. 

 

Operation 

The large display contains the symbols for all important information and a plain text area. Naviga-

tion with the coordinate keys is matched to the display sequence. 



 

Navigation keys for selecting the display and for changing parameters.

 

Entry to a menu, release of a value for changing with the navigation keys (enter key).



 

Return from the menu level selected last, exit from the parameterising of a value (return 
key).

The side keys 



 are the navigation keys for selecting the required display such as e.g. collector 

or tank temperature during regular operation. A different sensor symbol and the corresponding tem-
perature are displayed for each pressure. 

 

The appropriate symbol is displayed for information above the text line (according to the example 

of the collector temperature). The choice of symbol has no effect on the control function. All instruc-
tion during parameterisation are below the text line. 

 
To the side of the display, the currently active outputs are identifiable on the 

green

 illuminated figures 1

–3.  

 

 

 

 

 

 

 

 

 

 
 

 

     

   2 
 1 

Содержание UVR61-3

Страница 1: ...y Building drying can be carried out with all universal controllers that have a DL bus with the excep tion of UVR63 H Goal Lowering humidity through specific ventilation with dry air Improvement of ai...

Страница 2: ...y sensor must not be directly subjected to insolation or rain If neces sary the sensor will be protected with a small shield Operation The large display contains the symbols for all important informat...

Страница 3: ...navigation keys The value is saved pressing the arrow key in upward direction View of the display after the first start of controller UVR61 3 Display after switching on The sensor values initially sho...

Страница 4: ...r values in the menu SENSOR Access to menu ENTER Par and definition of the parameters Controller version Program number Linking of output First parameter value max1 Second parameter value max1 Value b...

Страница 5: ...inking of output LO OFF Ext Sensor E1 14 max 1 75 70 no effect Ext Sensor E2 24 min 1 2 1 minimum humidity inside SENSOR value transfer diff 1 1 0 0 5 minimum humidity differential outside inside TIME...

Страница 6: ...2 min3 9 If the temperature falls below this room temperature the fan is blocked diff1 1 0 0 5 minimum humidity differential outside inside SENSOR value transfer TIMER optional Sensor S1 E1 Outputs OP...

Страница 7: ...runs Daily according to time window Recommended settings for UVR61 3 Menu ENTER Par Code 32 Menu ENTER Men Code 64 Program PR 129 EXT DL Linking of output LO OFF Ext Sensor E1 14 max 1 75 70 no effect...

Страница 8: ...4 Interior room temperature Electrical connection UVR61 3 Output 3 must be made potential free For this the red jumper on the rear of the detacha ble upper controller part is removed Meaning of the lu...

Страница 9: ...f the room temperature is high enough Recommended settings for UVR61 3 Men ENTER Par Code 32 Menu ENTER Men Code 64 Program PR 129 EXT DL Linking of output LO OFF Ext Sensor E1 14 max 1 75 70 no effec...

Страница 10: ...ure Electrical connection UVR61 3 Output 3 must be made potential free For this the red jumper on the rear of the detachable upper controller part is re moved Meaning of the luminous digits 1 Fan oper...

Страница 11: ...DL Linking of out put LO OFF Ext Sensor E1 11 max 1 75 70 no effect Ext Sensor E2 21 max 2 100 95 no effect Ext Sensor E3 12 max 3 50 45 no effect Ext Sensor E4 22 min 1 2 1 Start threshold for insid...

Страница 12: ...he red jumper on the rear of the detachable upper controller part is re moved An external auxiliary relay whose contact is arranged in series with both other outputs is connected to output 2 We reserv...