Technische Alternative UVR61-3 Скачать руководство пользователя страница 6

Application 2 

Room drying with minimum temperature monitoring 

The humidity should be lowered in a humid room. If a ventilated room is too cold, the fan is switched 
off.  

The fan runs if: 

-

 

the absolute humidity is lower outside than inside 

and

  

-

 

the room temperature is high enough (protection against too much cooling down in the winter) 

and

 the optional interval switch ("timer") is active. 

Recommended settings for UVR61-3 

Menu 

ENTER Par 

Code: 

32

 

 

Menu 

ENTER Men 

Code: 

64

 

Program 

PR

 

129 

 

 

EXT DL 

 

Linking of output 

LO

 

OFF 

 

  Ext. Sensor E1 

14 

max 1  

 / 

 

75/70 

no effect

 

  Ext. Sensor E2 

24 

max 3 

 

10 

minimum room temperature

 

  Ext. Sensor E3 

22 

min1  

 / 

 

 2/1 

minimum humidity, inside

 

  Ext. Sensor E4 

12 

min3 

 

If the temperature falls below this 
room temperature, the fan is blocked.

 

 

 

 

diff1  

 / 

 

1,0/0,5 

minimum humidity differential, 
outside/inside

 

 

SENSOR

 (value transfer) 

TIMER

 

optional

 

 

Sensor S1 

E1 

Outputs  

OPA 1 

The fan is switched ON and OFF 
alternately (ON and OFF time in 
minutes).

 

  Sensor S2 

E2 

Release time 

00:20 

  Sensor S3 

E3 

Block time 

00:40 

  Sensor S4 

E4 

 

 

 

 

 

O1 

Auto 

 

 

 

O3 

Auto 

 

 

 

 

 

 

 

 

Anzeige 

 

 

 

 

T1 and E1 

Absolute interior humidity (g/m³, displayed in °C) 

T2 and E2 

Absolute exterior humidity (g/m³, displayed in °C) 

T3 and E3 

Exterior temperature  

T4 and E4 

Interior room temperature 

 

Electrical connection UVR61-3 

Output 3

 must be made 

potential-free

. For 

this, the red jumper on the rear of the detacha-
ble upper controller part is removed.

 

 

 

Meaning of the luminous digits 

1

: Fan operation for room drying activated 

3

 : Fan operation for room drying blocked 

because the room temperature is too 
low 

Содержание UVR61-3

Страница 1: ...y Building drying can be carried out with all universal controllers that have a DL bus with the excep tion of UVR63 H Goal Lowering humidity through specific ventilation with dry air Improvement of ai...

Страница 2: ...y sensor must not be directly subjected to insolation or rain If neces sary the sensor will be protected with a small shield Operation The large display contains the symbols for all important informat...

Страница 3: ...navigation keys The value is saved pressing the arrow key in upward direction View of the display after the first start of controller UVR61 3 Display after switching on The sensor values initially sho...

Страница 4: ...r values in the menu SENSOR Access to menu ENTER Par and definition of the parameters Controller version Program number Linking of output First parameter value max1 Second parameter value max1 Value b...

Страница 5: ...inking of output LO OFF Ext Sensor E1 14 max 1 75 70 no effect Ext Sensor E2 24 min 1 2 1 minimum humidity inside SENSOR value transfer diff 1 1 0 0 5 minimum humidity differential outside inside TIME...

Страница 6: ...2 min3 9 If the temperature falls below this room temperature the fan is blocked diff1 1 0 0 5 minimum humidity differential outside inside SENSOR value transfer TIMER optional Sensor S1 E1 Outputs OP...

Страница 7: ...runs Daily according to time window Recommended settings for UVR61 3 Menu ENTER Par Code 32 Menu ENTER Men Code 64 Program PR 129 EXT DL Linking of output LO OFF Ext Sensor E1 14 max 1 75 70 no effect...

Страница 8: ...4 Interior room temperature Electrical connection UVR61 3 Output 3 must be made potential free For this the red jumper on the rear of the detacha ble upper controller part is removed Meaning of the lu...

Страница 9: ...f the room temperature is high enough Recommended settings for UVR61 3 Men ENTER Par Code 32 Menu ENTER Men Code 64 Program PR 129 EXT DL Linking of output LO OFF Ext Sensor E1 14 max 1 75 70 no effec...

Страница 10: ...ure Electrical connection UVR61 3 Output 3 must be made potential free For this the red jumper on the rear of the detachable upper controller part is re moved Meaning of the luminous digits 1 Fan oper...

Страница 11: ...DL Linking of out put LO OFF Ext Sensor E1 11 max 1 75 70 no effect Ext Sensor E2 21 max 2 100 95 no effect Ext Sensor E3 12 max 3 50 45 no effect Ext Sensor E4 22 min 1 2 1 Start threshold for insid...

Страница 12: ...he red jumper on the rear of the detachable upper controller part is re moved An external auxiliary relay whose contact is arranged in series with both other outputs is connected to output 2 We reserv...

Отзывы: