Application 2
Room drying with minimum temperature monitoring
The humidity should be lowered in a humid room. If a ventilated room is too cold, the fan is switched
off.
The fan runs if:
-
the absolute humidity is lower outside than inside
and
-
the room temperature is high enough (protection against too much cooling down in the winter)
and
the optional interval switch ("timer") is active.
Recommended settings for UVR61-3
Menu
ENTER Par
Code:
32
Menu
ENTER Men
Code:
64
Program
PR
129
EXT DL
Linking of output
LO
OFF
Ext. Sensor E1
14
max 1
/
75/70
no effect
Ext. Sensor E2
24
max 3
10
minimum room temperature
Ext. Sensor E3
22
min1
/
2/1
minimum humidity, inside
Ext. Sensor E4
12
min3
9
If the temperature falls below this
room temperature, the fan is blocked.
diff1
/
1,0/0,5
minimum humidity differential,
outside/inside
SENSOR
(value transfer)
TIMER
optional
Sensor S1
E1
Outputs
OPA 1
The fan is switched ON and OFF
alternately (ON and OFF time in
minutes).
Sensor S2
E2
Release time
00:20
Sensor S3
E3
Block time
00:40
Sensor S4
E4
O1
Auto
O3
Auto
Anzeige
T1 and E1
Absolute interior humidity (g/m³, displayed in °C)
T2 and E2
Absolute exterior humidity (g/m³, displayed in °C)
T3 and E3
Exterior temperature
T4 and E4
Interior room temperature
Electrical connection UVR61-3
Output 3
must be made
potential-free
. For
this, the red jumper on the rear of the detacha-
ble upper controller part is removed.
Meaning of the luminous digits
1
: Fan operation for room drying activated
3
: Fan operation for room drying blocked
because the room temperature is too
low