Application 1
Room drying only
The humidity should be lowered in a humid room. As soon as the absolute exterior humidity is lower
than the one inside, a fan is switched on.
The fan runs if
-
the absolute humidity is lower outside than inside
and
-
the optional interval switch ("Timer") is active.
Recommended settings for UVR61-3
Menu
ENTER Par
Code:
32
Menu
ENTER Men
Code:
64
Program
PR
0
EXT DL
Linking of output
LO
OFF
Ext. Sensor E1
14
max 1
/
75/70
no effect
Ext. Sensor E2
24
min 1
/
2/1
minimum humidity, inside
SENSOR
(value transfer)
diff 1
/
1,0/0,5
minimum humidity differential,
outside/inside
TIMER
optional
Sensor S1 ->
E1
Outputs
OPA 1
The fan is switched ON and OFF
alternately (ON and OFF time in
minutes).
Sensor S2 ->
E2
Release time
00:20
Block time
00:40
O1
Auto
Display
T1 and E1
Absolute interior humidity (g/m³, displayed in
°C)
T2 and E2
Absolute exterior humidity (g/m³, displayed in
°C)
Electrical connection UVR61-3
Meaning of the luminous digits
1
: Fan operation for room drying
activated