Supplementary instructions for UVR61-3 

Building drying with ventilator 

 

A special application of the universal controller is the 

energy-saving

 and cost-effective drying of 

basements and other building parts with fan control. The special functionality (measurement of the 
absolute humidity) of the sensor RFS-DL enables this simple drying out of buildings in connection with 
the universal controller. The absolute humidity inside and outside is compared and a fan switched on 
or off accordingly.  
Building drying can be carried out with all 

universal controllers

 that have a DL bus (with the excep-

tion of UVR63-H). 

 

 

  

 Goal 

  Lowering humidity through specific ventilation with dry air  
  Improvement of air quality and odour with regular ventilation 
  Replacement of energy-intensive dehumidification devices  

 

 

Required material: 

Complete 

UVR61-GT

 set comprising:  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

 

 

1 universal controller 
01/UVR61-3-R 

2 humidity sensors 
01/RFS-DL 

RFS-DL 
for outside 

The address must be changed if the RFS-DL is 
installed 

outside

The 

DIP switch 1

 must be set to 

ON

This changes the sensor address to 2. 

UVR61-GT 

 

Vers. 1.6 EN 

Technische Alternative RT GmbH 

 

A-3872 Amaliendorf, Langestr. 124  

Tel +43 (0)2862 53635     [email protected] 

 

Содержание UVR61-3

Страница 1: ...y Building drying can be carried out with all universal controllers that have a DL bus with the excep tion of UVR63 H Goal Lowering humidity through specific ventilation with dry air Improvement of ai...

Страница 2: ...y sensor must not be directly subjected to insolation or rain If neces sary the sensor will be protected with a small shield Operation The large display contains the symbols for all important informat...

Страница 3: ...navigation keys The value is saved pressing the arrow key in upward direction View of the display after the first start of controller UVR61 3 Display after switching on The sensor values initially sho...

Страница 4: ...r values in the menu SENSOR Access to menu ENTER Par and definition of the parameters Controller version Program number Linking of output First parameter value max1 Second parameter value max1 Value b...

Страница 5: ...inking of output LO OFF Ext Sensor E1 14 max 1 75 70 no effect Ext Sensor E2 24 min 1 2 1 minimum humidity inside SENSOR value transfer diff 1 1 0 0 5 minimum humidity differential outside inside TIME...

Страница 6: ...2 min3 9 If the temperature falls below this room temperature the fan is blocked diff1 1 0 0 5 minimum humidity differential outside inside SENSOR value transfer TIMER optional Sensor S1 E1 Outputs OP...

Страница 7: ...runs Daily according to time window Recommended settings for UVR61 3 Menu ENTER Par Code 32 Menu ENTER Men Code 64 Program PR 129 EXT DL Linking of output LO OFF Ext Sensor E1 14 max 1 75 70 no effect...

Страница 8: ...4 Interior room temperature Electrical connection UVR61 3 Output 3 must be made potential free For this the red jumper on the rear of the detacha ble upper controller part is removed Meaning of the lu...

Страница 9: ...f the room temperature is high enough Recommended settings for UVR61 3 Men ENTER Par Code 32 Menu ENTER Men Code 64 Program PR 129 EXT DL Linking of output LO OFF Ext Sensor E1 14 max 1 75 70 no effec...

Страница 10: ...ure Electrical connection UVR61 3 Output 3 must be made potential free For this the red jumper on the rear of the detachable upper controller part is re moved Meaning of the luminous digits 1 Fan oper...

Страница 11: ...DL Linking of out put LO OFF Ext Sensor E1 11 max 1 75 70 no effect Ext Sensor E2 21 max 2 100 95 no effect Ext Sensor E3 12 max 3 50 45 no effect Ext Sensor E4 22 min 1 2 1 Start threshold for insid...

Страница 12: ...he red jumper on the rear of the detachable upper controller part is re moved An external auxiliary relay whose contact is arranged in series with both other outputs is connected to output 2 We reserv...

Отзывы: