Programming with TAPPS2 / M-Bus
41
By selecting suitable thresholds and output values, a fixed value can be specified for the bus
converter in the event of a measurement failure, to allow a function to continue operating in
emergency mode (fixed hysteresis: 10 or 1.0 °C).
The short circuit threshold must be defined below the lead break threshold.
Example
: Temperature
If the measurement is below 10 °C, 50 °C will
be issued; if it exceeds 100 °C, 70 °C will be
issued.
Once the parameter entries have been completed by pressing
OK
, the M-Bus input in
TAPPS2
will look
like this:
Input number
Address
Value number
Designation