Programming with TAPPS2 / M-Bus
37
M-Bus
The M-Bus is a master/slave system for reading data from energy and volume meters (electricity,
heat, water, gas).
The CAN-BC2 is designed for up to 4 M-Bus "unit loads". Up to 4 M-Bus meters, each with 1 unit load,
can therefore be connected. The bus converter (master) cyclically reads the values from the individual
devices. The interval time is adjustable.
As a master, this bus converter is therefore suitable for the parallel connection of up to four
M-Bus meters (slaves).
In total
, a maximum of 32 M-Bus values can be read per bus converter. There must only be one
master in the M-bus system.
This menu contains all the information and settings needed to set up an M-Bus network.
Settings
In the Device settings / M-Bus menu, the general
settings for the M-Bus and the addresses of the M-Bus
devices are defined.
Baud rate
The standard baud rate of the M-Bus devices is
2400 Bd. The factory setting does therefore not
usually need changing.
Interval time
The readout intervals can be adjusted from
10 seconds to 2 days. Longer intervals use up
less battery life in battery operated M-Bus
meters.
M-Bus device 1-4
For every connected M-Bus device, enabling
must be set to "
Yes
" and the
primary
slave
address
must be entered (between 0 and 250).
The primary slave address is set at the M-Bus
device in accordance with the manufacturer's
instructions.
The same slave address cannot be used twice
in the M-Bus network.