4.3.4 - REMOTE CONTROL

• See paragraph "accessories".

4.3.5 - MISCELLANEOUS

• Alarm transfer:

Potential-free changeover contact (2A - 250 VAC max.) available on the unit's terminal strip (terminals 5 (common), 6
and 7 of the printed circuit) for remote signaling. See schematic.

- In case of alarm:

- contact open between terminals 5 and 6,
- contact closed between terminals 5 and 7.

5 - OPERATION OF “ECH” ELECTRONIC CONTROL

• See the wiring diagrams at the back of the manual.

5.1 - DELIVERY STATE

• The control unit is supplied fitted in the machine and

factory pre-set.

• All the connections are made except those concerning the

available signals or the options.

5.2 - PRINCIPLE

• The microprocessor controls the operation of the machine

and of the associated alarms.
It continuously compares the water temperature
measured by the probe 

SD1

and the setpoint temperature

value entered via the keyboard.
Each operating request produced by the control unit is
indicated by the light (

6

) (see below).

This light flashes if a safety delay is in progress. It stays on when the compressor is operating.

• The 

control probe SD1

is located on the 

water inlet

in the factory.

• The controller is connected on a printed circuit board on which the inputs and outputs are connected. 

On this board: 

- 12 V supply transformer,
- the alarm report relay,
- the 230 V circuit fuse (4 A - 250 V - 5x20 - fast - breaking capacity: 1.5 kA).

5.3 - PRESENTATION

5.3.1

DISPLAY KEYBOARD

(1) 

Key for:

- Local On / Off control,
- access to parameters (in combination with button (

2

)),

- alarm clearance,
-  hour counter reset.

(2) 

Key for:

- access to parameters (in combination with button (

1

)).

(3)

LED display.

(4)

Cooling mode indicator (not used).

(5)

Heating mode indicator.

(6)

Compressor on indicator.

(7)

Defrosting indicator.

(8)

Anti-freeze on indicator.

(9)

Decimal point: if illuminated when the operating time is displayed, the value must be multiplied by 100.

DIGITAL INPUTS

12 VAC 

SUPPLY

TRANSFORMER

ACTUATORS

SD1     Water inlet

temperature probe

(for control)

SD2     Water

outlet temperature

probe

(for anti-

freeze protection)

SD3     Air heat

exchanger

temperature probe

(for defrosting and

pressure

adjustment)

SD4     Outside

temperature probe

ECH 210 BDT

CONTROLLER

AI1
AI2
AI3
AI4

Содержание PHTJ 14/19

Страница 1: ...aldamento Fluido refrigerante R 407 C Bomba de calor de alta temperatura con equipamiento hidr ulico s lo calefacci n Fluido refrigerante R 407 C Hochtemperatur W rmepumpe mit Hydraulikmodul Nur Heize...

Страница 2: ...18 R 407 C Fluid R 407 C is not a pure fluid but a blend composed of 23 R 32 25 R 125 52 R 134 A The compressors approved for operation with this fluid are filled beforehand with polyalcohol oil Contr...

Страница 3: ...on the installation check that its power supply is disconnected and locked out 1 4 USE OF EQUIPMENT This device is designed for heating buildings This appliance is not designed to be used by people i...

Страница 4: ...t not be directed towards surrounding windows vibrations and noise must not be transmitted to a nearby building avoid exposure to salty air or sulphuric gas the proximity of the extractor fan projecti...

Страница 5: ...devices not supplied See ratings in the table below Note The unit is designed to be connected to a power supply having a TT neutral regime neutral to ground or TN S regime to neutral as per NF C 15 10...

Страница 6: ...is light flashes if a safety delay is in progress It stays on when the compressor is operating The control probe SD1 is located on the water inlet in the factory The controller is connected on a print...

Страница 7: ...paragraph 5 4 If the light flashes it means that the compressor is starting required but that a safety delay is in progress This light stays on when the compressor has started To stop the unit open t...

Страница 8: ...s 1 and above are accessed Note 2 The normal display level 0 returns automatically after 5 minutes if no buttons are pressed Level 0 Normal display Level 1 Level 2 Level 3 Level 4 Temperature S1 Alarm...

Страница 9: ...ection in the menu Briefly and simultaneously press buttons 1 and 2 The message appears Enter the password using buttons 1 and 2 and validate it by simultaneously pressing buttons 1 and 2 It is now po...

Страница 10: ...ilation can restart after defrosting is completed to prevent excessive pressure build up For special climatic conditions the factory set time counter value of 30 minutes can be adjusted To do this mod...

Страница 11: ...or lamp flashes The stand by mode is indicated by the extinction of the heating mode indicator lamps Pre ventilation Generally speaking in order to condition the air heat exchanger the fan always star...

Страница 12: ...55 The functions and display are exactly the same as those on controller The only difference concerns the buttons and which are separated by the ON OFF and Mode buttons Reminder the parameters are acc...

Страница 13: ...ssure 2 bar That there are no leaks That the machine is stable That the power cables are well fixed to their connection terminals Terminals that are poorly tightened may cause overheating and malfunct...

Страница 14: ...e cleaning and protection of condensate tanks Treating odours and the disinfection of room surfaces and volumes also contributes to the cleanliness of the air breathed by users Carry out the following...

Страница 15: ...er use oxygen or dry air as the risk of fire or explosion is present Use dehydrated nitrogen or a nitrogen and refrigerant mix indicated on the manufacturer s plate For units equipped with pressure ga...

Страница 16: ...3 00 27 89 13 4 43 4 61 4 93 18 99 22 94 27 87 14 4 50 4 68 5 06 18 95 22 89 27 85 15 4 57 4 76 5 19 18 92 22 83 27 83 16 4 64 4 84 5 32 18 88 22 77 27 82 17 4 71 4 92 5 45 18 84 22 72 27 80 18 4 79 5...

Страница 17: ...11 4 43 18 99 22 64 25 60 14 4 12 4 18 4 56 18 95 22 59 25 58 15 4 19 4 26 4 69 18 92 22 53 25 56 16 4 26 4 34 4 82 18 88 22 47 25 55 17 4 33 4 42 4 95 18 84 22 42 25 53 18 4 41 4 50 5 08 18 80 22 36...

Страница 18: ...ink N Black R Red W White Colours of the wires M3 1 U N 45 1 3 2 4 KM3 M2 1 S R C M N B L1 L3 L1 B B 46 N C1 32 31 P3 56 55 J1 E2 BP 54 53 L L BP G R1 HP G HP 52 51 A1 SD 4 SD 3 SD 2 SD 1 U2 U1 N1 N2...

Страница 19: ...2 R1 W3 26 25 24 23 KM2 W2 W1 21 22 22 21 7 5 6 4 2 3 1 P1 P2 N XP PE XP U XP M M1 1 P W G M G 2 1 5 4 3 CX1 M11 1 P W G M G 2 1 5 4 3 CX2 C11 M B E1 U1 N1 N B U SD1 SD2 SD3 P4 P5 CN1 I CN1 II A3 SD4...

Страница 20: ...F GB D P I E...

Страница 21: ...F GB D P I E...

Страница 22: ...dificarli senza preaviso En el inter s de mejoras constantes nuestros productos pueden modificarse sin aviso pr vio Unsere Produkte werden laufend verbessert und k nnen ohne Vorank ndigung abge ndert...

Отзывы: