PCB switches / configuration & alarms:
• This board is fitted out with 2 “
SW1
” and “
SW2
” microswitches as well as “
JTP
” and “
JPC
” jumpers for the configuration:
-
SW1 - 1 Micro-switch
:
In “
ON
” position (factory setting), the circulating pump starts automatically if the outdoor temperature is below 0°C to
prevent the hydraulic circuit from freezing.
Caution
: In the “
oFF
” position, this function is deactivated.
-
SW1 - 2 Micro-switch
:
The “
ON
” position (factory setting) activates the “
FL
” alarm (heat pump water flow rate) at the system.
Caution: For heat pump with electric support heater applications, this micro-switch must be in the “ON”
position.
For heat pump in boiler back-up applications, the micro-switch must be placed in the “
OFF
” position.
-
SW2 - 1 micro-switch
:
The “
ON
” position activates the “Circulating pump speed variation” function.
The function is not available on this version.
The
SW2-1
micro-switch is left in “
OFF
” position (factory setting).
-
SW2 - 2 micro-switch
:
To select the circulating pump speed variation control algorithm.
SW2-2
in “
OFF
” position (factory setting) = “
PWM
” control.
SW2-2
in “
ON
” position = “
0/10V
” control.
The function is not available on this version.
-
JTP jumper
:
E2P
input selection.
Must be positioned on “
2-3
” (factory setting).
-
JPC jumper
:
Selection of type of circulating pump speed variation signal.
JPC
on “
1-2
” = “
PWM
” (factory setting).
JPC
on “
2-3
” = “
0/10V
”.
-Other plugs:
CHK
: not to be used
DISP
: short circuiting this plug allows operation of CWC2 board by a service remote control even if the power board A3 is not
connected. In this case, alarm E04 (see part 5), which indicates trouble in the communication between A2 and A3 board, does
not occur. This is signaled by power LED flashing.
• Alarms:
- "
AL
" LED:
-
Flashing
= Automatic reset heat pump alarm.
-
Stays on
= Manual reset heat pump alarm.
- "
W
" LED:
-
Off
= No water flow.
-
Stays on
= Water flow.
-
Slow flashing
= Water flow rate alarm.
(once a second)
-
Quick flashing
= Water outlet temperature too low alarm.
(twice a second)
-
Flickers
= TW2 water outlet temperature sensor fault.
-
“Power”
LED: illuminates when the power is on. Flashes if there is trouble with the EEPROM of the board (and also if short
circuiting “DISP” plug – see before).
Содержание PHIE 095
Страница 2: ...2...
Страница 10: ...10...
Страница 11: ...11...
Страница 12: ...12 1 3 2 THREE PHASES MODELS...
Страница 13: ...13...
Страница 14: ...14...
Страница 15: ...15...
Страница 17: ...17 1 4 PHYSICAL CHARACTERISTICS...
Страница 18: ...18...
Страница 19: ...19 1 5 DESCRIPTION 1 5 1 SINGLE PHASE MODELS...
Страница 20: ...20 1 5 2 THREE PHASES MODELS...
Страница 22: ...22...
Страница 23: ...23...
Страница 31: ...31 2 1 FRIGORIFIC HYDRAULIC DIAGRAMS 2 1 1 DIAGRAMS FOR MODELS 095 125 155 157 175 177 195 197...
Страница 32: ...32 2 1 2 DIAGRAMS FOR MODELS 257 307...
Страница 34: ...34 Connection diagram for 155 175 195 Connection diagram for 157 177 197 257 307 257 307...
Страница 38: ...38 Speed control input voltage Vsp Revolution pulse output Control 1 Vcc 2 PG 3 Vsp Power 1 Vm 2 not used 3 GND...
Страница 43: ...43 Failure matrix...
Страница 44: ...44 Failure handling...
Страница 49: ...49 3 1 ELECTRICAL DIAGRAMS 3 1 1 MODEL 095 2 HP 230V Single phase...
Страница 50: ...50 3 1 2 MODEL 125 3 HP 230V Single phase...
Страница 51: ...51 3 1 3 MODELS 155 175 4 5 HP 230V Single phase...
Страница 52: ...52 3 1 3 MODEL 195 6 HP 230V Single phase...
Страница 53: ...53 3 1 3 MODELS 157 177 197 4 5 6 HP 400V Three phases...
Страница 54: ...54 3 1 3 MODELS 257 307 8 10 HP 400V Three phases...
Страница 55: ...55 3 1 4 SYMBOLS...
Страница 56: ...56 3 2 MAIN COMPONENTS DESCRIPTION 3 2 1 CONTROL SYNOPTIC FOR HEAT PUMP ELECTRICAL SUPPORT HEATER APPLICATIONS...
Страница 57: ...57 3 2 2 CONTROL SYNOPTIC FOR HEAT PUMP IN BOILER BACK UP APPLICATIONS...
Страница 65: ...65 A3 board A086VH up side FOR UNIT 125 HIC temperature sensor plug Power LED EEPROM LED...
Страница 76: ...76 HIC board for units 257 307 Hybrid Integrated Circuit for inverter compressor Diode bridge HIC board...
Страница 77: ...77 A4 Supply and filter board for units 257 307...
Страница 85: ...85 4 9 AIR HEAT EXCHANGER DEFROST CONTROL Performed by A3 board 4 9 1 FLOWCHART OF DEFROST CONTROL 1 2 3...
Страница 100: ...100 5 1 5 ALARM DIAGNOSIS E31 F04 F06 F07 F08 F12 P22 P26 P29 For models 095 125 155 157 175 177 195 197...
Страница 101: ...101 For models 257 307...
Страница 104: ...104 For models 095 125 Replace A3 PCB...
Страница 105: ...105 For models 155 157 175 177 195 197...
Страница 106: ...106 For models 257 307...
Страница 107: ...107 For models 095 125...
Страница 108: ...108 For models 155 157 175 177 195 197 Check diode bridge...
Страница 109: ...109 For models 257 307 Check diode bridge...