Then adjust the red knob to the value
∆
P for the requested water flow rate Q as per the following formula:
∆
P = (Q / Qm)² x
∆
Pm
For example:
With unit type 155 – fitted with Stratos Para 25/1-7, the requested water flow Q is 1.75 m3/h (see tables below).
For an adjustment in the maximum position (7 m w),if the measured water pressure is
∆
Pm = 4.7 m, according circulating pump
curve, it relates to a flow rate of Qm = 2.3 m3/h.
Then, for a requested water flow of 1.75 m3/h, the adjustment will be :
∆
P
= (1.75 / 2.3)² x 4.7 =
2.1m w
Requested water flow (nominal): in m3/h
CONTENT
095 125 155 157 175 177 195 197 257 307
Pump reference
25/1-7 25/1-8
25/1-12
Water temp. 35°C
0.92 1.40
1.84
2.32
2.60
3.50 4.09
Water temp. 45°C
0.80 1.36
1.75
2.23
2.55
3.30 3.91
Water temp. 55°C
0.65 0.82
1.03
1.30
1.32
2.05 2.46
Wilo-Stratos Para 25/1-12
0 1 2 3
4
5
6
7 8 9 10 11
12
Water flow – m3/h
Differential pressure
∆
P (mW)
Unit :
307
Содержание PHIE 095
Страница 2: ...2...
Страница 10: ...10...
Страница 11: ...11...
Страница 12: ...12 1 3 2 THREE PHASES MODELS...
Страница 13: ...13...
Страница 14: ...14...
Страница 15: ...15...
Страница 17: ...17 1 4 PHYSICAL CHARACTERISTICS...
Страница 18: ...18...
Страница 19: ...19 1 5 DESCRIPTION 1 5 1 SINGLE PHASE MODELS...
Страница 20: ...20 1 5 2 THREE PHASES MODELS...
Страница 22: ...22...
Страница 23: ...23...
Страница 31: ...31 2 1 FRIGORIFIC HYDRAULIC DIAGRAMS 2 1 1 DIAGRAMS FOR MODELS 095 125 155 157 175 177 195 197...
Страница 32: ...32 2 1 2 DIAGRAMS FOR MODELS 257 307...
Страница 34: ...34 Connection diagram for 155 175 195 Connection diagram for 157 177 197 257 307 257 307...
Страница 38: ...38 Speed control input voltage Vsp Revolution pulse output Control 1 Vcc 2 PG 3 Vsp Power 1 Vm 2 not used 3 GND...
Страница 43: ...43 Failure matrix...
Страница 44: ...44 Failure handling...
Страница 49: ...49 3 1 ELECTRICAL DIAGRAMS 3 1 1 MODEL 095 2 HP 230V Single phase...
Страница 50: ...50 3 1 2 MODEL 125 3 HP 230V Single phase...
Страница 51: ...51 3 1 3 MODELS 155 175 4 5 HP 230V Single phase...
Страница 52: ...52 3 1 3 MODEL 195 6 HP 230V Single phase...
Страница 53: ...53 3 1 3 MODELS 157 177 197 4 5 6 HP 400V Three phases...
Страница 54: ...54 3 1 3 MODELS 257 307 8 10 HP 400V Three phases...
Страница 55: ...55 3 1 4 SYMBOLS...
Страница 56: ...56 3 2 MAIN COMPONENTS DESCRIPTION 3 2 1 CONTROL SYNOPTIC FOR HEAT PUMP ELECTRICAL SUPPORT HEATER APPLICATIONS...
Страница 57: ...57 3 2 2 CONTROL SYNOPTIC FOR HEAT PUMP IN BOILER BACK UP APPLICATIONS...
Страница 65: ...65 A3 board A086VH up side FOR UNIT 125 HIC temperature sensor plug Power LED EEPROM LED...
Страница 76: ...76 HIC board for units 257 307 Hybrid Integrated Circuit for inverter compressor Diode bridge HIC board...
Страница 77: ...77 A4 Supply and filter board for units 257 307...
Страница 85: ...85 4 9 AIR HEAT EXCHANGER DEFROST CONTROL Performed by A3 board 4 9 1 FLOWCHART OF DEFROST CONTROL 1 2 3...
Страница 100: ...100 5 1 5 ALARM DIAGNOSIS E31 F04 F06 F07 F08 F12 P22 P26 P29 For models 095 125 155 157 175 177 195 197...
Страница 101: ...101 For models 257 307...
Страница 104: ...104 For models 095 125 Replace A3 PCB...
Страница 105: ...105 For models 155 157 175 177 195 197...
Страница 106: ...106 For models 257 307...
Страница 107: ...107 For models 095 125...
Страница 108: ...108 For models 155 157 175 177 195 197 Check diode bridge...
Страница 109: ...109 For models 257 307 Check diode bridge...