72
UNITS 157 / 177 / 197 – COMMENTS
•
S002 rotary switch
(10 positions, black)
/ S003 DIP switches
(2P, blue)
:
Address for split air to air units – not used for the application.
The factory setting below must not be changed :
•
S001 AUTo ADDress push button switch
(black)
:
Normally, the addressing sequence between refrigerant circuit power board A3 and control board A2 takes place when power is
initially turned on at the factory.
In case of board replacement or problem of communication on the field, it can be necessary to launch again an addressing
sequence. For that, press once the switch.
During automatic address setting, LEDs 1 & 2 are blinking alternatively (pressing again this switch stops automatic address
setting).
•
S005 Pump down push button switch
(red)
:
Used for split air to air units for refrigerant recovery sequence – not used for the application.
•
CN032 RC-P Service remocon connection plug
(5P, red)
:
See PART 6
•
JP007
jumper:
Not used.
•
CN036 Test plug
(2P, red)
:
Used for PCB inspection in factory.
•
CN031 MODE plug
(2P, white)
:
Not used.
•
CN012 ROM plug
(4P, white)
:
Used for PCB software loading in factory with “PAC checker” interface.
•
CN026 EXCT plug
(3P, red)
:
Designed for capacity control – not used.
•
CN028 SILENT (or QUIET) MODE plug:
Software version:
Unit Version
Date
157 (4HP)
V150
Nov. 2011
177 (5HP)
197 (6HP)
Содержание PHIE 095
Страница 2: ...2...
Страница 10: ...10...
Страница 11: ...11...
Страница 12: ...12 1 3 2 THREE PHASES MODELS...
Страница 13: ...13...
Страница 14: ...14...
Страница 15: ...15...
Страница 17: ...17 1 4 PHYSICAL CHARACTERISTICS...
Страница 18: ...18...
Страница 19: ...19 1 5 DESCRIPTION 1 5 1 SINGLE PHASE MODELS...
Страница 20: ...20 1 5 2 THREE PHASES MODELS...
Страница 22: ...22...
Страница 23: ...23...
Страница 31: ...31 2 1 FRIGORIFIC HYDRAULIC DIAGRAMS 2 1 1 DIAGRAMS FOR MODELS 095 125 155 157 175 177 195 197...
Страница 32: ...32 2 1 2 DIAGRAMS FOR MODELS 257 307...
Страница 34: ...34 Connection diagram for 155 175 195 Connection diagram for 157 177 197 257 307 257 307...
Страница 38: ...38 Speed control input voltage Vsp Revolution pulse output Control 1 Vcc 2 PG 3 Vsp Power 1 Vm 2 not used 3 GND...
Страница 43: ...43 Failure matrix...
Страница 44: ...44 Failure handling...
Страница 49: ...49 3 1 ELECTRICAL DIAGRAMS 3 1 1 MODEL 095 2 HP 230V Single phase...
Страница 50: ...50 3 1 2 MODEL 125 3 HP 230V Single phase...
Страница 51: ...51 3 1 3 MODELS 155 175 4 5 HP 230V Single phase...
Страница 52: ...52 3 1 3 MODEL 195 6 HP 230V Single phase...
Страница 53: ...53 3 1 3 MODELS 157 177 197 4 5 6 HP 400V Three phases...
Страница 54: ...54 3 1 3 MODELS 257 307 8 10 HP 400V Three phases...
Страница 55: ...55 3 1 4 SYMBOLS...
Страница 56: ...56 3 2 MAIN COMPONENTS DESCRIPTION 3 2 1 CONTROL SYNOPTIC FOR HEAT PUMP ELECTRICAL SUPPORT HEATER APPLICATIONS...
Страница 57: ...57 3 2 2 CONTROL SYNOPTIC FOR HEAT PUMP IN BOILER BACK UP APPLICATIONS...
Страница 65: ...65 A3 board A086VH up side FOR UNIT 125 HIC temperature sensor plug Power LED EEPROM LED...
Страница 76: ...76 HIC board for units 257 307 Hybrid Integrated Circuit for inverter compressor Diode bridge HIC board...
Страница 77: ...77 A4 Supply and filter board for units 257 307...
Страница 85: ...85 4 9 AIR HEAT EXCHANGER DEFROST CONTROL Performed by A3 board 4 9 1 FLOWCHART OF DEFROST CONTROL 1 2 3...
Страница 100: ...100 5 1 5 ALARM DIAGNOSIS E31 F04 F06 F07 F08 F12 P22 P26 P29 For models 095 125 155 157 175 177 195 197...
Страница 101: ...101 For models 257 307...
Страница 104: ...104 For models 095 125 Replace A3 PCB...
Страница 105: ...105 For models 155 157 175 177 195 197...
Страница 106: ...106 For models 257 307...
Страница 107: ...107 For models 095 125...
Страница 108: ...108 For models 155 157 175 177 195 197 Check diode bridge...
Страница 109: ...109 For models 257 307 Check diode bridge...