2

IMPORTANT!
Please read before installation

This air conditioning system meets strict safety and operating
standards.
For the installer or service person, it is important  to install or
service the system so that it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical  codes.
• Pay close attention to all warning and caution notices given in

this manual.

•The unit must be supplied with a dedicated electrical line.

This symbol refers to a hazard or unsafe practice which can result
in severe personal injury or death.

This symbol refers to a hazard or unsafe practice which can result
in personal injury or product or property damage.

If necessary, get help

These instructions are all you need for most installation sites and
maintenance conditions.
If you require help for a special problem, contact our sale/service
outlet or your certified dealer for additional instructions.

In case of improper installation

The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow the
instructions in this document.

SPECIAL PRECAUTIONS

• During installation, connect before the refrigerant system and

then the wiring one; proceed in the reverse orden when removing
the units.

When wiring

ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIANS SHOULD ATTEMPT
TO WIRE THIS SYSTEM.

• Do not supply power to the unit until all wiring and tubing are

completed or reconnected and checked, to ensure the grounding.

• Highly dangerous electrical voltages are used in this system.

Carefully refer to the wiring diagram and these instructions when
wiring.
Improper connections and inadequate grounding can cause

accidental injury and death

.

Ground the unit 

following local electrical codes.

• The Yellow/Green wire cannot be used for any connection

different from the ground connection.

• Connect all wiring tightly. Loose wiring may cause overheating

at connection points and a possible fire hazard.

• Do not allow wiring to touch the refrigerant tubing, compressor,

or any moving parts of the fan.

• Do not use multi-core cable when wiring the power supply and

control lines. Use separate cables for each type of line.

When transporting

Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to
reduce strain on your back. Sharp edges or thin aluminium fins on
the air conditioner can cut your fingers.

When installing...
... In a ceiling or wall

Make sure the ceiling/wall is strong enough to hold the unit-weight.
It may be necessary to build a strong wooden or metal frame to
provide added support.

... In a room

Properly insulate any tubing run inside a room to prevent
"sweating", which can cause dripping and water damage to walls
and floors.

... In moist or uneven locations

Use a raised concrete base to provide a solid level foundation for
the outdoor unit.
This prevents damage and abnormal vibrations.

... In area with strong winds

Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.

... In a snowy area (for heat pump-type systems)

Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.

When connecting refrigerant tubing

• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare

and union tubes before connecting them;  screw by hand and
then tighten the nut with a torque wrench for a leak-free
connection.

• Check carefully for leaks before starting the test run.

NOTE:

Depending on the system type, liquid and gas lines may be either
narrow or wide. Therefore, to avoid confusion, the refrigerant
tubing for your particular model is specified as narrow tube for
liquid, wide tube for gas.

When servicing

• Turn the power OFF at the main power board  before opening

the unit to check or repair electrical parts and wiring.

• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no

metal scraps or bits of wiring have been left inside the unit being
serviced.

• Ventilate the room during the installation or testng the refrigeration

system; make sure that, after the installation, no gas leaks are
present, because this could produce toxic gas and dangerous
if in contact with flames or heat-sources.

WARNING

CAUTION

WARNING

EG

Содержание GRF96R5IA Series

Страница 1: ...er s installation and or operating instructions Power Supply 220 240 V 50 Hz OPERATING LIMITS Cooling Maximum conditions Outdoor temperature 46 C D B Room temperature 32 C D B 23 C W B Cooling Minimum...

Страница 2: ...ring to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line When...

Страница 3: ...e as well as unrestricted air flow around the unit Installation site selection Outdoor unit AVOID Heat sources exhaust fans Direct sunlight Damp humid or uneven locations To make holes in areas where...

Страница 4: ......

Страница 5: ...CEE e 93 68 CEE Compatibilit Elettromagnetica n 89 336 CEE 92 31 CEE e 93 68 CEE Questa dichiarazione sar nulla nel caso di impiego diverso da quello dichiarato dal Fabbricante e o di mancata osserva...

Страница 6: ...ontatto con i tubi refrigeranti il compressore o le parti mobili del ventilatore Nel collegare l alimentazione e le linee di controllo non usare cavi a pi conduttori Usare cavi separati per ciascun ti...

Страница 7: ...e da espulsioni di aria calda L esposizione diretta al sole Zone umide o soggette ad allagamenti e piano di appoggio non livellato Di eseguire fori nelle zone dove si trovano parti elettriche o impian...

Страница 8: ......

Страница 9: ...ibilit Electromagn tique n 89 336 CEE 92 31 CEE et 93 68 CEE Cette d claration sera nulle en cas d une utilisation diff rente de celle d clar e par le Constructeur et ou de la non observation m me si...

Страница 10: ...endie Il ne faut en aucun cas laisser les c bles toucher la tuyauterie du r frig rant le compresseur ou toute pi ce mobile N utilisez pas de c ble multiconducteur pour le c blage des lignes d alimenta...

Страница 11: ...stallation Appareil ext rieur EVITEZ Les sources de chaleur les ventilateurs d evacuation etc La lumi re directe du soleil Les endroits mouill s humides ou de surface irr guli res Faire trous o il y a...

Страница 12: ......

Страница 13: ...ntspricht Niederspannungsrichtilinie 73 23 EWG und 93 68 EWG Elektromagnetische Vertr glichkeit 89 336 EWG 92 31 EWG und 93 68 EWG Bei falschem Einsatz des Ger tes und oder Nichtbeachtung auch nur von...

Страница 14: ...hlmittelrohre den Kompressor oder die beweglichen Teile des Ventilators ber hrt Verwenden Sie keine Mehraderkabel f r die Verdrahtung der Stromversorgung und Steuerleitungen Benutzen Sie separate Kabe...

Страница 15: ...e Direkte Sonneneinstrahlung Feuchte luftfeuchte oder unhebene Stellen L cher im Bereich mit elektrischen Kabeln und Rohrkabeln zu bohren WAS SIE TUN SOLLTEN W hlen Sie eine Stelle an der es so k hl w...

Страница 16: ......

Страница 17: ...3 23 CEE y 93 68 CEE Compatibilidad Electromagnetica n 89 336 CEE 92 31 CEE y 93 68 CEE Esta declaraci n no tendr efecto en s lo caso de que se haga un uso diferente al declarado por el Fabricante y o...

Страница 18: ...n contacte con el tubo de refrigerante compresor o parte m viles del ventilador No use cable coaxial para cablear las l neas de potencia y las de control Use cables separados para cada una de las l n...

Страница 19: ...l Zonas h medas o con riesgo de inundaciones lugares de apoyo no nivelados Hacer orificios en las zonas donde hay partes el ctricas o instalaciones ES PREFERIBLE Elegir zonas a la sombra ligeramente a...

Страница 20: ...r la position la plus indiqu e pour l installation de l unit V rifier la possibilit d vacuer les condensats vers l ext rieur en assurant une bonne pente Eine passende Aufstellungsstelle w hlen von der...

Страница 21: ...ttro viti del pannello frontale Enlever le filtre air et ensuite les quatre vis du panneau frontal Den Luftfilter und die vier Schrauben des Gitters entfernen Quitar el filtro del aire y los cuatro to...

Страница 22: ...en bas Die Verbindungsleitungen von au en strecken Die Anschl sse auf der Inneneinheit sind unten auf der rechte Seite Introducir los tubos de conexi n desde fuera Las dem s conexiones de la unidad i...

Страница 23: ...ra y atornillar hasta el fondo Colgar la unidad en la abrazadera I EG F D E M Remove the electrical box cover to operate on the terminal strip Rimuovere il coperchio scatola componenti elettrici per a...

Страница 24: ...ziehen Sie dann die Schrauben an Colocar el cable el ctrico y concitarlo al tablero de bornes v ase esquema de conexiones Bloquear el cable a la abrazadera de la brida Controlar que los bornes de los...

Страница 25: ...Use if necessary the accessories supplied Versione pompa di calore Utilizzare se necessario il materiale a corredo Version r versible Si n cessaire employer les accessoires livr s W rmepumpe Ausf hru...

Страница 26: ...l tubo de cobre hacia abajo para evitar que puedan entrar posibles residuos min 8 mm min 8 mm Insulation I EG F D E I EG F D E G Insert flare nuts removed from the units then make a flare at the end o...

Страница 27: ...la prova di tenuta Isoler soigneusement les tubes en laissant libres les jonctions pour l essai d etanch it Die R hre gut isolieren die Verbindungen aber f r die Dichtheits Pr fung frei lassen Aislar...

Страница 28: ...tness of all joints using liquid soap Con la pompa del vuoto in funzione chiudere il rubinetto del gruppo manometrico bassa pressione Quindi fermare la pompa del vuoto Con una chiave esagonale aprire...

Страница 29: ...halten Die Ventilverschl sse und den Stutzen wieder anbringen Mit Drehmoment bei 200 Kg cm anziehen Abrir completamente las v lvulas de servicio sentido contrario a las agujas del reloj A este punto d...

Страница 30: ...ungst ck sollte ber einen Druckstift verf gen La v lvula de servicio de la unidad exterior donde se realiza la conexi n para vaciar el sistema Ilenar con refrigerante y medir la presi n de frabajo es...

Страница 31: ...disinserzione dalla rete interruttore generale deve essere del tipo adatto con distanza minima di apertura dei contatti di 3 mm Le dispositif omnipolaire de protection et de sectionnement de la ligne...

Страница 32: ...t de fixation du c ble et le bornier soit telle que les conducteurs actifs Phase Neutre se tendent avant le conducteur de mise la terre pour permettre aux conducteurs actifs Phase Neutre de se d branc...

Страница 33: ...commande aux endroits suivants En plein soleil Derri re un rideau ou tout autre endroit o elle serait cach e A plus de 8 m tres du climatiseur Pr s de la sortie d air du climatiseur Aux endroits exce...

Страница 34: ...Placer la t l commande dans la position d sir e V rifier que la commande distance peut tre utilis e dans cette position Fixer le support au mur avec deux vis et accrocher la telecommande POSITION AN E...

Страница 35: ...kmesser abblasen Das Hochdruck Ventil zudrehen Conectar el grupo manom trico a la v lvula de baja presi n abrirla parcialmente 1 4 vuelta Purgar el aire del man metro Cerrar completamente la v lvula d...

Страница 36: ...ut prior notice Per garantire un costante miglioramento dei nostri prodotti ci riserviamo di modificarli senza preavviso Par souci d am lioration constante nos produits peuvent tre modifi s sans pr av...

Отзывы: