5-21 MAINTENANCE
5-21.1 Changing the Address of the Air Conditioner
In case of more than one air conditioner operating in the same room, it may be necessary to assign
an address to each unit in order to avoid operation conflicts. Address is set acting on the dip-switches
located on the indoor PCB and on the remote controller.
The PCB settings must match the corresponding ones on the wireless remote controller.
How to change address of the air conditioner
Set the PCB to the address desidered
UNIT
ADDRESS
1
2
1
off
off
2
off
on
3
on
off
4
on
on
As default, switches 1 and 2 are in 'off' status (PCB factory state).
How to change address on Remote Control Unit
Dip switch is located on the battery compartment.
As default switches 1 and 2 are in 'off' status while 3 and 4 are in 'on' status
(remote controller factory state).
SETTINGS
26
Содержание MPAF129R5IAA
Страница 9: ...2 DIMENSIONAL DATA MRAF99R5IAA MRAF129R5IAA 9...
Страница 10: ...2 DIMENSIONAL DATA MPAF99R5IAA MPAF129R5IAA 10...
Страница 13: ...4 ELECTRICAL DATA 4 1 Electric Wiring Diagrams MRAF99R5IAA MRAF129R5IAA MPAF99R5IAA MPAF129R5IAA 13...
Страница 28: ...6 3 SYSTEM DOES NOT RUN 28...
Страница 29: ...6 3 SYSTEM DOES NOT RUN 29...
Страница 30: ...6 4 OUTDOOR UNIT DOES NOT RUN AND NO FAULT IS DISPLAIED 6 5 ONLY OUTDOOR UNIT IS OFF 30...
Страница 31: ...6 6 OUTDOOR UNIT FAULT SIGNALING 31...
Страница 33: ...3 CHECK MODE BUTTON OPERATION ON THE UNIT Push the mode button The unit does not run PCB assy is defective 33...
Страница 34: ...6 8 NOISY PROBLEM 34...
Страница 35: ...7 CHECKING ELETRICAL COMPONENTS 7 1 35...
Страница 36: ...7 2 36...