5.FUNCTION
5-1 System operation control
The inputs to the systems come from indoor and outdoor sensors. The outdoor unit is the system
MASTER while the indoor one is the SLAVE.
Communication between units is made with a 2 poles RS485 bus
The indoor units receives the user input (fan speed, flap position etc) through remote controller
which sends signal every time a button is pressed and in any case, automatically, every 5 minutes.
5.1.1 control specification
During operation compressor speed can be subjected to change due to thermal load variations
or protection activations but in any case:
•
The minimum time interval between an OFF and a ON operation is not lower than 3 minutes
•
The minimum operating time is not lower than 3 minutes
•
The acceleration/deceleration rate is fixed at 50rpm /sec
•
During the start-up compressor speed increases according to a defined rule which is
independent from the thermal load calculation.
14
Содержание MPAF129R5IAA
Страница 9: ...2 DIMENSIONAL DATA MRAF99R5IAA MRAF129R5IAA 9...
Страница 10: ...2 DIMENSIONAL DATA MPAF99R5IAA MPAF129R5IAA 10...
Страница 13: ...4 ELECTRICAL DATA 4 1 Electric Wiring Diagrams MRAF99R5IAA MRAF129R5IAA MPAF99R5IAA MPAF129R5IAA 13...
Страница 28: ...6 3 SYSTEM DOES NOT RUN 28...
Страница 29: ...6 3 SYSTEM DOES NOT RUN 29...
Страница 30: ...6 4 OUTDOOR UNIT DOES NOT RUN AND NO FAULT IS DISPLAIED 6 5 ONLY OUTDOOR UNIT IS OFF 30...
Страница 31: ...6 6 OUTDOOR UNIT FAULT SIGNALING 31...
Страница 33: ...3 CHECK MODE BUTTON OPERATION ON THE UNIT Push the mode button The unit does not run PCB assy is defective 33...
Страница 34: ...6 8 NOISY PROBLEM 34...
Страница 35: ...7 CHECKING ELETRICAL COMPONENTS 7 1 35...
Страница 36: ...7 2 36...