5-10 Protection operations on outdoor unit
5-10.1 Overheating
During cooling operation as soon as the outdoor coil temperature (OCT) increases, compressor speed
is reduced in order to avoid heat exchanger overheating. System stops compressor operation when OCT
reaches 60 °C
5-10.2 Compressor discharge temperature
During operation, as soon as the discharge temperature increases, (CDT) compressor speed is reduced
in order to avoid overheating of the motor. Compressor is stopped when CDT reaches 105°C
5-10.3 Compressor power-module overheating
The module temperature, detected by a built-in thermistor, is always monitored by the control system and kept
operating in a safe area. If temperature exceeds 100°C, operation is automatically stopped.
5-10.4 Outdoor fan power-module overheating
The module temperature, detected by a built-in thermistor, is always monitored by the control system and kept
operating in a safe area. If temperature exceeds 100°C, operation is automatically stopped.
5-10.5 Compressor power-module overcurrent
In case of current driven to each motor phase greater than 10 A operation is automatically stopped
5-10.6 Outdoor fan power-module overcurrent
In case of current driven to each motor phase greater than 400mA operation is automatically stopped
19
Содержание MPAF129R5IAA
Страница 9: ...2 DIMENSIONAL DATA MRAF99R5IAA MRAF129R5IAA 9...
Страница 10: ...2 DIMENSIONAL DATA MPAF99R5IAA MPAF129R5IAA 10...
Страница 13: ...4 ELECTRICAL DATA 4 1 Electric Wiring Diagrams MRAF99R5IAA MRAF129R5IAA MPAF99R5IAA MPAF129R5IAA 13...
Страница 28: ...6 3 SYSTEM DOES NOT RUN 28...
Страница 29: ...6 3 SYSTEM DOES NOT RUN 29...
Страница 30: ...6 4 OUTDOOR UNIT DOES NOT RUN AND NO FAULT IS DISPLAIED 6 5 ONLY OUTDOOR UNIT IS OFF 30...
Страница 31: ...6 6 OUTDOOR UNIT FAULT SIGNALING 31...
Страница 33: ...3 CHECK MODE BUTTON OPERATION ON THE UNIT Push the mode button The unit does not run PCB assy is defective 33...
Страница 34: ...6 8 NOISY PROBLEM 34...
Страница 35: ...7 CHECKING ELETRICAL COMPONENTS 7 1 35...
Страница 36: ...7 2 36...