TECH ST-402N PWM Скачать руководство пользователя страница 18

ST-402N User's Manual v 1.0.3

 

18

 -

 

following modes:

 

 

a) 

Priority of Tank 1

 – first, tank 1 is heated (only pump 1 operates), after the set temperature 

is reached, pump 2 is activated and reheats tank 2.

 

 

b) 

Parallel Operation

 – the pumps operate independently of one another, each  within its own 

range (according to the settings) and both tanks are heated at the same time.

 

 

V.b.12) 

 

Tank Reheating Priority 

Option active only in the case of setting the installation scheme number: 9.

 

 

After the user marks this function, the tank's set temperature is treated as a priority – the valve 

does not switch to the circulation with the heat receiver until the tank's set temperature is reached. 
The function of oscillation loading is not taken into account in this situation. 

 

 

V.c) 

 

Solar Collector

 

This menu allows the user to adjust all parameters related to the Solar Collector.

 

 

V.c.1) Overheat Temperature 

This is the Solar Collector's acceptable alarm temperature at which the pump is forced to activate in 
order to cool down the solar panels.  The discharge of warm water will take place regardless of the 
tank's set temperature. The pump will operate until its temperature drops below the alarm temperature 
by the 

Alarm Hysteresis Value

 (

Service Settings > Solar Collector > Alarm Hysteresis

) or until the tank 

reaches  the  maximum  acceptable  temperature  (

Service  Settings  >  Accumulation  Tank  >  Maximum 

Temperature

)

 

 

V.c.2) Minimum Reheating Temperature 

This is the collector's threshold temperature. If the temperature within the collector is higher and is 
dropping after reaching the minimum reheating temperature, the pump is deactivated. On the other 
hand, when the temperature on the collector is below this limit and is increasing - the pump is activated 
after  reaching  the  minimum  reheating  temperature  plus  hysteresis  -  3°C.  The  threshold  reheating 
temperature is not active in the emergency mode, manual operation or collector defrosting.

 

 

V.c.3) Anti-Freeze Temperature 

Due  to  the  different  freezing  temperatures  of  the  liquid  in  the  solar  installation,  the 

Anti-Freeze 

Temperature

  was  introduced.  This  parameter  determines  the  minimum  safe  temperature  when  the 

glycol liquid does not freeze (temperature measured on the collector). In the case of a significant drop 
in the  collector's  temperature  (to  the  value  of  this  parameter),  the  pump  is  activated  and  operates 
continuously until the collector is heated to a safe temperature. The settings range of this coefficient is 
within -50: +10°C.

 

 

V.c.4) Alarm Hysteresis 

Using this function, the user declares the value of the collector's alarm hysteresis. If the tank reaches 
the alarm temperature (

Overheat Temperature

) and the pump is activated, it will deactivate again when 

the collector's temperature drops below 

the maximum temperature

 by the value of this hysteresis.  

 

 

V.c.5) Defrosting Time 

Using this function, the user determines for how long the pump is activated after the activation of the 
function 

Collector Defrosting

.

 

 

V.c.6) Collector Delta 

Option active only in the case of setting the installation scheme number: 4.

 

 

Only one heating circulation is always active in this system. The switching valve is to switch the 

circulation to the collector that currently has temperature higher at least by the value of collector delta 
(this is the difference in temperatures of both Collectors).

 

 
 
 
 

Содержание ST-402N PWM

Страница 1: ...Tech 1 User s manual ST 402N PWM...

Страница 2: ...ure the regulator is disconnected from the mains before perform ing any activities involving the power supply plugging cables installing the device etc The device should be installed by a qualified el...

Страница 3: ...l signal relay is necessary to control the heater III Principle Of operation Description of the Control Panel of a Sample System Opis panelu steruj cego przyk adowego uk adu The regulator is controlle...

Страница 4: ...Active Operation Mode The Symbol of Active Additional Device Peripherals Automatic Operation Mode Circulation Pump Collector Defrosting Mode Firing up the Pellet Boiler voltage free signal Holiday Mo...

Страница 5: ...VICE MENU Pumps Solar Pump Deactivation Delta in this case the pump will be activated again when the temperature on the collector increases above the tank s temperature by the Solar Pump Activation De...

Страница 6: ...of activating the disinfection the temperature of disinfection needs to be reached in no longer than the time defined by the user SERVICE MENU Peripherals Heater Anti Legionella Maximum Anti Legionel...

Страница 7: ...ction of property IV h Statistics The parameters in this submenu allow the user to monitor the current conditions of the controller s operation IV h 1 Gain This parameter allows the user to monitor th...

Страница 8: ...essing the Menu button In order to return to the display s main view exit the service menu the user should use the Exit button by pressing it several times or waiting for approx 30 seconds the device...

Страница 9: ...Time Anti Freeze Temperature Collector Delta Heat receiver Receiver Maximum Temperature Receiver Activation Temperature Heat Receiver Hysteresis Pumps Regulated Revolutions Collector Maximum Temperat...

Страница 10: ...al peripherals Installation Sensors The Collector s sensor The Accumulation Tank s sensor V a 2 Scheme 2 17 One Tank Order Installation 2 17 Operates The Collector Pump The Switching Valve top bottom...

Страница 11: ...not possible to cool down using the DHW pump Installation Sensors The collector s sensor The two sensors of the Accumulation Tank top and bottom The boiler temperature sensor Additional Parameters to...

Страница 12: ...k s pump Tank 1 with top and bottom circulation Tank 2 One direction of the collectors location Additional peripherals not possible to cool down using the DHW pump Installation Sensors The collector s...

Страница 13: ...irculation If the tank s temperature is too low the valve switches to the furnace Additional Parameters to be Adjusted additional submenu in the service menu Installation s Options reheating deactivat...

Страница 14: ...ta of pump 2 Activation delta of pump 2 V a 13 Scheme 13 17 Two Collectors Pump Valve Tank and Additional Tank Connected in Series Installation 13 17 Operates The Collector Pump The Switching Valve Th...

Страница 15: ...ce the submenu Peripherals is hidden in the controller s service menu The switching valve operating the additional receiver is connected instead of the peripherals Additional parameters to be adjusted...

Страница 16: ...eiver receiver maximum temperature receiver activation temperature heat receiver hysteresis V b Accumulation Tank This menu allows the user to adjust all parameters related to the tank heat container...

Страница 17: ...e of scheme 6 the setting relates to valve control when cooling the Collector down in the Summer Mode or Alarm Mode as well as when defrosting The valve hysteresis determines the difference in tempera...

Страница 18: ...minimum reheating temperature the pump is deactivated On the other hand when the temperature on the collector is below this limit and is increasing the pump is activated after reaching the minimum reh...

Страница 19: ...r declares the value of the collector s maximum alarm temperature when the pump may be damaged This temperature should be adjusted according to the collector s technical data Due to phenomenon of glyc...

Страница 20: ...hes to circulation 2 and the pump operates in operation cycles parameter Maximum Heating Time of Tank 2 as well as pause Parameter Oscillation Pause Time When the collector reaches a high enough tempe...

Страница 21: ...n NO deactivate Additional available devices and examples of connections supporting all available installation schemes are presented below In the case of using schemes 12 or 14 it is not possible to c...

Страница 22: ...rthermore a tank sensor is needed for it to operate in the case of two sensors in the tank the top sensor If the criteria referred to above are met the peripheral will be activated contact closing whe...

Страница 23: ...ve in the case of setting the installation scheme number 5 and 11 This parameter is used to adjust the threshold tank temperature at which the valve will switch to reheating the boiler s return V h 5...

Страница 24: ...free operation the regulator has been equipped with a range of safeguards 1 Installation Sensor Protection If one of the sensors is damaged an acoustic signal is activated and the following symbol wil...

Страница 25: ...its cables The user should also check if the controller is properly mounted and clean it if dusty or dirty Technical Data of ST 402N Controller Power Supply Voltage 230V 50Hz 10 Temperature Adjustment...

Страница 26: ...not replace the design of the CH installation It is aimed at demonstrating the possibility for expanding the controller The presented scheme of the heating installation does not contain cut off and pr...

Страница 27: ...t 7 IV h 3 Power Supply Failures 7 IV i Backlight 7 IV j Display Contrast 7 IV k Language 7 IV l Information 7 IV m Factory Settings 8 V Service Menu 8 V a Installation Scheme 10 V a 1 Scheme 1 17 Bas...

Страница 28: ...7 V b 10 Hysteresis of Tank 2 17 V b 11 Operation Algorithm 17 V b 12 Tank Reheating Priority 18 V c Solar Collector 18 V c 1 Overheat Temperature 18 V c 2 Minimum Reheating Temperature 18 V c 3 Anti...

Страница 29: ...Type of Agent 22 V g 3 Glycol Solution 22 V g 4 Calibration 22 V h Installation Options 23 V h 1 Reheating Activation Delta 23 V h 2 From Hour to Hour 23 V h 3 Energy Release 23 V h 4 Energy Release...

Страница 30: ...Voltage Directive LVD 2006 95 EC the Act dated April 13th 2007 on electromagnetic compatibility Journal of Laws 07 82 556 implementing the provisions of Directive EMC 2004 108 EC as well as the Regul...

Страница 31: ...y number assigned by the Main Inspector of Environmental Protection The symbol of a crossed out rubbish bin on a product means that the product must not be thrown out to ordinary waste bins By segrega...

Страница 32: ...ST 402N User s Manual v 1 0 3 32...

Отзывы: