In the examples  given, the jumper is shown as a black filling. 

In the four examples we can see how to program the frequency which corresponds to the maximum 
output. 

When changing the maximum frequency, this should be done with the instrument disconnected from 
the mains supply. The instrument reads the switch data only when it is switched on. 

4. CONFIGURATION

It is not normally necessary for the user to have to change the basic configuration of the instrument, 
given that the CI-420 is supplied according to the clients specifications. 

In the example given the instrument is configured for a COVOL input and 4-20 mA output. 

The JP1 and JP2 jumpers are used to configure the type of input and should not be moved 

The jumpers JP3, JP4, JP5 & JP6 are used to configure the type of output. 

             Beginning           Full                     JP3                     JP4                      JP5                   JP6 
             of Scale              Scale                                          1           2                                                             

1.           0 mA                   20 mA                   X                               X                                  
2.           4 mA                   20 mA                                        X                               
3.           0 V                        5 V                        X                               X                     X                        X 
4.           0 V                       10 V                       X                               X                     X 
5.           1 V                        5 V                                             X                                X                        X           
6.

2 V                       10 V                                            X                                X          

Jumpers JP5 and JP6 are used only for voltage outputs, and have only one position. 

Jumper JP3 fixes the full scale range. 

Jumper JP4 is used to determine the beginning of the scale and has two positions, "1" towards the  
top of the PCB and "2" towards the bottom of the PCB. 

The jumpers should be placed in the position marked with "X". 

The potentiometer

 POT1

 can be used for fine adjustment of the full scale reading.

Содержание CI-420

Страница 1: ...t input 3 2 3 Analog output connection 4 2 4 Pulse output connection 4 3 SETTING UP 4 4 CONFIGURATION 5 5 TECHNICAL CHARACTERISTICS 6 5 1 Working conditions 6 5 2 Mains supply 6 5 3 Analog output 6 5...

Страница 2: ...voltage outputs to obtain the following voltage outputs Beginning of Scale Full Scale 0 V 5 V 0 V 10 V 1 V 5 V 2 V 10 V The value of fr the full scale frequency is selected by means of four BCD switc...

Страница 3: ...2 2 1 Pick up Input For the input from turbine type flowmeters which use magnetic inductive pick ups to detect the movement of the turbine blades the wiring must be made as following CI 420 Terminal...

Страница 4: ...ct the four significant digits and with the jumper we select the position of the decimal point To get to the switches a screwdriver can be used to lever out the top cover which is just clipped in its...

Страница 5: ...ent is configured for a COVOL input and 4 20 mA output The JP1 and JP2 jumpers are used to configure the type of input and should not be moved The jumpers JP3 JP4 JP5 JP6 are used to configure the typ...

Страница 6: ...e 5 3 Analog Output The analog output is configured internally for current or voltage output Current Output Maximum Load 600 ohms Voltage Output Minimum Load 10 000 ohms 5 4 Pulse inputs 1 The input c...

Страница 7: ...owing drawings the outside dimensions and the layout of the fastening holes for screws are given The layout of the fastening holes is given looking at the top of the instrument The weight of the instr...

Страница 8: ...ed in the order the result of service or modification by un authorized persons bad handling or accident This warranty is limited to cover the repair or replacement defective parts which have not been...

Отзывы: