IMPORTANT

 : In order to comply with the safety requirements as per IEC 1010-1, a  mains 

switch must be provided to disconnect the equipment. This switch must be marked as the 
disconnecting device for the equipment and be within easy reach of the operator. The equipment 
must be installed inside an electrical mounting cabinet to avoid the possibility that the operator 
may touch a connection terminal. 

2.2 Input connection

       The CI-420 is designed to be able to work with two types of inputs.  

2.2.1 Pick-up Input

 For the input from turbine type flowmeters which use magnetic inductive pick-ups to detect 
the movement of the turbine blades, the wiring must be made as following: 

                                CI-420 Terminal N

o

.                      Pick-up Terminal N

o

.

                                          14 shield                                        1 shield 
                                          15 live                                              2 live 
                                          16 live                                              3 live 

              "live" means the two ends of the pick-up coil. 

 The input cables must not be installed close to mains cables as these can induce 
errors due to electrical interferences. 

2.2.2 Electrical contact input

 For connecting inputs from reed switches etc., as one can find for example in COVOL 
flowmeters, the wiring must be made as following:  

                                CI-420 Terminal N

o

.                      COVOL Terminal N

o

.

                                          14 shield                                        1 shield 
                                          15 no connection                            
                                          16 live                                              2 live 

Содержание CI-420

Страница 1: ...t input 3 2 3 Analog output connection 4 2 4 Pulse output connection 4 3 SETTING UP 4 4 CONFIGURATION 5 5 TECHNICAL CHARACTERISTICS 6 5 1 Working conditions 6 5 2 Mains supply 6 5 3 Analog output 6 5...

Страница 2: ...voltage outputs to obtain the following voltage outputs Beginning of Scale Full Scale 0 V 5 V 0 V 10 V 1 V 5 V 2 V 10 V The value of fr the full scale frequency is selected by means of four BCD switc...

Страница 3: ...2 2 1 Pick up Input For the input from turbine type flowmeters which use magnetic inductive pick ups to detect the movement of the turbine blades the wiring must be made as following CI 420 Terminal...

Страница 4: ...ct the four significant digits and with the jumper we select the position of the decimal point To get to the switches a screwdriver can be used to lever out the top cover which is just clipped in its...

Страница 5: ...ent is configured for a COVOL input and 4 20 mA output The JP1 and JP2 jumpers are used to configure the type of input and should not be moved The jumpers JP3 JP4 JP5 JP6 are used to configure the typ...

Страница 6: ...e 5 3 Analog Output The analog output is configured internally for current or voltage output Current Output Maximum Load 600 ohms Voltage Output Minimum Load 10 000 ohms 5 4 Pulse inputs 1 The input c...

Страница 7: ...owing drawings the outside dimensions and the layout of the fastening holes for screws are given The layout of the fastening holes is given looking at the top of the instrument The weight of the instr...

Страница 8: ...ed in the order the result of service or modification by un authorized persons bad handling or accident This warranty is limited to cover the repair or replacement defective parts which have not been...

Отзывы: