1 Introduction 

3 Measurements 

3.3 Power 

Each successive press of the 

button select a new range: 

This document provides operating, maintenance and installation 
instructions. This unit measures and displays the characteristics 
of Single Phase Two Wire (1P2W), Three Phase Three Wire 
(3P3W) and Three Phase Four Wire (3P4W) networks. The 
measuring parameters include Voltage (V), Current (A), 
Frequency (Hz), Power (kW/KVA/KVAr), Power Factor (PF), 
Imported, Exported and Total Energy (kWh/kVArh).The unit also 
measures Maximum Demand Current and Power, this is 
measured over preset periods of up to 60 minutes. 

The buttons operate as follows: 

Selects the Voltage and Current display screens. In 
Set-up M

ode, this is the “Left” or “Back” button. 

Select the Frequency and Power factor display 
screens. In Set-

up Mode, this is the “Up” button. 

Select the Power display screens. 
In Set-

up Mode, this is the “Down” button. 

Select the Energy display screens. In Set-up mode, 
this is the “Enter” or “Right” button. 

Instantaneous Active 

Power in kW. 

User Manual 

DRS-CT-3P-MOD-2T 

DIN Rail Energy Meter for CT Connected 

Three Phase Electrical Systems 

DUAL TARRIF 

Instantaneous Reactive Power in 

kVAr. 

It also comes with a complete comms capability with built in 
Pulse and RS485 Modbus RTU outputs, configuration is 
password protected. 

3.1 Voltage and Current 

Each successive press of the 
parameter: 

button selects a new 

This unit is 1A or 5A current transformer operated. 
Auxiliary powered. 

Instantaneous Volt-Amps in KVA. 

1.1 Unit Characteristics 

Phase to neutral voltages. 

The DRS-CT-3P can measure and display: 

• Phase to Neutral Voltage and THD% (Total 

Harmonic Distortion) of all Phases 

• Line Frequency 
• Current, Maximum Demand Current and Current 

THD% of all Phases 

• Power, Maximum Power Demand and Power Factor 
• Imported, Exported & Total Active Energy 
• Imported, Exported & Total Reactive Energy 

Total kW, kVArh, kVA. 

Phase to Line voltages 

3.4 Energy Measurements 

Each successive press of the 

button selects a new range: 

Current on each phase. 

The unit has a Password-Protected set up menu for: 

• Changing the Password 
• System Configuration - 1P2W, 3P3W, 3P4W. 
• Demand Interval Time 
• Reset for Demand Measurements 
• Pulsed Output Duration 

Voltage THD% per phase 

1.2 RS485 Serial 

– Modbus RTU 

RS485 serial port with Modbus RTU protocol to provide a means 
of remotely monitoring and controlling the Unit. Set-up screens 
are provided for setting up the RS485 port. Refers to section 4.8. 

Current THD% per each phase. 

1.3 Pulse output 

Two pulsed outputs that can be set for active (kWh) or reactive 
(kVArh) energy. 

3.2 Frequency and Power Factor and Demand 

Each successive press of the 

button selects a new range: 

2 Start Up Screens 

The first screen lights up all 
display segments and can be used 
as a display check. 

Frequency and Power 

Factor (total). 

The second screen indicates the 
firmware installed in the unit and 
its build number. 

Power Factor of each phase. 

Please note: Values may vary from 
the numbers shown here. 

Maximum Current 

Demand. 

The interface performs a self-test 
and indicates the result if the test 
passes. 

Maximum Power Demand. 

*After a short delay, the screen will display active energy 
measurements. 

 

Caution: Risk of 

Warnings 

Electric Shock 

 

During  normal  operation,  voltages  hazardous  to  life 
may be present at some of the terminals of this unit. 

 

At voltages below that specified in the Range of Use 
the  meter  may  shut  down.  However,  voltages 
hazardous to life may still be present at some of the 
terminals of this unit. 

 

Installation  and  servicing  should  be  performed  only 
by  qualified,  properly  trained  personnel  abiding  by 
local regulations. 

 

Ensure  all  supplies  are  de-energised  before 
attempting connection or other procedures. 

 

Terminals  should  not  be  user  accessible  after 
installation and external installation provisions must 
be  sufficient  to  prevent  hazards  under  fault 
conditions. 

 

This  unit  is  not  intended  to  function  as  part  of  a 
system providing the sole means of fault protection - 
good  engineering  practice  dictates  that  any  critical 
function be protected by at least two independent and 
diverse means. 

 

The  unit  does  not  have  internal  fuses  therefore 
external fuses must be used for protection and safety 
under fault conditions. 

 

Never  open-circuit  the  secondary  winding  of  an 
energized current transformer. 

 

This product should only be operated with the CT 
secondary connections earthed. 

 

If this equipment is used in a manner not specified by 
the  manufacturer,  protection  provided  by  the 
equipment may be impaired. 

Tariff 1 active energy in kWh. 

Total active energy in kWh. 

Please note the register is 9999999.9 display over two lines. 
 
Date and Time can only be set via Modbus 

Tariff 2 active energy in kWh. 

Total reactive energy in kVArh. 

Tariff 1 reactive energy in kWh. 

Tariff 2 reactive energy in kWh. 

 