background image

4.5 Supply System 

supplies). 

• Percentage voltage THD% between phases 

(three phase supplies only). 

• Current 100A (Direct connected) 
• Continuous Overload current 120% 
• Current THD% for each phase. 
• Burden <10VA (nom 2VA) 
• Self powered from any phase 

Use 

and 

to set the first 

The unit has a default setting of 3Phase 4wire (3P4). 

Use this 

section to set the type of electrical system. 

digit and press 

to confirm 

your selection. The next digit will 
flash. 
Repeat the procedure for the 
remaining three digits. 

From the set-up menu, use 

and 

buttons to select the 

system option. 

5.1.2 Power factor and Frequency and Max. Demand 

The screen will show the currently 
selected power supply. 

• Frequency in Hz 
• Instantaneous power: 
• Power 0 to 3600 MW 
• Reactive power 0 to 3600 MVAr 
• Volt-amps 0 to 3600 MVA 
• Maximum demanded power since last Demand 

reset Power factor 

• Maximum neutral demand current, since the last 

Demand reset (for three phase supplies only) 

After setting the last digit, SET will 
show. 

Press 

to enter the selection 

routine. The current selection will 
flash. 

Use 

and 

buttons to 

Press 

to exit the number setting routine and return to the 

select the required system option: 
1P2(W),3P3(W), 3P4(W). 

Set-up menu. SET will be removed. 

5.1.3 Energy Measurements 

4.8 DIT Demand Integration Time 

• Imported/Exported active 

energy 

• Imported/Exported 

reactive energy 

• Total active energy 
• Total reactive energy 

0 to 9999999.9 kWh 

This sets the period in minutes over which the current and power 
readings are integrated for maximum demand measurement. The 
options are: off, 5, 10,15 30,60 minutes. 

Press 

to confirm the 

0 to 9999999.9 kVArh 

selection. SET indicator will 
appear. 

0 to 9999999.9 kWh 
0 to 9999999.9 kVArh 

From the set-up menu, use 

5.2 Measured Inputs 

and 

buttons to select the DIT 

Press 

to exit the system selection routine and return to the 

Voltage inputs through 4-way fixed connector with 2.5mm² 
stranded wire capacity. Single phase two wire(1p2w), three 
phase three wire(3p3w) or three phase four wire(3p4w) 
unbalanced. Line frequency measured from L1 voltage or L3 
voltage. 

option. The screen will show 

menu. SET will disappear and you will be returned to the main 
set-up Menu. 

the currently selected integration 
time. 

4.6 CLR 

Press 
routine. 

to enter the selection 

The meter provides a function to reset the maximum demand 
value of current and power. 

5.3 Accuracy 

The current time interval will flash. 

• Voltage 
• Current 
• Frequency 
• Power factor 
• Active power (W) 
• Reactive power (VAr) 
• Apparent power (VA) 
• Active energy (Wh) 
• Reactive energy (VARh) 
• Total harmonic 

distortion 

• Response time to 

step input 

0·5% of range maximum 
0·5% of nominal 
0·2% of mid-frequency 
1% of unity (0.01) 
±1% of range maximum 
±1% of range maximum 
±1% of range maximum 
Class 1 IEC 62053-21 
±1% of range maximum 
1% up to 31st harmonic 

From the set-up menu, use 

Use 

and 

buttons to select the time required. 

and 

buttons to select the 

reset option. 

Press 

to enter the selection 

Press 

to confirm the 

routine. The dIt will flash. 

selection. SET indicator will 
appear. 

1s, typical, to >99% of 
final reading, at 50 Hz. 

5.4 Interfaces for External Monitoring 

Press 

to confirm the setting and press 

to return to 

Press 
menu. 

to exit the DIT selection routine and return to the 

the main set up menu. 

Three interfaces are provided: 

4.7 Change Password 

• RS485 communication channel that can be 

programmed for Modbus RTU protocol 

• Relay output indicating real-time measured energy. 

(configurable) 

• Pulse output 400imp/kWh (not configurable) 

5 Specifications 

5.1 Measured Parameters 

Use the 

and 

to choose the change 
password option. 

The unit can monitor and display the following parameters of a 
single phase two wire (1p2w), three phase three wire (3p3w) or 
three phase four wire (3p4w) system. 

The Modbus configuration (baud rate etc.) and the pulse relay 
output assignments (kW/kVArh import/export etc.) are configured 
through the set-up screens. 

5.1.1 Voltage and Current 

Press the 

to enter the 

change password routine. The 
new password screen will appear 
with the first digit flashing. 

5.4.1 Pulse Output 

• Phase to neutral voltages 100 to 289V a.c. 

(not for 3p3w supplies). 

• Voltages between phases 173 to 500V a.c. 

(3p supplies only). 

• Continuous Overload voltage 120% 
• Percentage total voltage harmonic distortion 

(THD%) for each phase to N ( not for 3p3w 

Opto-coupler with potential free SPST-NO Contact 
(Contact range 5-27VDC / Max current input: Imin 2mA and Imax 
27mA DC). The pulse output can be set to generate pulses to 
represent kWh or kVArh. 

4.9 CT Ratio 

The CT option sets the secondary current (CT2 1A or 5A)  of the 
current  transformer  (CT)  that wires  to  the meter  and the ratio  to 
the primary current. 

From the set-up menu, use 

and 

buttons to select the 
secondary CT menu. 

Press 

to enter the CT 

Secondary value. 5A/1A 

Press 

to enter the CT 

Ratio

 

The range is 0001 to 9999. 
The value is entered as a RATIO of the 
primary and secondary current. 

CT RATIO 
For example, if using a 100/5A current transformer you would 
enter 0020 on this screen. 

4.10 PT Ratio 

The PT option sets the secondary voltage (PT2 100 to 500V)  of 
the voltage transformer (PT) that wires to the meter. 

From the set-up menu, use 

and 

buttons to select the secondary PT 
menu. The default value is 400V 

Press 

to enter the PT 

secondary voltage. The range is 100 to 
500V L-L 

Press 

to enter the PT 

RATIO

 

RATIO. 

The range is 0001 to 9999. 
The value is entered as a RATIO of the 
primary and secondary voltage. 

PT RATIO 
For  example,  if  using  a  8,000/400V  voltage  transformer  you 
would enter 0020 on this screen. 

 

Отзывы: