5.6 Daisy-Chain Connection
It is possible to configure a multiple power supply system to shut down all units when a fault
condition occurs in one of the units. When the fault is removed, the system recovers according to
a preset state: Safe start mode or Automatic restart.
Set signal “
SO
” to positive logic via Front panel (refer to section 5.7.1) . If a fault occurs in one of
the units it’s “PS_OK” signal will be set to low level and the display will indicate the fault. The other
units will shut off and their displays will indicate “
SO
”. When the fault condition is removed, the
units will recover to their last setting according to their respective Safe start or Auto-restart setting.
Fig.5-6 shows connection of three units, however the same connection method applies to systems
with more units.
Fig.5-6: Daisy-Chain connection
P OWE R S UP P LY
#1
J 3-7
J 3-2
J 3-5
IF C _C OM
P S _OK
S O
P OWE R S UP P LY
#2
J 3-7
J 3-2
J 3-5
IF C _C OM
P S _OK
S O
P OWE R S UP P LY
#3
J 3-7
J 3-2
J 3-5
IF C _C OM
P S _OK
S O
5.7 Rear Panel (J3 Connector) Functions and Settings
Subsystem
Level
Display
Function
Level
Display
Parameter Level
Display
Description
Rear Panel
R.AN
Interlock
IC
Enable (ON)
O
Enable/Disable
iner- lock
function (Analog
ON/OFF)
Disable (OFF)
OFF
Shut OFF
SO
Positive
OS
Positive (polarity)
same such PS_OK
signal
Negative
NEG
Programmed
PIN 1
i1
High
Hi
Open collector
Low
o
Programmed
PIN 2
i2
High
Hi
Open collector
Low
o
Table 5-3: Rear panel subsystem menu
Содержание Z+ series
Страница 4: ......
Страница 5: ......
Страница 27: ...26 2 4 Z200W 400W Outline Drawing...
Страница 28: ...27 2 5 Z200W 400W Optional IEEE Isolated Analog Interface Outline Drawing...
Страница 29: ...28 2 6 Z200W 400W Front Panel Output Binding Post Outline Drawing...
Страница 134: ...NOTES...
Страница 135: ...NOTES...
Страница 136: ...NOTES...
Страница 137: ...NOTES...