TPF45000-385
POWER SUPPLY
OPERATION MANUAL
21
3 February 2022
READ_ENA_STATUS
This Command is used to determine which of the 10 modules inside the TPF45000-385 set the
Output Enabled/Output
Disabled (ENA) Bit in the “STATUS REGISTER”.
Command Used
Type
#Data bytes
DEh
Read Word
2
Module in Disable Mode is indicated by “1”.
Module
Bit # in
1
st
Byte
Meaning
1
0
Vout of Module #1 Disabled
2
1
Vout of Module #2 Disabled
3
2
Vout of Module #3 Disabled
4
3
Vout of Module #4 Disabled
5
4
Vout of Module #5 Disabled
6
5
Vout of Module #6 Disabled
7
6
Vout of Module #7 Disabled
8
7
Vout of Module #8 Disabled
Module
Bit # in
2
st
Byte
Meaning
9
0
Vout of Module #9 Disabled
10
1
Vout of Module #10 Disabled