Introduction

The 4008/4006-9801 Expansion Power Supply (EPS) is an option module 
that installs into the main fire alarm control panel. The EPS provides two 
additional NACs, and filtered/regulated 24 VDC, alarm power.

The 3 A alarm power may be split between the two NACs and the 
0.5 A auxiliary 24 VDC power tap. Refer to the NAC ratings section of these 
instructions for circuit loading restrictions. The expansion power supply is 
mounted to the right of the main system board (MSB) at the bottom of the 
chassis, and is connected by the installer via three separate harnesses.

One EPS per system is allowed.

Figure 1, below, is an illustration of the EPS assembly.

The EPS assembly is shipped with the following:

EPS assembly (bracket with two PCBs)

Screws/washers (441-002; qty: 2)

AC harness (734-179): black/white leads

Battery harness (734-180): red/black leads

Data flex harness (166-438): flat cable 

Note: 

This document contains instructions on installing the EPS into the fire 

alarm control panel. For programming instructions, refer to the 

Front Panel 

Installing, Operating, and Programming Instructions

  (579-704 for 4006, or 

579-716 for 4008).

 Figure 1  The Expansion Power Supply

Specifications

General

System 
Compatibility

4006/4008 Fire Alarm System

Operating 
Temperature

0 to 49 degrees C
32 to 120 degrees F

Operating 
Humidity

Up to 93% relative humidity 
(non condensing)

Mounting

Dimensions

Width = 4.38 in ( 11.2 cm)
Height = 7 in (17.8 cm) 
Depth = 4 in (10.2 cm)

Power

Current 
Rating

2 A  per NAC; 3 A.alarm power 
@ 24 VDC

AC Input 
Voltage

120 V, 60Hz, 2 A max
240 V, 50 Hz, 1.5 A max

Expansion Power Supply (EPS)

 Installation Instructions

In this Document

Mounting .........................................2
Panel interconnections ...................3
NAC wiring......................................5
Auxiliary 24 V wiring .......................6
NAC ratings .................................... 7

Technical Manuals Online! - http://www.tech-man.com

Summary of Contents for 4008-9801

Page 1: ...PS assembly bracket with two PCBs Screws washers 441 002 qty 2 AC harness 734 179 black white leads Battery harness 734 180 red black leads Data flex harness 166 438 flat cable Note This document contains instructions on installing the EPS into the fire alarm control panel For programming instructions refer to the Front Panel Installing Operating and Programming Instructions 579 704 for 4006 or 57...

Page 2: ...s Mounting Mount the EPS to the main annunciation cabinet as shown in the figure below Figure 2 Mounting the EPS Fasten the EPS to the cabinet with two slotted torx screws 441 002 EPS MAIN CABINET Screwholes Technical Manuals Online http www tech man com ...

Page 3: ...or 4008 3 Connect the data flex harness 166 438 from J1 on the EPS to J8 on the 4006 9801 J3 on the 4008 9801 4 The AC harness 734 179 is used to connect AC power from the MSB to the EPS AC source is 120 VAC 60 Hz single phase or 240 VAC nominal 50 Hz single phase Strip 3 8 insulation from the black and white wires Connect the black wire lead to the LEFT MSB AC power terminal TB4 marked LINE Conne...

Page 4: ...N TB4 RIGHT ON P6 TINTED AREA PORTION OF BOTTOM BOARD OBSCURED BY TOP OF ASSEMBLY REMOVE POWER FROM AC AND BATTERY TERMINALS AND FROM EXPANSION POWER SUPPLY R76 DEPLETED BATTERY CUTOUT JUMPER CIRCUIT BREAKER BEFORE WIRING THE WHITE RIGHT ON TB4 LEFT ON P6 BLACK RIGHT ON P13 P14 ON P3 TOP ON P3 J3 on 4008 J8 on 4006 DEPLETED BATTERY CUTOUT JUMPER R407 on 4008 R313 on 4006 MAIN SYSTEM BOARD P14 on 4...

Page 5: ...122 F Alarm Current Amps Max Distance from Panel to Last Device Feet Line Resistance Ohms 18 AWG 16 AWG 14 AWG 12 AWG 0 25 840 1335 2126 3382 12 0 50 420 667 1063 1691 6 0 75 280 445 709 1127 4 1 00 210 334 532 845 3 1 25 168 267 425 676 2 4 1 50 140 222 354 564 2 1 75 120 191 304 483 1 71 2 00 105 167 266 423 1 5 CLASS B WIRING CLASS A WIRING TYPICAL AUDIBLE VISIBLE APPLIANCES B B A A B B A A A A...

Page 6: ...610 9111 4606 9101 Annunciators If wiring is routed outside the building use of a listed secondary protector is required Use 2081 9044or 2081 9028 A protector must be installed at each building exit entrance Each 2081 9044 adds 6 Ohms resistance at 200 mA Each 2081 9028 adds 0 2 Ohms wiring resistance and is rated for more than the 0 5 A aux 24 V capacity If the circuit is used to power the Model ...

Page 7: ...e per NAC All other regulated 24 VDC synchronized notification appliances require the use of their associated Listed external synchronization module Notification Circuit rating is 1 5 A maximum 1 35 A maximum strobe load per power supply Table 1 NAC Ratings 15Cd 30Cd 75Cd 110Cd 4906 Rated Current Max per NAC Rated Current Max per NAC Rated Current Max per NAC Rated Current Max per NAC 9101 0 060 3...

Page 8: ...ges or modifications to this unit not expressly approved by the party responsible for compliance could void the user s authority to operate equipment NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is op...

Reviews: