22
Supply (*1)
Full Scale (*1)
RFE1600-12
15V
RFE1600-24
30V
RFE1600-32
40V
RFE1600-48
60V
5.3.2
Monitoring Output Current (READ_IOUT)
The accuracy of the current reading is +/-10%
The read back output current can be calculated using the “Direct data Format”.
Refer to Table 5-1 for the Coefficients for calculating the Output Current.
Command Used
Type
#Data Bytes
8Ch
Read Word
2
Example:
Hex read back = 0361h;
Converted to Decimal = 865;
Using the required coefficients the output current = 865x1000/25575 = 33.82A;
Read the actual Output current (Ex: 33.05A) / Accuracy is (33.05-33.82)/40(*1)x100 = -1.92%.
Supply (*1)
Full Scale (*1)
RFE1600-12
160A
RFE1600-24
80A
RFE1600-32
60A
RFE1600-48
40A
5.3.3
Monitoring Supply Temperature (READ_TEMPERATURE_1)
The accuracy of the Temperature reading is +/-3
℃
The read back supply temperature can be calculated using the “Direct data Format”.
Please refer to Table 5-1 for the Coefficients for calculating the Supply Temperature.
Command Used
Type
#Data Bytes
8Dh
Read Word
2
Example:
Hex read back = 01DCh;
Converted to Decimal = 476;
Using the required coefficients the Supply Internal Temperature = 476*100/1023 = 46.53
℃
.
5.3.4
Programming Output Voltage (VOUT_COMMAND)
The accuracy of the Output Voltage Programming is +/-2%
The output Voltage can be programmed using the “Direct data Format”.
Please refer to Table 5-1 for the Coefficients to be used for calculating the Voltage Programming.
Command Used
Type
#Data Bytes
21h
R/W Word
2
Example:
Power Supply RFE1600-24;
To program the Output Voltage to 24V, send ((-15360))/10 = 511 (DEC);
Read the actual set output Voltage (Ex: 24.05V) / Accuracy is (24.05-24)/30(*1)x100 = 0.16%.
Supply (*1)
Full Scale (*1)
RFE1600-12
15V
RFE1600-24
30V
RFE1600-32
40V
RFE1600-48
60V