Programming and Monitoring Functions
For Monitoring and Programming functions use the following equation. This is the direct data format.
𝑌 = (𝑚𝑋 + 𝑏) ∗ 10
𝑅
,
𝑋 =
(𝑌∗10
−𝑅
−𝑏)
𝑚
Where
Y - digital value sent or received from the supply.
X is the normal value (V, A, °C)
m, b, R - coefficients that are explained in
Table 5-1
.
Voltage (V)
Physical value
Physical Unit
Min. Value
Max. Value
m
b
R
48
Voltage Programming
V
38.4
58
426
-15335
-1
Voltage monitoring
V
0
60
1705
0
-2
Current monitoring
A
0
40
25575
0
-3
Temperature monitoring
℃
0
100
1023
0
-2
32
Voltage Programming
V
28.8
38.4
639
-15333
-1
Voltage monitoring
V
0
40
25575
0
-3
Current monitoring
A
0
60
1705
0
-2
Temperature monitoring
℃
0
100
1023
0
-2
24
Voltage Programming
V
19.2
29
853
-15360
-1
Voltage monitoring
V
0
30
341
0
-1
Current monitoring
A
0
80
12787
0
-3
Temperature monitoring
℃
0
100
1023
0
-2
12
Voltage Programming
V
9.6
13.2
1705
-15345
-1
Voltage monitoring
V
0
15
682
0
-1
Current monitoring
A
0
160
6394
0
-3
Temperature monitoring
℃
0
100
1023
0
-2
12,24,32,48
Current Programming
%
50
110
146
-5830
-1
Table 5-1: Coefficients Table
m, b, R coefficients can also be recovered from the EEPROM.
Coefficients are stored in ASCII Format.
Command Name
Command Code
Type
#Data Bytes
MFR_VOLTAGE_MON_COEFF
D2h
Read Block
16
MFR_CURRENT_MON _COEFF
D3h
Read Block
16
MFR_TEMP_MON_COEFF
D4h
Read Block
16
MFR_VOLTAGE PROG_COEFF
D5h
Read Block
17
MFR_CURRENT_ PROG_COEFF
D7h
Read Block
16
5.3.1
Monitoring Output Voltage (READ_VOUT)
The accuracy of the voltage reading is +/-2%
The output voltage is read before the ORING Circuit (~50mV Voltage drop @ load, no drop @no load).
The read back Output Voltage can be calculated using the “Direct data Format”.
Refer to Table 5-1 for the Coefficients for calculating the Output Voltage.
Command Code
Type
#Data Bytes
8Bh
Read Word
2
Example:
Power Supply RFE1600-48;
Hex read back = 032Ch;
Converted to Decimal = 812;
Using the required coefficients the Output Voltage 812x100/1705 = 47.62V.
Read the Actual Output Voltage on the Output Bus Bar (Ex: 47.90V). Add 0.05V to compensate O-Ring
Circuit drop.
So, the actual voltage is (Ex: 47.90 + 0.05 = 47.95V).
Accuracy is (47.95-47.62)/60(*1) x100 = 0.55%