Faults Section
This section displays the selected power supply’s Fault register. If any fault occurs,
the “Fault” LED will lit. It will be required to scan all the supplies in the chain to
check which of the supply has generated the fault. If the supply is found, the
respective fault LED will be lit.
Indicator
Faults
DC
DC Fail
OTP
Over Temperature Protection
OTA
Over Temperature Alarm
FAN
Fan Fail
AC
AC Fail
OVP
Over Voltage Protection
PVA
Programmed Voltage more than Allowed
CE
Command Error
Table 8. Faults Indicator
Clear Faults: If any of the fault occurs, the fault will get registered in the fault
register. It will not be cleared even if the fault is not present. With this button, the
fault register can be cleared. If the fault is present after the “Clear Faults” button
is clicked, the fault will be registered again in the fault register.
5.4.2 DC Power
➔
Group Page
Fig 6. Group Page