Login: Click the “Login” button at the bottom-left side of the web page. Enter “admin” in the user
name box. By default, password is empty. Click “Login”.
A user may logout by clicking the “Logout” button, by closing the web browser or by leaving the
web browser idle for “LAN Keep-alive” seconds.
The password may be set or changed on the LAN -> Users web page (see section 5.5.6). A front
panel LAN reset or a LAN Specific command will clear the password.
Check to Modify: Click this button to make the changes. If this button is not clicked, no changes
can be made.
After the changes are made, de-select the button.
Output: Click the On/Off button to make the Power Supply On or Off.
Voltage / Current Setting: In the case of HFE2500 supply, two programming buttons will be
seen – Voltage and Current. For first time entry in the Output section, the Voltage/Current setting
window will be blank. Click on Voltage or Current button to view the settings.
Enter the value in the window. Click “Apply”. Deselect “Check to Modify” button and the programmed
Voltage or Current setting will be seen in the Voltage/Current setting window.
Please refer to HFE User Manual (/S option) for the range of Voltage and Current programming
for each model (*1).
In the case of HFE1600 supply, there is voltage programming only, so only the voltage setting
will be seen in the Voltage/Current setting window.
Maximum Voltage Setting: Maximum voltage setting can be entered in the Max. Voltage setting
window. This is a protection window and will not allow programming voltage to go beyond the
value set in the window.
Supply
Maximum Voltage (*1)
12V
15V
24V
30V
32V
40V
48V
60V
Table 7. Maximum Voltage Setting Values
Ex - If the above value is set to 49V, the output voltage cannot be set above 49V.
If Current programming is selected, this value has to be at maximum.
Note - Any value programmed beyond the range will result in “Data out of Range” message on
the display.
If the current programming value is sent without the “%” sign, “Percentage Symbol missing” will
be seen on the display.
Note – If the “Check to Modify” button is not de-selected, the programmed values will not be seen
after a new value is set.
Settings through Web Page only: When this button is clicked, power supply settings and
LAN settings can be carried out via the web page only. Settings cannot be carried out via other
protocols. Only monitoring is available via other protocols.
The default setting is “disabled”.