- 24 -
TDK-Lambda
EZA11K series
Quick Manual / Basic
Parameter
Unit
Initial
Value
Lower
Limit
Upper
Limit
Note
Symbol
Name
CCD
Deviation of Volts
for Cancel
Warning of
Charging Upper
Limit
V
0
0
60
When Battery Volt<TBV-CUD-CCD,
Warning signal is canceled.
LBV
Limit of Battery
Volts for
Discharging
V
216
144
306
Set the limit of battery voltage for
discharging.
This parameter is used for Battery
over discharge protection. Set a
value larger than UBV.
DLD
Deviation of Volts
for Warning of
Discharging Lower
Limit
V
60
0
60
Set deviation of volts for warning of
discharging lower limit
、
When
Battery Volt<LBV+DLD, Warning
signal is outputted.
DCD
Deviation of Volts
for Cancel
Warning of
Discharging Lower
Limit
V
0
0
20
When Battery Volt
>LBV+DLD+DCD, Warning signal is
canceled.
UDZ
Upper Side Volts
for Dead Zone
V
0
0
20
Set plus side volts for dead zone.
When Grid voltage is between
TGV and TGV+UDZ, EZA do not
charge or discharge in Grid
Automatic CV mode.
LDZ
Lower Side Volts
for Dead Zone
V
0
0
20
Set minus side volts for dead zone.
When Grid voltage is between TGV
and TGV-LDZ, EZA do not charge
or discharge in Grid Automatic CV
mode.
CCF
Converter
Configure
Function
(Flag bit
assignment)
0
0
15*
bit0: Battery overcharge protection
function (0 disables, 1 enables)
bit1: Battery over discharge
protection function (Disabled by 0,
enabled by 1)
bit2: Battery bus ramping up
function (0 is invalid, 1 is valid)
bit3: Grid bus ramping up function
(0 is invalid, 1 is valid)
* If you enter more than 16, EZA will
be recognized as 15.